Arizona Low Voltage Practice flashcards
Arizona Low Voltage Practice · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's Law
- The relationship among voltage, current, and resistance in a circuit: E equals I multiplied by R. Rearranged, current equals voltage divided by resistance, and resistance equals voltage divided by current.
- Power Formula
- Electrical power in watts equals voltage multiplied by current. Substituting Ohm's Law gives P equals I squared times R, or P equals E squared divided by R.
- Series Circuit Rules
- In a series circuit the same current flows through every component, total resistance is the sum of individual resistances, and the voltage divides across components in proportion to their resistance.
- Parallel Circuit Rules
- In a parallel circuit the voltage is the same across every branch, branch currents add to give total current, and total resistance is found from the reciprocal sum of the branch resistances.
- Voltage Drop Formula
- For a two-wire circuit, voltage drop equals two times the resistivity constant K, times current, times one-way length in feet, divided by conductor area in circular mils.
- Circular Mil Definition
- A circular mil is the area of a circle one thousandth of an inch in diameter. Conductor area in circular mils equals the diameter in mils squared.
- Class 2 Circuit Limits
- Class 2 circuits are power-limited by a listed transformer or supply. NEC Chapter 9 Tables 11(A) and 11(B) set the maximum voltage and current for the circuit.
- NEC Article 725 Scope
- Article 725 governs Class 1, Class 2, and Class 3 remote-control, signaling, and power-limited circuits that are not part of a communications or fire alarm system.
- Plenum Cable Rating CMP
- CMP cable is listed for installation in ducts and plenum spaces used for environmental air. It has the lowest flame spread and smoke production of the copper cable ratings.
- Cable Substitution Rule
- A cable with a higher fire-resistance or circuit-integrity rating may replace a lower-rated cable in the same location, but a lower-rated cable may never replace a higher-rated one.
- Power and Signal Separation
- Class 2 and Class 3 cables must be kept at least two inches from electric light and power conductors unless a raceway, cable sheath, or permanent barrier provides separation.
- Twisted Pair Bend Radius
- Four-pair balanced twisted-pair cable must not be bent tighter than four times its diameter during installation, or eight times its diameter after installation is complete.
- Firestop Penetration Requirement
- Openings made through fire-rated walls or floors for cables must be sealed with a listed firestop system approved for that specific cable type and penetration arrangement.
- Bonding Versus Grounding
- Bonding intentionally connects metallic parts to form a conductive path that carries fault current. Grounding connects the system to earth. Bonding clears faults; grounding alone does not.
- Telecom Bonding Conductor Size
- NEC Table 800.100(A) sizes the telecommunications bonding conductor by length: 14 AWG copper up to 6 feet, 12 AWG up to 10 feet, and 6 AWG up to 18 feet.
- Primary Protector Requirement
- A listed primary protector is required where communications conductors enter a building, and it must be bonded to the building grounding electrode system near the entry point.
- GFCI Protection Locations
- Ground-fault circuit interrupter protection is required in bathrooms, kitchens, garages, outdoors, wet locations, and within six feet of sinks, per NEC Article 210.8.
- Equipment Grounding Conductor
- The equipment grounding conductor provides a low-impedance fault path back to the source. It must be continuous, connected to every enclosure, and sized per NEC Table 250.122.
- NFPA 72 Scope
- NFPA 72 is the National Fire Alarm and Signaling Code. It sets requirements for the installation, inspection, testing, and maintenance of fire detection and notification systems.
- Smoke Detector Spacing
- On a smooth ceiling, smoke detectors are spaced no more than 30 feet apart, with the first detector within 15 feet of any wall and at least 4 inches from it.
- Heat Detector Spacing
- Listed fixed-temperature heat detectors rated 135 to 174 degrees Fahrenheit are spaced up to 50 feet apart on smooth ceilings, reduced for high ceilings per NFPA 72 factors.
- Notification Appliance Circuit
- A notification appliance circuit supplies and supervises horns, strobes, and speakers. Voltage drop must be calculated so the last appliance receives its listed minimum operating voltage.
- Survivable Fire Alarm Cable
- Circuit integrity cable, marked CI, is listed to remain operational during a fire for a specified time and must be installed according to its listing conditions.
- Fail-Safe Versus Fail-Secure
- Fail-safe locks release when power is lost and are used on egress doors. Fail-secure locks stay locked when power is lost and are used where security outweighs egress concerns.
- Wiegand Interface
- Wiegand is a legacy access control signaling interface that sends credential data as pulses on data-zero and data-one lines, commonly in 26-bit to 40-bit formats.
- Power over Ethernet Standards
- IEEE 802.3af supplies up to 15.4 watts at the source, 802.3at up to 30 watts, and 802.3bt up to 60 or 90 watts, with lower power available at the device.
- Video Storage Calculation
- Storage in bytes approximately equals bit rate in bits per second times 3600 seconds per hour times recording hours, divided by eight, summed over all cameras and retention days.
- T568A and T568B Pinouts
- These are the two standard pin assignments for eight-position modular jacks. Either is acceptable, but the same standard must be used throughout a given cabling project.
- Horizontal Cabling Distance
- The permanent horizontal link is limited to 90 meters, or 295 feet. Adding patch cords at each end gives a maximum channel length of 100 meters, or 328 feet.
- Category Cable Frequencies
- Category 5e cable is rated to 100 MHz, Category 6 to 250 MHz, Category 6A to 500 MHz, and Category 8 to 2000 MHz over a limited 30-meter distance.
- Constant Voltage Audio Line
- A 70.7-volt or 100-volt distributed audio system places many speakers on one line. The sum of all speaker wattage taps must not exceed the amplifier's rated output.
- Arizona ROC License Number
- Arizona contractors must display their Registrar of Contractors license number on advertising, bids, and contracts. Unlicensed contracting is a criminal offense under state law.