BICSI RCDD study materials
BICSI RCDD study resources

BICSI RCDD cheat sheet

BICSI RCDD · Keep the key ideas within reach.

Quick reference

Design Basics

  • Horizontal cabling maximum distance is 90 m (295 ft) of permanent link plus 10 m (33 ft) of patch cords for a 100 m channel.

  • Backbone distance limits depend on media and application; single-mode fiber supports 2,000 m and multimode OM3/OM4 commonly 300-550 m for 10GBASE-SR.

  • Recognized horizontal media are balanced twisted-pair (Category 5e and above) and multimode optical fiber; coaxial is not a recognized horizontal medium.

  • Consolidation point: a single transition point in horizontal cabling, no more than one per horizontal run, located in accessible ceiling or floor space.

  • MUTOA serves multiple work areas; its patch cord length plus permanent link must not exceed the 100 m channel limit.

  • Minimum bend radius rule of thumb: 4x cable OD for UTP during installation and 10x OD for fiber (varies by fiber type and manufacturer).

  • Separation from power: maintain at least 305 mm (12 in) from unshielded power lines unless a barrier or calculated separation per applicable codes is used.

  • Pathway fill: keep cable bundle cross-section to about 40 percent of conduit internal area for existing (40%) and 31 percent for new pulls to allow future growth.

Quick reference

Cabling Infrastructure

  • Balanced twisted-pair categories: Cat 5e (100 MHz), Cat 6 (250 MHz), Cat 6A (500 MHz), Cat 8 (2,000 MHz) rated to 30 m channels.

  • Cat 6A supports 10GBASE-T to 100 m; Cat 6 supports 10GBASE-T only to about 55 m in bundled conditions.

  • Shielded/FTP systems require proper grounding and bonding at both ends to control common-mode noise and EMI.

  • Fiber types: OM1 62.5/125, OM2 50/125, OM3/OM4 laser-optimized 50/125 multimode; OS1/OS2 single-mode.

  • Fiber connector polish: PC, UPC (ultra-physical contact) and APC (angled physical contact, 8-degree); never mate APC with UPC.

  • T568A and T568B pin/pair assignments differ in pairs 2 and 3; both are acceptable if used consistently across the installation.

  • Cable jacket ratings: CMP (plenum), CMR (riser), CM (general), CMX (limited use); plenum spaces require CMP or equivalent low-smoke cable.

  • Insertion loss budget for fiber = cable loss (dB/km x length) + connector loss (typically 0.75 dB per mated pair) + splice loss (about 0.3 dB each).

Quick reference

Telecommunications Spaces and Architecture

  • Entrance facility (EF) is where outside plant meets inside plant; it houses entrance cables, protectors, and demarcation.

  • Equipment room (ER) houses major cross-connects and active equipment; it is distinct from a telecommunications room (TR).

  • TR serves a floor or portion of a floor; each TR should serve a maximum usable floor area of about 1,000 m2 (10,000 ft2) with horizontal distances limited to 90 m.

  • TR sizing: at least 3.3 m2 (35 ft2) for the first 100 m2 of served area plus 0.1 m2 per additional 10 m2, with minimum dimensions about 2.4 m x 3.0 m.

  • TR environmental targets: temperature 18-27 C (64-81 F), relative humidity 30-55 percent, and positive pressure with filtered air.

  • TR requires dedicated electrical: at least two dedicated duplex outlets on separate circuits, plus lighting at 500 lux and a minimum door width of 0.9 m (3 ft).

  • Cross-connect types: main cross-connect (MC), intermediate cross-connect (IC), and horizontal cross-connect (HC).

  • Vertical backbone cabling runs between EF/ER and TRs; horizontal cabling runs from HC to work areas.

Quick reference

Telecommunications Distribution Systems

  • Pathway types: conduit, cable tray, raceway, underfloor duct, cellular floor, and ceiling pathways; each has defined fill and support rules.

  • Conduit fill per common practice: 1 cable = 53 percent, 2 cables = 31 percent, 3 or more cables = 40 percent of interior cross-section.

  • Support horizontal cable at intervals not exceeding 1.5 m (5 ft) and within 300 mm (12 in) of boxes and terminations.

  • J-hook and cable tray support: maintain cable bend radius and avoid exceeding manufacturer fill recommendations.

  • Sleeves through walls/floors should be at least 100 mm (4 in) and firestopped to the rated assembly.

  • Telecommunications bonding backbone (TBB) ties together TRs; the telecommunications main grounding busbar (TMGB) is in the EF/ER.

  • Grounding conductor sizing follows local electrical code; bonding conductors are typically 6 AWG for TBB and 2 AWG or larger for the TMGB.

  • Horizontal pathways must be separated from power and other EMI sources and must maintain the channel length limit of 100 m total.

Quick reference

ICT Systems and Applications

  • Ethernet media standards: 1000BASE-T over Cat 5e/6 to 100 m; 10GBASE-T over Cat 6A to 100 m; 40/100GBASE-SR over OM3/OM4 short distances.

  • PoE standards: 802.3af (15.4 W at PSE), 802.3at (30 W), and 802.3bt (60 W Type 3 and 90 W Type 4).

  • PoE cable heating: bundled cables carrying PoE current derate; higher temperature and larger bundles reduce allowable current per conductor.

  • Wireless: 802.11ax (Wi-Fi 6) and 802.11be (Wi-Fi 7) require adequate AP density, channel planning, and backhaul over Cat 6A or fiber.

  • DAS (distributed antenna system) and small cells extend cellular coverage inside buildings using fiber or coax distribution.

  • IP video surveillance and access control require dedicated VLANs, PoE budgets, and adequate uplink capacity.

  • Data center topologies include Top-of-Rack (ToR) and End-of-Row (EoR); spine-leaf designs support east-west traffic scaling.

  • Power over Ethernet budgeting: sum device draw plus cable loss (about 10 percent) and reserve headroom for future loads.

Quick reference

Project Management

  • Project phases: initiation, planning, execution, monitoring/control, and closure; each phase produces defined deliverables.

  • Scope baseline = scope statement + work breakdown structure (WBS) + WBS dictionary; changes require formal change control.

  • Critical path method (CPM): the longest path through the network determines minimum project duration; float is schedule slack.

  • Earned value: CV = EV - AC, SV = EV - PV, CPI = EV/AC, SPI = EV/PV; CPI or SPI below 1.0 indicates unfavorable performance.

  • Risk management includes identification, qualitative/quantitative analysis, response planning, and monitoring; responses are avoid, mitigate, transfer, accept.

  • Procurement documents include RFP, RFQ, and IFB; contract types: fixed-price, cost-reimbursable, time and materials.

  • Quality management uses inspection, testing, and acceptance criteria defined in the statement of work and specifications.

  • Stakeholder communication plan defines audience, frequency, format, and escalation paths for project reporting.

Quick reference

Documentation and Administration

  • As-built documentation includes floor plans, pathway layouts, cable schedules, and rack elevation drawings.

  • Cable labeling: unique identifier per cable, both ends labeled, and record kept in the administration database or spreadsheet.

  • Administration records include the record of the telecommunications space, cable records, and grounding/bonding records.

  • Test reports for copper include wire map, length, insertion loss, NEXT, and return loss; fiber reports include insertion loss and length.

  • Change management: every configuration change updates the administration records and as-built drawings.

  • Documentation should be delivered in both native and PDF formats, with revision numbers and dates.

  • Asset inventory tracks equipment serial numbers, rack locations, ports, and warranty/maintenance dates.

  • Class and administration per TIA-606: classes 1-4 define labeling and record-keeping scope from simple to full automated management.