Diagnosing a Refrigeration System with High Superheat and Low Subcooling

Koeltechnicus Cat I · Put your knowledge to work in context.

All case studies

Diagnosing a Refrigeration System with High Superheat and Low Subcooling

A walk-in freezer using R-448A has a condensing unit with an air-cooled condenser. The system has a thermostatic expansion valve (TEV) with an external equalizer. The freezer is not maintaining temperature; it is running at -5°C instead of -18°C. The suction pressure is 0.5 bar gauge, and the discharge pressure is 12 bar gauge. The superheat at the evaporator outlet is 15 K, and subcooling at the condenser outlet is 2 K. The ambient temperature is 30°C. The evaporator fan is working. The system has a liquid line sight glass showing bubbles. The filter drier is not restricted. The compressor is a semi-hermetic reciprocating type. The system charge is 5 kg R-448A.

1. What are the possible causes of the symptoms, and how would you systematically diagnose the issue?

Read the worked answer

Symptoms: high superheat (15 K vs typical 5-8 K), low subcooling (2 K vs typical 5-10 K), bubbles in sight glass, low suction pressure, normal to high discharge? Discharge 12 bar gauge for R-448A at 30°C ambient: R-448A has a pressure-temperature relationship; at 30°C condensing, pressure should be around 12-13 bar gauge? Actually, check: R-448A at 30°C condensing is about 12.5 bar gauge? So discharge seems normal. Suction 0.5 bar gauge corresponds to about -20°C evaporating? That is low for -18°C room, but maybe due to high superheat. High superheat and low subcooling with bubbles indicate undercharge or restriction. Since filter drier is not restricted, likely undercharge. But could also be TEV overfeeding? No, high superheat means TEV is not feeding enough, so it could be TEV restricted or lost bulb charge, or low refrigerant charge. Also, could be a restriction in liquid line. Systematic: check sight glass for bubbles (indicates insufficient liquid). Check subcooling: low subcooling means not enough liquid in condenser, so undercharge or restriction. Check superheat: high superheat means not enough refrigerant in evaporator. So likely undercharge. Verify by checking charge: weigh in additional refrigerant and observe. Also check TEV: is it adjusted? Could be TEV bulb losing charge. Check for frost on liquid line? Not mentioned. Also, check compressor amps: low amps due to low mass flow. Check evaporator air flow: if low, superheat would be high but subcooling would be normal? Actually low airflow would cause low suction pressure and high superheat, but subcooling would be normal or high? Not sure. But bubbles in sight glass point to undercharge. So first, leak check and recharge. Also, check for non-condensables: would cause high discharge pressure and high subcooling, not low. So diagnosis: undercharge due to leak. Steps: leak check, repair, evacuate, recharge by weight, adjust TEV if needed.

2. If adding refrigerant does not resolve the issue, what other components would you investigate and why?

Read the worked answer

If adding refrigerant does not resolve, then the problem is likely a restriction or TEV malfunction. Investigate the TEV: check if the bulb is properly attached and insulated, check if the valve is stuck closed or partially closed, check superheat adjustment. Also, check for a restriction in the liquid line, such as a kinked line or a plugged filter drier (though stated not restricted, but could be partially). Check the liquid line solenoid valve if present. Also, check the evaporator for oil logging or ice buildup. Check the compressor valves: if worn, could cause low capacity, but would not cause bubbles in sight glass. Bubbles indicate insufficient liquid reaching TEV, so restriction upstream of TEV. Use temperature measurements along the liquid line to find a temperature drop indicating a restriction. Also, check the receiver if present: if receiver outlet is not submerged, could draw vapor. So systematically check each component.