BICSI RCDD flashcards
BICSI RCDD · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Horizontal channel length
- Maximum horizontal channel is 100 m total: 90 m permanent link plus 10 m of patch cords at the work area and cross-connect.
- Consolidation point
- A single transition point in horizontal cabling located in accessible ceiling or floor space; only one is allowed per horizontal run.
- MUTOA
- A multi-user telecommunications outlet assembly serving several work areas; patch cord plus permanent link must not exceed the 100 m channel.
- Bend radius rule
- During installation, keep at least four times the cable outside diameter for UTP and ten times for fiber to prevent damage.
- Cat 6A
- Balanced twisted-pair rated to 500 MHz and supports 10GBASE-T to 100 m; often shielded and requires proper grounding and bonding.
- OM3 and OM4
- Laser-optimized 50/125 multimode fibers supporting 10GBASE-SR to 300 m and 550 m respectively, used for building backbones.
- APC connector
- An angled physical contact fiber connector with an 8-degree endface that reduces back reflection; it must not be mated with UPC.
- T568A versus T568B
- Two acceptable pin/pair assignments for twisted-pair outlets that differ in pairs 2 and 3; use one consistently throughout a project.
- Plenum cable
- CMP-rated cable with low smoke and flame spread, required in plenum air-handling spaces; CMR is used in risers.
- Fiber loss budget
- Total allowed loss equals cable attenuation plus connector loss (about 0.75 dB per mated pair) plus splice loss (about 0.3 dB each).
- Entrance facility
- The space where outside plant cables enter the building and meet inside plant, housing protectors and the demarcation point.
- Telecommunications room
- A dedicated space serving a floor area, typically up to about 1,000 m2, housing the horizontal cross-connect and active equipment.
- TR environmental targets
- Telecommunications rooms should be maintained at 18-27 C and 30-55 percent relative humidity with filtered positive-pressure air.
- Cross-connect hierarchy
- Main cross-connect in the equipment room, intermediate cross-connect in a backbone node, and horizontal cross-connect in each telecommunications room.
- Conduit fill rule
- Common practice allows 53 percent fill for one cable, 31 percent for two, and 40 percent for three or more cables.
- Horizontal support spacing
- Support horizontal cables at intervals no greater than 1.5 m (5 ft) and within 300 mm (12 in) of boxes and terminations.
- TMGB
- The telecommunications main grounding busbar, located in the entrance facility or equipment room, bonded to the building grounding electrode system.
- Firestopping
- Penetrations through rated walls and floors must be sealed with listed materials to restore the fire-resistance rating of the assembly.
- 802.3bt PoE
- Power over Ethernet standard delivering up to 60 W (Type 3) or 90 W (Type 4) at the power sourcing equipment.
- PoE cable heating
- Bundled cables carrying PoE current derate; larger bundles and higher ambient temperatures reduce allowable current per conductor.
- Spine-leaf topology
- A data center network design where every leaf switch connects to every spine switch, supporting scalable east-west traffic.
- DAS
- A distributed antenna system that extends cellular coverage indoors using fiber or coaxial distribution from a central head-end.
- Wi-Fi 6
- IEEE 802.11ax wireless standard improving efficiency in dense environments; planning requires adequate AP density and backhaul capacity.
- Critical path
- The longest sequence of dependent activities in a project network; it determines the minimum project duration and has zero float.
- Cost performance index
- CPI equals earned value divided by actual cost; a value below 1.0 indicates the project is over budget.
- Schedule performance index
- SPI equals earned value divided by planned value; a value below 1.0 indicates the project is behind schedule.
- Risk responses
- Standard strategies for threats are avoid, mitigate, transfer, and accept; opportunities use exploit, enhance, share, and accept.
- Work breakdown structure
- A hierarchical decomposition of project scope into deliverables and work packages that forms the basis for estimating and scheduling.
- As-built drawings
- Final drawings reflecting installed conditions, including pathway layouts, cable schedules, and rack elevations, delivered at project closeout.
- Cable labeling rule
- Each cable receives a unique identifier, is labeled at both ends, and the identifier is recorded in the administration database.
- Copper test report fields
- Field tests record wire map, length, insertion loss, near-end crosstalk, and return loss for each permanent link.
- TIA-606 classes
- Administration classes 1 through 4 define increasing scope of labeling and record keeping, from simple to fully automated management systems.