BICSI Installer 1 flashcards
BICSI Installer 1 · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Article 800 (NEC)
- NEC Article 800 covers communications circuits, including copper and optical fiber cabling, and addresses installation requirements such as cable listing and fire resistance.
- TIA-568 commercial cabling standard
- ANSI/TIA-568 specifies commercial building telecommunications cabling, including cable types, topology, maximum distances, and transmission performance for balanced twisted-pair and fiber.
- TIA-569 pathways and spaces
- ANSI/TIA-569 defines telecommunications pathways and spaces, such as conduit, cable tray, sleeves, and telecommunications rooms, used to route and house cabling.
- TIA-606 administration standard
- ANSI/TIA-606 provides requirements for labeling, records, and administration of telecommunications infrastructure so cables, pathways, and spaces can be uniquely identified.
- TIA-607 bonding and grounding
- ANSI/TIA-607 specifies telecommunications bonding and grounding, including the TMGB, TGB, bonding backbone, and connection to the building grounding electrode system.
- Plenum cable (CMP)
- CMP cable is listed for use in environmental air spaces, such as return-air plenums, and has low smoke and flame-spread characteristics required by NEC Article 800.
- Horizontal channel length limit
- A balanced twisted-pair horizontal channel is limited to 100 m (328 ft) total: up to 90 m (295 ft) of horizontal cable plus up to 10 m (33 ft) of patch cords.
- OSHA 29 CFR 1926
- OSHA 29 CFR 1926 contains safety and health regulations for construction, including fall protection, ladders, electrical safety, and excavation requirements.
- Ladder 4-to-1 rule
- For every 4 ft (1.2 m) of ladder height, the ladder base is placed 1 ft (0.3 m) from the vertical support, and it extends 3 ft above the landing.
- GFCI on construction sites
- OSHA requires ground-fault circuit interrupter protection for 120-volt, 15- and 20-ampere receptacles on construction sites that are not part of permanent wiring.
- ANSI Z87.1 eye protection
- ANSI Z87.1 is the standard for eye and face protection; safety glasses and goggles used on the job should be marked as meeting it.
- Lockout/tagout (LOTO)
- Lockout/tagout isolates hazardous energy before servicing equipment; OSHA 29 CFR 1910.147 requires locks, tags, and verification of de-energization.
- Class C fire extinguisher
- A Class C extinguisher is suitable for fires involving energized electrical equipment and uses a nonconductive extinguishing agent.
- Category 6A cable
- Category 6A balanced twisted-pair cable is characterized to 500 MHz and supports 10GBASE-T over a 100 m channel in commercial installations.
- T568A wiring sequence
- T568A assigns pins 1-2 to green, 3-6 to orange, 4-5 to blue, and 7-8 to brown; the same sequence must be used at both ends for a straight-through cord.
- T568B wiring sequence
- T568B assigns pins 1-2 to orange, 3-6 to green, 4-5 to blue, and 7-8 to brown; it is the other recognized eight-position modular wiring pattern.
- 8P8C modular connector
- The 8P8C connector, commonly called RJ-45 in data cabling, has eight positions and eight contacts and terminates four-pair balanced twisted-pair cable.
- OM3 multimode fiber
- OM3 is a laser-optimized 50/125 µm multimode fiber designed for 10 Gb/s Ethernet over longer distances than OM2, using VCSEL sources.
- 75-ohm coaxial cable
- 75-ohm coaxial cable is used for video, CATV, and broadband signals; 50-ohm coax is used for RF and radio systems.
- Solid vs stranded conductor
- Solid conductors are used for permanent horizontal cable because they have lower attenuation; stranded conductors are used in patch cords because they are more flexible.
- Conduit fill 40 percent
- For three or more current-carrying conductors in a raceway, NEC Chapter 9 limits fill to 40 percent of the conduit interior cross-sectional area.
- 360-degree bend limit
- NEC limits a conduit run to 360 degrees of total bends between pull points, such as boxes or conduit bodies, to permit pulling cable.
- Firestop penetration requirement
- NEC 300.21 requires fire-rated floor and wall penetrations to be sealed with listed firestop systems to maintain the fire-resistance rating.
- Power separation distances
- TIA-569 separation for unshielded twisted-pair from power lines is typically 2 in (50 mm) below 2 kVA, 4 in (100 mm) for 2-5 kVA, and 12 in (300 mm) above 5 kVA.
- Horizontal cable support interval
- TIA-569 generally requires horizontal cable to be supported at intervals not exceeding 5 ft (1.5 m), using J-hooks or other listed supports.
- Cable bend radius rule
- A common installation rule is a minimum bend radius of 4 times the cable outside diameter for four-pair UTP and 10 times for fiber under no load.
- Permanent link test
- A permanent link test measures the installed horizontal cable and connectors, excluding patch cords, and is limited to 90 m (295 ft).
- Wire map test
- Wire map verifies pin-to-pin continuity and identifies opens, shorts, crossed pairs, reversed pairs, and split pairs in twisted-pair cabling.
- NEXT (near-end crosstalk)
- NEXT measures signal coupling from one pair to another at the same end of the cable; it is a key test for twisted-pair link performance.
- Return loss
- Return loss measures reflected signal energy caused by impedance mismatches; poor return loss often indicates a bad connector, kink, or cable damage.
- OLTS fiber testing
- An optical loss test set uses a light source and power meter to measure insertion loss and verify polarity and continuity of a fiber link.
- OTDR testing
- An optical time-domain reflectometer locates fiber events such as splices, connectors, and breaks by measuring backscattered light versus distance.