Grounding and Bonding for a Roof-Mounted CCTV System

Arizona Low Voltage Practice · Put your knowledge to work in context.

All case studies

Grounding and Bonding for a Roof-Mounted CCTV System

A security integrator is installing a 16-camera IP CCTV system on a new commercial building. The cameras are mounted on metal poles on the roof, and the cabling is run in PVC conduit to a network video recorder (NVR) in the IT room on the first floor. The building has a concrete-encased electrode (Ufer ground) as the grounding electrode system, with a measured resistance to ground of 4 ohms. The integrator plans to ground each camera pole with a separate 8-foot ground rod driven at the base of each pole, connected to the pole with a 6 AWG copper conductor. The NVR is plugged into a standard 120 V receptacle, and the integrator intends to bond the NVR chassis to a nearby water pipe for grounding. The roof has a lightning protection system (LPS) with air terminals and down conductors, but the integrator is not connecting to it. The local AHJ requires compliance with NEC Article 820 for CATV and Article 830 for network-powered broadband, but the CCTV system uses PoE (Power over Ethernet) from a switch. The building has a single grounding electrode system. The integrator has a copy of NEC 250.50 and 250.52.

1. Evaluate the integrator's grounding plan for the camera poles. Is using separate ground rods at each pole compliant and effective? What does NEC require for grounding multiple electrodes?

Read the worked answer

The integrator's plan to drive a separate 8-foot ground rod at each camera pole and connect it with 6 AWG copper is not compliant with NEC 250.50, which requires that all grounding electrodes present at a building or structure be bonded together to form a single grounding electrode system. Each ground rod is a grounding electrode, and they must be bonded to the building's grounding electrode system, not left isolated. Isolated ground rods can create potential differences between the poles and the building ground, leading to equipment damage or safety hazards during lightning or fault conditions. Additionally, the resistance of a single 8-foot rod may not be low enough (25 ohms or less per NEC 250.53(A)(2)), and multiple rods must be bonded together. The proper approach is to bond each pole's grounding conductor to the building's grounding electrode system using a conductor sized per NEC 250.66 (based on the service conductor size). The 6 AWG copper may be adequate for bonding if the service is not too large, but it must run to the building ground, not just to a local rod. Also, the presence of a lightning protection system means that the CCTV grounding should be bonded to the LPS per NFPA 780 to avoid side flashes. The integrator should connect the camera poles to the building's single grounding electrode system and ensure all connections are irreversible (exothermic welding or listed pressure connectors).

2. The integrator wants to bond the NVR chassis to a nearby water pipe. Is this acceptable? What are the requirements for bonding to interior metal water piping?

Read the worked answer

Bonding the NVR chassis to a nearby water pipe is generally not acceptable unless the water pipe is part of the grounding electrode system and has been properly bonded. NEC 250.104 requires that interior metal water piping systems be bonded to the grounding electrode system, but the pipe itself is not a grounding electrode unless it meets the criteria of 250.52(A)(1) (10 feet or more in direct contact with earth, etc.). Using a water pipe as an equipment grounding conductor is prohibited by NEC 250.121. The NVR chassis should be connected to an equipment grounding conductor (the green wire or conduit) that is part of the branch circuit, not to a water pipe. If the water pipe is used as a grounding electrode, it must be bonded to the service ground with a conductor sized per 250.66, and any bonding jumpers must be sized per 250.102. The integrator should plug the NVR into a properly grounded receptacle and ensure the rack is bonded to the equipment grounding conductor. If a separate grounding conductor is needed, it should be run to the grounding electrode system, not to a random water pipe. Additionally, bonding to a water pipe can cause galvanic corrosion and is not a reliable low-impedance path. The correct method is to use the building's equipment grounding system.