Barbados Wireman Licence Exam study materials
Barbados Wireman Licence Exam study resources

Barbados Wireman Licence Exam cheat sheet

Barbados Wireman Licence Exam · Keep the key ideas within reach.

Quick reference

Electrical Theory and Fundamentals

  • Ohm's law: V = I × R; power: P = V × I = I²R = V²/R.

  • In a series circuit, current is constant; voltage divides in proportion to resistance.

  • In a parallel circuit, voltage is constant; current divides inversely with resistance.

  • Three-phase power (balanced): P = √3 × V_L × I_L × cos φ.

  • Conductor resistance: R = ρL/A; ρ is resistivity (Ω·m), L length (m), A cross-sectional area (m²).

  • AC impedance: Z = √(R² + X²); power factor = cos φ = R/Z.

  • Energy (kWh) = power (kW) × time (h); 1 kWh = 3.6 MJ.

  • For a sine wave, RMS = peak / √2 ≈ 0.707 × peak; average = 0.637 × peak.

Quick reference

Wiring Regulations and Code Requirements

  • Final circuits must be protected against overload and short circuit; protective device rating must not exceed conductor current-carrying capacity.

  • Socket-outlet circuits require 30 mA RCD protection where required by the applicable code (e.g., BS 7671).

  • Cable current-carrying capacity must be derated for ambient temperature, grouping, and thermal insulation.

  • Minimum cross-sectional area for lighting circuits is typically 1.0 mm² or 1.5 mm² copper, depending on code.

  • Earth continuity conductor sizing: for phase conductors ≤ 16 mm², the CPC is typically the same size; above 16 mm², a reduced size may be permitted.

  • Isolation and switching must break all live conductors; a neutral need not be switched if it is reliably at earth potential.

  • Voltage drop limits: typically 3% for lighting and 5% for other uses from the origin of the installation.

  • Every installation must have a means of isolation and a main protective device; discrimination between devices must be ensured.

Quick reference

Installation Practice and Workmanship

  • Cable bends must not be tighter than the manufacturer's minimum bending radius (often 4× cable diameter for fixed wiring).

  • Cables in walls must be run in safe zones (horizontal within 150 mm of ceiling, vertical within 150 mm of corners) or protected by earthed conduit.

  • Conductors must be terminated with compatible terminals; no strands may be cut away to fit a terminal.

  • Jointing is permitted only in accessible, enclosed, and approved enclosures; no joints in conduit runs without access.

  • Cable supports must be at intervals that prevent strain; typical maximum spacing is 300–400 mm for horizontal runs.

  • All exposed conductive parts must be bonded to the protective earth; bonding conductors must be continuous and mechanically protected.

  • Enclosures must maintain their IP rating after cable entry; unused openings must be sealed.

  • Colour coding: line conductors brown, neutral blue, protective earth green/yellow (harmonised).

Quick reference

Protection, Earthing and Bonding

  • Earthing system types: TN-S, TN-C-S, TT, IT; the type determines the protective device and RCD requirements.

  • Earth fault loop impedance Zs must be low enough to operate the protective device within the disconnection time (e.g., 0.4 s for 230 V final circuits).

  • Maximum disconnection times: 0.4 s for TN systems ≤ 32 A final circuits; 0.2 s for TT systems; 5 s for distribution circuits.

  • RCDs: 30 mA for additional protection; 100 mA or 300 mA for fire protection or selectivity.

  • Main protective bonding conductor size: ≥ 6 mm² for TN-C-S, ≥ 10 mm² for TN-S, or half the supply neutral if smaller.

  • Supplementary bonding resistance between exposed and extraneous conductive parts must be ≤ 0.05 Ω (or ≤ 0.1 Ω in some codes).

  • TT systems require an RCD because the earth fault loop impedance is too high for overcurrent devices.

  • Surge protective devices (SPDs) must be installed where required by the code and coordinated with the earthing system.

Quick reference

Inspection, Testing and Certification

  • Test sequence: visual inspection, continuity of protective conductors, continuity of ring final circuit conductors, insulation resistance, polarity, earth fault loop impedance, RCD operation, functional tests.

  • Insulation resistance test voltage: 500 V DC for circuits ≤ 500 V; minimum acceptable value 1 MΩ (some codes require ≥ 1 MΩ).

  • Continuity of CPC: resistance should be low and consistent with conductor length and size; typical values < 1 Ω for short runs.

  • Ring final circuit continuity: end-to-end resistance of line, neutral, and CPC should be within 0.05 Ω of each other.

  • Polarity test: verify that line is connected to the centre pin of sockets and that switches are in the line conductor.

  • Earth fault loop impedance test: measured Zs must be ≤ the tabulated maximum for the protective device and disconnection time.

  • RCD test: verify tripping time at IΔn and 5×IΔn; typical maximum times are 300 ms and 40 ms respectively.

  • Certification: Electrical Installation Certificate (EIC) for new work; Minor Works Certificate for small alterations; Periodic Inspection Report for existing installations.

Quick reference

Electrical Safety and Health at Work

  • Before work, isolate and lock off; prove dead with an approved voltage tester on all conductors.

  • Use of portable electrical equipment requires regular inspection and testing; Class I earthed, Class II double insulated.

  • Live working is permitted only when it is unreasonable to work dead and suitable precautions are taken (risk assessment, insulated tools, PPE).

  • First aid for electric shock: do not touch the casualty until isolated; call emergency services; commence CPR if trained.

  • Arc flash risk: maintain safe approach distances; use appropriate PPE (arc-rated clothing, face shield) for live work.

  • Safety signs: yellow triangle for warning, blue circle for mandatory action, red circle for prohibition.

  • Working at height: use ladders only for short-duration light work; scaffold or platform for longer tasks.

  • Report all electrical incidents and near misses; keep records of maintenance and testing.

Quick reference

Consumer Installations and Service Equipment

  • Consumer unit must be located in an accessible position; main switch must be clearly labelled.

  • Service head: supply authority's responsibility up to the meter; consumer's responsibility from meter onward.

  • Main protective device rating must be coordinated with the supply capacity and consumer unit busbar rating.

  • Meter tails must be sized according to supply current; typical 25 mm² for 100 A supply.

  • Earthing conductor from consumer unit to earth electrode must be protected against mechanical damage and corrosion.

  • Consumer unit requires a main switch, RCDs/RCBOs, and MCBs for final circuits; spare ways should be blanked.

  • Isolation of supply: main switch must disconnect all live conductors; a means of isolation for maintenance must be provided.

  • Labelling: each circuit must be identified; RCD test notice and earthing arrangement label must be present.