- Fixture unit
- A relative measure of the load a fixture places on a drainage or supply system; one water closet is about 3 drainage fixture units and 2.5 supply fixture units.
- Building drain
- The lowest horizontal pipe inside the building that receives soil and waste from stacks, running to the building sewer outside the foundation wall.
- Trap arm length
- The distance from a fixture trap weir to its vent connection; limited by pipe size, about 5 ft for 1.5 in and 6 ft for 2 in pipe.
- Static pressure loss
- Pressure drops 0.433 psi for every foot of elevation rise above the water source; one foot of water column equals 0.433 psi.
- Vent stack height
- A vent stack must extend at least 6 in above the roof and at least 12 in above any roof area within 10 ft when used for other purposes.
- Drain slope rule
- Drain pipe 2.5 in and smaller slopes at least 1/4 in per ft; 3 in and larger may use 1/8 in per ft but never less.
- Copper type K
- The thickest copper tube, used underground and for heavy-duty service where wall thickness and pressure resistance matter most.
- Copper type L
- Standard-weight copper tube used for interior water supply lines; a common choice for above-ground domestic water piping.
- CPVC pipe
- Chlorinated polyvinyl chloride rated for hot water up to about 200 F at reduced pressure; uses its own solvent cement, not PVC cement.
- Solvent cement joint
- Cut square, deburr, prime, apply cement to both surfaces, insert with a quarter turn, hold 30 seconds, and cure before testing.
- Dielectric union
- A fitting that separates dissimilar metals, such as copper and galvanized steel, to prevent galvanic corrosion at the connection.
- No-hub coupling
- A cast iron pipe joint using a neoprene gasket wrapped by a stainless steel band clamped with screws, replacing lead-and-oakum joints.
- Lead-free solder
- Solder required on potable water lines; heat the fitting rather than the solder and keep the joint dry while soldering.
- PEX tubing
- Flexible cross-linked polyethylene tubing used for water supply; use brass or copper fittings and follow manufacturer temperature and pressure ratings.
- Trap seal depth
- The water seal in a fixture trap must be at least 2 in and no more than 4 in deep to block sewer gas without causing slow drainage.
- Water closet flush volume
- Standard water closets use 1.6 gallons per flush; high-efficiency models use 1.28 gpf or less; urinals commonly use 1.0 gpf or less.
- Wet vent
- A vent that also serves as a drain for one or two fixtures on a single floor, provided it is one size larger than the drain it serves.
- Cleanout spacing
- Cleanouts are required at the base of each stack, at horizontal changes over 45 degrees, and at the building sewer, no more than 100 ft apart.
- Backwater valve
- A device required where the building drain is below the next upstream manhole, preventing sewage from backing up into the building.
- Drainage fixture units
- Load values per fixture: water closet 3, lavatory 1, bathtub 2, shower 2, kitchen sink 2, floor drain 2, washing machine 2, dishwasher 2.
- Vent above flood rim
- A vent must rise at least 6 in above the fixture flood-level rim before turning horizontal; horizontal vents slope back to the drain.
- Air gap
- The highest level of backflow protection, created by a physical separation between a water outlet and the flood-level rim of a receptacle.
- RPZ device
- A reduced-pressure zone backflow preventer used for high-hazard connections; a double check valve is only for low-hazard protection.
- Trench protective system
- Any trench 5 ft deep or more requires shoring, sloping, or shielding unless in stable rock; a competent person inspects daily.
- Soil sloping ratios
- Type C soil slopes 1.5 to 1, Type B slopes 1 to 1, and Type A slopes 3/4 to 1 horizontal to vertical for trench protection.
- Water heater relief valve
- Set at or below the tank pressure rating, piped full size to within 6 in of the floor or a drain, and never capped or plugged.
- Pressure test criteria
- Water piping is tested at 1.5 times working pressure but not less than 100 psi for at least 2 hours; DWV is tested to 10 ft of head or 5 psi.
- Estimating waste factor
- Add about 5 to 10 percent extra pipe and fittings to a material takeoff to cover cuts, errors, and normal installation waste.
- Labor unit
- An estimating value expressed in hours per fixture or per 100 ft of pipe; overhead and profit are added as a percentage on top.
- Confined space entry
- Before entry, test for oxygen, flammable gas, and toxic gas; keep an attendant outside and have a rescue plan ready.
- Galvanized steel pipe
- Steel pipe with a zinc coating joined by threaded fittings; connect to copper only through a dielectric union to prevent corrosion.
- Fixture drain size
- Minimum drains: water closet 3 in, lavatory 1.25 in, bathtub 1.5 in, and kitchen sink 1.5 in.