- Category I scope
- Certification level covering all refrigeration systems and any F-gas charge, including hermetic, permanently sealed and open systems; required for leak checks, recovery, charging, servicing and decommissioning.
- CO2e calculation
- Multiply the refrigerant charge in kilograms by the gas's GWP from the regulation's Annex. Example: 5 kg R-404A at GWP 3922 equals 19,610 kg CO2e, i.e. 19.6 t CO2e.
- Leak-check interval 5–50 t
- Systems with a CO2e charge between 5 and 50 tonnes must be leak-checked at least every 12 months; with a verified leak-detection system the interval becomes 24 months.
- Leak-check interval 50–500 t
- Systems charged with 50 to 500 t CO2e require leak checks at least every 6 months; a verified leak-detection system extends the interval to 12 months.
- Leak-check interval above 500 t
- Systems containing 500 t CO2e or more must be checked at least every 3 months; with a verified leak-detection system the interval is 6 months.
- Leak record retention
- Records of refrigerant quantities, CO2e, leak-check dates and results, and recovered or charged amounts must be kept for at least five years and shown on request.
- Recovery efficiency thresholds
- Before dismantling, recover at least 95% of the charge for systems of 10 kg or more, and 98% for hermetically sealed equipment, using certified recovery equipment.
- Reuse of recovered refrigerant
- Recovered F-gas may be reused only by certified undertakings after documented recycling or reclamation; otherwise it must be destroyed or delivered to an authorised handler.
- Certificate validity
- F-gas certificates are personal, tied to the holder, and valid for a limited period set by the national scheme, typically five years, after which reassessment or refresher training is required.
- GWP of common refrigerants
- Regulatory GWP values include R-404A 3922, R-410A 2088, R-134a 1430, R-32 675, R-407C 1774 and R-744 (CO2) 1; always use the current Annex values.
- Prohibited deliberate venting
- Deliberate release of fluorinated greenhouse gases to the atmosphere is prohibited; refrigerant must be recovered, and only trace amounts from service connections are tolerated.
- Certified company obligation
- Companies performing covered work must employ certified personnel and hold the necessary equipment; the certificate proves individual competence, not company authorisation.
- Superheat definition
- Superheat is the suction or evaporator outlet temperature minus the evaporating saturation temperature at the measured pressure; it proves the refrigerant is fully vapour before the compressor.
- Subcooling definition
- Subcooling is the condensing saturation temperature minus the liquid line temperature; it confirms the refrigerant is fully liquid before the expansion device.
- Typical TEV superheat
- A thermostatic expansion valve is normally set for 5 to 8 K evaporator superheat; too little risks liquid floodback, too much reduces evaporator capacity and raises discharge temperature.
- Triple evacuation procedure
- Evacuate below 1000 micron, break the vacuum with dry nitrogen, repeat at least twice, then evacuate to 500 micron or lower and perform a standing vacuum test.
- Standing vacuum test
- After evacuation to 500 micron, isolate the pump and observe the gauge for 10 to 15 minutes; a small stable rise indicates moisture or a leak needing investigation.
- Non-condensable symptoms
- Air or nitrogen in the system raises condensing pressure and discharge temperature while subcooling stays high; purge only with recovery equipment, never by venting refrigerant.
- Undercharge symptoms
- Insufficient charge shows low suction pressure, high superheat, bubbles in the sight glass, low subcooling and reduced capacity; locate and repair the leak before recharging.
- Nitrogen pressure testing
- Use dry, oxygen-free nitrogen only for strength and tightness tests, never oxygen or air; respect the system's maximum allowable pressure and test in stages.
- Brazing with nitrogen purge
- Pass dry nitrogen through the pipe while brazing to displace air and prevent internal oxidation scale, which can block expansion devices and damage the compressor.
- Electronic leak detection
- Electronic detectors locate small leaks at joints, valves and flare connections; confirm findings with soap solution or a pressure test before opening the circuit.
- Recovery cylinder filling limit
- Never fill a recovery cylinder above 80% of its capacity by weight of liquid, and label it with the refrigerant type and whether the contents are recycled or reclaimed.
- Pump-down and isolation
- Pump-down moves refrigerant into the receiver or condenser and isolates it before service; verify isolation valves hold and pressures are released before opening any joint.
- Three-phase compressor rotation
- Confirm correct rotation direction before charging; reverse rotation gives no oil pressure, high noise and possible immediate compressor damage on scroll and screw machines.
- High-pressure switch setting
- The high-pressure cut-out must be set below the system's maximum allowable pressure with adequate margin; verify cut-out and manual reset function during commissioning and maintenance.
- Oil management checks
- Check oil level, colour and acidity; dark or acidic oil indicates overheating or moisture, and oil must be replaced with the grade specified by the compressor manufacturer.
- Leak test before charging
- Pressure-test with nitrogen and evacuate to prove tightness before charging refrigerant; charging first hides leaks and wastes gas that must then be recovered.
- Condensing pressure control
- In low ambient conditions, fan cycling, speed control or flooding maintains minimum condensing pressure so the expansion device keeps sufficient pressure differential to feed the evaporator.
- Defrost termination control
- Defrost must terminate on temperature or pressure, not time alone, so the coil is cleared of frost without adding heat to the refrigerated space or flooding the compressor.
- Commissioning record content
- Record evaporating and condensing pressures, superheat, subcooling, compressor currents, switch settings and charge quantity; these baselines make later fault diagnosis reliable.
- Refrigerant cylinder handling
- Store cylinders upright, secured and below the specified temperature, keep caps fitted, and never heat with open flame; use only cylinders approved for the refrigerant type.