AZ Roofing Contractor · Put your knowledge to work in context.

All case studies

Standing-Seam Metal Movement and Snow

A 120 ft long, 5:12 standing-seam metal roof is being installed on an unheated barn in a mountain town. Panels are 24-gauge steel, 16 in. wide, 42 ft long, with concealed clips. The roof has a valley, two chimneys, and a snow load of 60 psf. The crew fixed clips at every pan at both eave and ridge, installed panels tight against a ridge cap, and placed snow guards only in a single row 12 in. above the eave. After a cold snap, panels show oil-canning and some clip screws have backed out; snow slides off in large sheets onto a walkway.

1. Diagnose the oil-canning and fastener backout. What is the likely cause and the corrective principle?

Read the worked answer
  • The panels are restrained at both ends. For steel, thermal movement over 42 ft and a 100°F range is roughly 42 x 100 x 6.5e-6 = 0.027 ft, or about 0.33 in. If both eave and ridge clips are fixed, that movement has nowhere to go.
  • Restrained expansion and contraction can buckle the pan, cause oil-canning, and work screws loose. Tight panels against the ridge cap make it worse.
  • Corrective principle: use fixed clips at a single point or at the center, and floating clips with slotted holes elsewhere. Allow the panel to move at eaves and ridges; do not pin both ends.
  • Also check substrate flatness, clip engagement, and panel width. Oil-canning can be installation-related, but the fixed-both-ends detail is a primary cause here.

2. Evaluate the snow-guard layout for a 60 psf snow load and a 5:12 slope. What should be changed?

Read the worked answer
  • A single row 12 in. above the eave is not an engineered snow-retention layout for 60 psf. It may also be too low and too sparse to control sliding snow.
  • Snow guards must be laid out for the roof slope, snow load, panel type, and the locations where sliding snow creates hazard: above walkways, doors, valleys, chimneys, and lower roofs.
  • Use an engineered system, often continuous snow fences or multiple rows, with clamps or brackets approved by the panel manufacturer. Adhesive-only guards are not reliable for this load.
  • Protect the walkway below immediately; do not wait for the permanent snow-retention system.

3. What flashing and clearance details should be corrected at the valley and chimneys?

Read the worked answer
  • Use an open valley with a metal valley pan, proper underlayment, and panel edges held back to allow drainage and movement. Do not trap panel ends tightly in the valley.
  • At each chimney, install a cricket on the uphill side and proper counterflashing. Keep the metal roof clear of the masonry and use a compatible sealant only as a secondary detail.
  • Maintain manufacturer-required clearances and allow thermal movement at all terminations. Recheck roof penetrations and pipe boots for compatibility with the metal roof.
  • The goal is to shed water and snow without restraining the panels; every detail must accommodate movement.