Backflow Tester flashcards
Backflow Tester · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Cross-connection
- Any actual or potential physical link between a potable water supply and a source of nonpotable fluid or contaminant that could allow backflow into the drinking water system.
- Backsiphonage
- Backflow caused by negative or sub-atmospheric pressure in the supply piping, which draws nonpotable fluid into the potable system through a cross-connection.
- Backpressure
- Backflow caused when pressure downstream of a cross-connection exceeds the supply pressure, pushing nonpotable fluid backward into the potable water system.
- Pollution hazard
- A cross-connection condition that degrades water quality aesthetically or otherwise but does not create a health hazard, typically requiring only non-health-hazard protection.
- Contamination hazard
- A cross-connection condition introducing substances that create a health hazard, requiring the highest level of protection such as an air gap or reduced pressure assembly.
- Air gap
- A physical separation between the potable outlet and the flood-level rim of a receiving vessel; minimum is two times the effective opening, never less than one inch.
- Flood-level rim
- The elevation at which water would overflow the receiving vessel or fixture, used to set the required vertical separation for an air gap.
- Atmospheric vacuum breaker
- A non-testable device with an air inlet that opens on backsiphonage; it may not be under continuous pressure for more than 12 hours and has no downstream shutoff.
- Pressure vacuum breaker
- A testable assembly with a loaded air-inlet check that must be installed at least 12 inches above the highest downstream outlet and protects against backsiphonage only.
- Reduced pressure assembly
- A testable assembly with two independent checks and a differential relief valve that protects against both backpressure and backsiphonage for health hazards.
- Double check valve assembly
- A testable assembly of two independent check valves used only for non-health-hazard protection against both backpressure and backsiphonage.
- Spill-resistant PVB
- A pressure vacuum breaker design that limits water discharge from the air inlet when the device is fouled, allowing installation where flooding would otherwise be unacceptable.
- Hose-bibb vacuum breaker
- A small non-testable device threaded onto a hose bibb that opens an air inlet on backsiphonage and must not be under continuous pressure or have a downstream shutoff.
- Dual check valve
- A non-testable two-check device used only for low-hazard protection, commonly at the meter or an appliance, and not accepted for health-hazard cross-connections.
- Test cock
- A small valved port on a backflow assembly used to connect test gauges and to bleed water so pressures at each check can be measured.
- Differential pressure check
- The pressure difference a check valve holds between its upstream and downstream sides, measured with a differential gauge to confirm the check seals properly.
- Static line pressure
- The supply pressure recorded at the upstream test cock with no flow through the assembly, used as the baseline for evaluating test results.
- Check 1 differential
- The pressure drop held across the first check of an assembly; a passing result requires it to remain at or above the specified minimum, commonly 1.0 psi.
- Check 2 differential
- The pressure drop held across the second check of a double check or reduced pressure assembly, measured separately and required to meet the minimum.
- Relief valve opening point
- The pressure differential at which the reduced pressure assembly relief valve begins to discharge, required to open at 2.0 psi or greater.
- Air-inlet opening point
- The differential pressure at which a pressure vacuum breaker air inlet opens to atmosphere, required to be 1.0 psi or greater on a passing test.
- High side connection
- The test gauge port connected upstream of the check being tested, so the gauge reads the higher of the two pressures during the measurement.
- Low side connection
- The test gauge port connected downstream of the check being tested, allowing the gauge to display the difference between upstream and downstream pressure.
- Gauge calibration
- Verification of test instrument accuracy against a known reference, required at least annually so recorded differentials are reliable and defensible.
- Test report contents
- Documentation including assembly make, model, size, serial number, location, static pressure, measured differentials or opening points, pass or fail, tester identity, and date.
- Failed assembly tag
- A notice placed on an assembly that fails testing, indicating it is out of service pending repair or replacement and notifying the purveyor and owner.
- Retest after repair
- A complete repeat of the assembly test performed after repair or replacement to confirm the device now meets all required differential and opening-point criteria.
- Continuous pressure limit
- The rule that an atmospheric vacuum breaker may not be subjected to supply pressure for more than 12 hours, since prolonged pressure can damage the air-inlet seal.
- Test sequence RP assembly
- Order of measurement for a reduced pressure assembly: check 1 differential, then check 2 differential, then the relief valve opening point.
- Bleed to open relief
- A test step in which the low-side gauge is slowly bled to reduce downstream pressure until the relief valve discharges, revealing the opening differential.
- Purveyor notification
- The requirement to report a failed or removed assembly to the water purveyor, typically within a set time, so the cross-connection program record stays current.
- Tester certification
- The credential, issued after written and practical examination, that authorizes a person to test backflow prevention assemblies and sign test reports.