BICSI Installer 2 Copper flashcards
BICSI Installer 2 Copper · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Conduit fill limit
- For three or more telecommunications cables, fill must not exceed 40 percent of the conduit's internal cross-sectional area; one cable is limited to 53 percent and two to 31 percent.
- J-hook spacing
- Support horizontal cables with J-hooks spaced about 4 to 5 feet (1.2 to 1.5 meters) apart, attached to building structure rather than to ceiling grid or support wires.
- Power separation minimum
- NEC 800.133 requires at least 2 inches (50 millimeters) of separation between telecommunications cable and electric light, power, or Class 1 circuits, unless a listed barrier separates them.
- Firestop penetration requirement
- Every cable penetration through a fire-rated wall or floor must be sealed with a listed firestop system tested for that construction, cable type, and penetration size.
- Maximum copper pull tension
- Four-pair copper cable should not be pulled with more than 25 pounds-force (110 newtons) of tension, because excess tension stretches conductors and increases attenuation.
- Horizontal link length
- The horizontal permanent link may not exceed 90 meters (295 feet); the full channel, including patch cords at both ends, is limited to 100 meters (328 feet).
- Work area slack
- Leave at least 12 inches (300 millimeters) of cable slack at each work area outlet and a service loop in the telecommunications room for retermination and cable management.
- Cable bend radius rule
- For four-pair unshielded twisted-pair cable, do not bend tighter than four times the cable outside diameter after installation; always follow the manufacturer's published minimum bend radius.
- T568B pin assignment
- T568B places orange pair on pins 1 and 2, green pair on pins 3 and 6, blue pair on pins 4 and 5, and brown pair on pins 7 and 8.
- T568A versus T568B
- T568A and T568B use the same pin positions but swap the orange and green pairs, so using one scheme on one end and the other creates a crossover cable.
- Untwist limit at termination
- For Category 5e and Category 6 terminations, keep the conductor twists intact to within about 0.5 inch (13 millimeters) of the connection point to control crosstalk.
- 110 punch-down tool use
- A 110-style punch-down tool seats and trims conductors on data jacks and 110 blocks; the blade's cut side must face the outside end of the terminal.
- Wire map test
- A wire map test verifies pin-to-pin continuity and identifies opens, shorts, reversed pairs, crossed pairs, and split pairs in a copper link.
- Permanent link versus channel
- A permanent link test covers the installed horizontal cable and its termination hardware but excludes patch cords; a channel test includes the patch cords and end equipment cords.
- TIA-606 labeling rule
- TIA-606 requires each cable, termination point, and pathway to carry a unique identifier, with labels placed at both ends and recorded in administration documentation.
- Certifier calibration
- A copper certification tester must be calibrated or verified according to the manufacturer's schedule, commonly annually, and test results must record the tester used and date.
- Split pair symptom
- A split pair occurs when one wire of a pair is terminated on the wrong pin; simple continuity may pass, but crosstalk and NEXT test results fail.
- High NEXT causes
- High near-end crosstalk usually results from over-untwisted conductors at termination, a kinked cable, or a connector that is not fully seated.
- TDR fault location
- A time-domain reflectometer sends a pulse down the cable and measures the reflection to report total length and the distance to an open or short.
- Horizontal cross-connect
- The horizontal cross-connect is the patch panel or block in the telecommunications room where horizontal cabling terminates and connects to active equipment or backbone cabling.
- PoE 802.3bt power
- IEEE 802.3bt Power over Ethernet provides up to 60 watts at the source for Type 3 and up to 90 watts for Type 4, using all four pairs.
- Consolidation point
- A consolidation point is a permanent interconnection point within horizontal cabling, typically in an open office ceiling, that allows reconfiguration without pulling new cable from the telecommunications room.
- Tone generator use
- A tone generator injects an audible signal on a cable and an inductive probe detects it at the far end, allowing installers to identify unlabeled cables without damaging insulation.
- J-hook support tool
- J-hooks are cable support hardware attached to structure at 4 to 5 foot intervals; they carry cable weight and maintain bend radius better than ceiling grid wire.
- Cable lubricant caution
- Use only cable lubricant approved for the specific jacket compound, because some lubricants can soften or degrade PVC and other cable jacket materials.
- Ladder 4-to-1 rule
- For every 4 feet (1.2 meters) of working height, place the ladder base 1 foot (0.3 meter) away from the wall, and maintain three points of contact while climbing.
- GFCI temporary power
- Temporary power tools used on a job site should be connected to ground-fault circuit interrupter protection to reduce shock risk in wet or damp locations.
- Voltage verification rule
- Before working near conductors, verify they are de-energized with a voltage tester; treat unmarked or unidentified cables as energized until proven otherwise.
- Plenum cable rating
- CMP cable is listed for air-handling spaces and has low smoke and flame spread; CMR cable is rated for vertical riser shafts but not for plenum spaces.
- TIA-607 bonding
- TIA-607 requires telecommunications bonding to the building grounding electrode system through a telecommunications main grounding busbar and telecommunications grounding busbars.
- Horizontal cable splicing
- Horizontal cabling must be installed as continuous runs without splices; any needed connection must use a permanent cross-connect or consolidation point, not a splice.
- Cable flame ratings
- Cable jacket flame ratings include CM (general), CMR (riser), CMP (plenum), and limited-use CMX; the rating must match the installed environment and local code.