Leak Detection and F-gas Reporting on a Split System

Koeltechnicus Cat I · Put your knowledge to work in context.

All case studies

Leak Detection and F-gas Reporting on a Split System

You are servicing a 12 kW split air-conditioning system using R-410A. The system has a charge of 3.5 kg. During a routine leak check, you find a leak at a flare connection. The system has been operating for 6 years. The owner reports that the system has been losing cooling capacity gradually over the past year. You have a electronic leak detector and soap bubbles. The system is in a commercial office and is not accessible during business hours except for a short window on weekends. The owner is concerned about downtime and cost.

1. What steps should you take to comply with F-gas regulations regarding leak checking and reporting for this system?

Read the worked answer

First, determine the CO2 equivalent of the charge. R-410A has a GWP of 2088. The charge is 3.5 kg, so CO2e = 3.5 × 2088 = 7308 kg CO2e, which is 7.3 tonnes CO2e. This is above the 5 tonnes CO2e threshold, so the system must be leak checked at least every 12 months (or every 6 months if leak detection system installed? Actually for 5-50 tonnes, frequency is every 12 months; if leak detection system, every 24 months). Here no leak detection system, so annual leak check required. Since a leak was found, you must repair it. After repair, you must perform a follow-up leak check within one month. You must record the leak check and repair in the equipment logbook, including date, nature of leak, amount of refrigerant recovered and added, and identity of technician. If the leak cannot be repaired immediately, you must inform the owner in writing of the obligation to repair within a certain timeframe. Also, if the system has a leak that is not repaired within 14 days (or 30 days if a justified delay), you may need to recover refrigerant and not recharge until repaired. For reporting, if the charge is 5 tonnes CO2e or more, you must report to the authority if required by national regulations (in some countries, annual reporting). Ensure you use certified personnel and recover any refrigerant properly.

2. How would you plan the repair to minimize downtime and ensure compliance with leak checking after repair?

Read the worked answer

Plan to do the repair during the weekend window. Before the repair, isolate the refrigerant in the system or recover it if necessary. Since the leak is at a flare connection, you can tighten or remake the flare. After repair, evacuate the system and recharge with recovered refrigerant plus additional to correct charge. Then perform a follow-up leak check within one month, but since you are already there, do it immediately after repair. Use electronic leak detector and soap bubbles to confirm no leak. Record the repair and follow-up check in the logbook. If the system cannot be repaired immediately due to access, you must inform the owner in writing of the requirement to repair within 14 days and avoid adding refrigerant until repaired. Also, consider installing a leak detection system if it helps reduce check frequency, but not required here.