BICSI Installer 1 cheat sheet
BICSI Installer 1 · Keep the key ideas within reach.
Standards, Codes, and Regulations
NEC Article 800 covers communications circuits; Article 770 covers optical fiber; Article 820 covers CATV and community antenna systems.
ANSI/TIA-568 defines commercial building cabling topology, media, and performance; 568.2 covers balanced twisted pair and 568.3 covers fiber.
ANSI/TIA-569 covers pathways and spaces; TIA-606 covers administration and labeling; TIA-607 covers bonding and grounding.
Horizontal channel = 90 m (295 ft) of horizontal cable + 10 m (33 ft) total patch cords = 100 m (328 ft).
Work area cord maximum length is 5 m (16 ft); total patch cord length in the channel is limited to 10 m.
CMP cable is required in environmental air spaces such as plenums; CMR is for risers; CM is general-purpose.
NEC Article 725 covers Class 2 and Class 3 circuits, often used for low-voltage control and signaling.
TIA-607 components include the TMGB, TGB, TBB, and bonding to the building grounding electrode system.
Safety Practices
OSHA 29 CFR 1926 contains construction safety regulations; 29 CFR 1910 contains general industry regulations.
Ladder setup uses a 1-ft horizontal base for every 4 ft of vertical height, and the ladder extends 3 ft above the landing.
Fall protection is required at 6 ft in construction under OSHA 1926.501 and at 4 ft in general industry under OSHA 1910.
GFCI protection is required for 120-volt, 15- and 20-ampere receptacles on construction sites when not part of permanent wiring.
Eye protection conforms to ANSI Z87.1; head protection conforms to ANSI Z89.1.
Lockout/tagout is covered by OSHA 1910.147; permit-required confined spaces are covered by OSHA 1910.146.
Class C extinguishers are for energized electrical fires; Class A is for ordinary combustibles; Class B is for flammable liquids.
Cabling Media and Components
Category 5e is characterized to 100 MHz; Category 6 to 250 MHz; Category 6A to 500 MHz; Category 8 to 2000 MHz over a 30 m channel.
Balanced twisted-pair cabling has a nominal impedance of 100 ohms.
T568A assigns pins 1-2 green, 3-6 orange, 4-5 blue, 7-8 brown; T568B assigns 1-2 orange, 3-6 green, 4-5 blue, 7-8 brown.
The 8P8C modular connector, often called RJ-45, terminates four-pair balanced twisted-pair cable.
OM1 is 62.5/125 µm multimode; OM2, OM3, and OM4 are 50/125 µm multimode; OM5 is wideband multimode; OS1 and OS2 are singlemode.
75-ohm coaxial cable is used for video and CATV; 50-ohm coaxial cable is used for RF and radio systems.
Solid conductors are used for permanent horizontal cable; stranded conductors are used for flexible patch cords.
LC is a small-form-factor fiber connector; SC is square push-pull; ST is bayonet-style.
Installation Practices
Horizontal cable is limited to 90 m (295 ft); slack is provided at the work area and telecommunications room as specified by design.
NEC Chapter 9 conduit fill limits are 53 percent for one conductor, 31 percent for two, and 40 percent for three or more.
A conduit run is limited to 360 degrees of total bends between pull points.
All fire-rated penetrations must be sealed with a listed firestop system per NEC 300.21.
TIA-569 UTP separation from power is typically 2 in below 2 kVA, 4 in for 2-5 kVA, and 12 in above 5 kVA.
Horizontal cable is generally supported at intervals not exceeding 5 ft (1.5 m) using J-hooks or listed supports.
Minimum bend radius is commonly 4 times the cable outside diameter for four-pair UTP and 10 times for fiber under no load, 20 times under tension.
Testing, Troubleshooting, and Documentation
Certification tests for twisted pair include wire map, length, insertion loss, NEXT, return loss, ACR-F, propagation delay, and delay skew.
A permanent link test is limited to 90 m (295 ft) and excludes patch cords; a channel test is limited to 100 m (328 ft) and includes them.
Wire map faults include opens, shorts, crossed or reversed pairs, and split pairs.
NEXT failures often occur at connectors or near the tester end; return loss failures indicate impedance mismatch such as a kink or poor termination.
Fiber Tier 1 testing uses an OLTS for insertion loss and length; Tier 2 testing uses an OTDR for event and distance analysis.
TIA-606 requires unique identifiers and records for cables, pathways, spaces, and grounding infrastructure.
A test report includes tester model, calibration date, date and time, operator, link identifier, test standard, and pass/fail result.