BPI BA-T flashcards
BPI BA-T · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Conduction heat flow
- Heat transfer through solid material driven by temperature difference. Calculated as Q equals U times area times delta T, where U is the assembly conductance and delta T is indoor-to-outdoor temperature difference.
- R-value definition
- Resistance to heat flow through a material or assembly, expressed in square feet times degrees Fahrenheit hours per Btu. Higher R-value means lower conductance, and layer R-values add in series.
- Thermal bridging effect
- Framing members, slabs, and penetrations conduct heat around insulation, lowering effective R-value. Effective U equals the area-weighted sum of frame and cavity conductances across the assembly.
- Dew point temperature
- The temperature at which air reaches saturation at constant moisture content. Surfaces below dew point collect condensation, so interior surface temperatures and insulation placement both matter.
- Relative humidity meaning
- Ratio of actual water vapor pressure to saturation vapor pressure at the same temperature, expressed as a percentage. It changes with temperature even when absolute moisture content stays constant.
- Stack effect
- Buoyancy-driven air movement caused by indoor-outdoor temperature and height difference. Warm air rises in winter, creating pressure differences that drive infiltration low and exfiltration high.
- Air leakage versus diffusion
- Air leakage moves moisture with bulk air through gaps and can carry far more water than vapor diffusion through materials. Sealing bypasses is usually the higher-priority moisture control step.
- Moisture balance principle
- Durable assemblies keep wetting sources smaller than drying capacity. Wetting includes rain, ground moisture, diffusion, and air leakage; drying includes drainage, ventilation, and diffusion outward.
- Latent versus sensible load
- Sensible load changes air temperature; latent load changes moisture content through evaporation or condensation. Air leakage and infiltration add both, which affects equipment sizing and comfort.
- Pre-assessment scoping
- Defining building type, vintage, occupancy, HVAC systems, and reported complaints before fieldwork. Scope determines instruments, sampling locations, and the sequence of site activities.
- Site walk sequence
- A structured inspection order, typically exterior drainage and envelope first, then interior moisture, air leakage, HVAC, and occupant patterns. Consistent order prevents missed systemic causes.
- Pin-type moisture meter
- An instrument that measures electrical conductivity between probes driven into material. Readings indicate relative moisture and require species or material calibration plus confirmation by another method.
- Pinless moisture meter
- A capacitance-based instrument that reads moisture through a surface without penetration. It is useful for scanning large areas but sensitive to density, coatings, and proximity to metal.
- Blower door setup conditions
- Exterior openings closed, interior doors open or pressure-balanced, combustion appliances off, and baseline pressures recorded. Setup consistency is required for comparable test results.
- Occupant interview value
- Structured questions about complaint timing, weather correlation, and recent renovations reveal patterns that measurements alone may miss. Interviews guide where to test and what to document.
- Sampling plan documentation
- Recording location, time, instrument, method, and calibration status for each measurement. Complete records support later analysis, reporting, and any dispute over findings.
- Data quality checks
- Repeat readings, compare instruments, flag outliers, and note weather conditions such as wind or stack effect. These steps separate real building behavior from measurement noise.
- Zone pressure diagnostic
- A manometer reading between a zone and outside while the house is depressurized. A reading near house pressure indicates connection; near zero indicates the zone is isolated.
- ACH50 calculation
- Air changes per hour at 50 pascals equals CFM50 times 60 divided by conditioned volume in cubic feet. It normalizes blower door leakage across buildings of different size.
- Infrared survey conditions
- Thermography needs a sufficient indoor-outdoor temperature difference, typically ten degrees Fahrenheit or more. Solar gain, wind, and wet surfaces create false anomalies.
- Duct leakage testing
- Pressurizing the duct system to 25 pascals and measuring airflow needed to hold it. Results are reported as CFM25 and as a percentage of total system airflow.
- Pressure pan testing
- Measuring pressure difference across a supply or return register while the house is depressurized. Higher readings suggest greater duct leakage to outside or other zones.
- Combustion safety testing
- Measuring carbon monoxide, draft pressure, and spillage under worst-case conditions. Reversed draft or elevated CO indicates a hazard requiring immediate corrective action.
- Worst-case depressurization
- Operating exhaust fans and closing interior doors to maximize negative pressure on combustion appliances. Testing under these conditions reveals whether flue gases can spill indoors.
- Manometer zeroing
- Setting the instrument reference to zero before each test so readings reflect actual pressure difference. Unzeroed instruments introduce offset errors that invalidate comparisons.
- Tracer gas testing
- Releasing a detectable gas and measuring concentration to identify air pathways or ventilation rates. It isolates connections that pressure tests alone may not resolve.
- Field note essentials
- Date, time, weather, instrument model and serial, calibration date, test conditions, and exact measurement locations. These details make results reproducible and defensible.
- Photo documentation practice
- Each image should include a scale reference, orientation, location label, and a note on what it documents. Unlabeled photos lose evidentiary value quickly.
- Report structure
- Objective and scope, methods, findings with data, limitations, conclusions, and prioritized recommendations. A consistent structure lets clients locate evidence behind each conclusion.
- Fact versus interpretation
- Measured values and observed conditions are facts; explanations and causes are interpretations. Reports should label each clearly and cite the method behind every number.
- Recording negative results
- Documenting tests that found nothing, including locations checked and methods used. This shows thoroughness and protects against later claims that an area was never examined.
- Limitations disclosure
- Stating inaccessible areas, weather constraints, and test conditions that reduce confidence. Honest limits prevent overreach and tell the client what further work may be needed.