Air Leakage and Duct Leakage Testing Fundamentals

  • Pressure is the driving force for leakage: airflow through an opening scales with the pressure difference across it, so test results are only comparable at the stated reference pressure.

  • CFM50 is the blower-door airflow needed to hold the house at 50 Pa; CFM25 is the duct-leakage reference pressure used for most duct tests.

  • ACH50 = CFM50 × 60 ÷ conditioned volume in cubic feet; ACHnat is estimated by dividing ACH50 by a climate-dependent n-factor, typically 10-20.

  • CFM50 per square foot of conditioned floor area is an alternative tightness metric; lower values indicate a tighter envelope.

  • ELA (effective leakage area) converts measured leakage to an equivalent orifice area, commonly referenced at 4 Pa for envelope work.

  • Leakage curves fit the power law Q = C × ΔP^n; n near 0.5 indicates orifice flow, n near 1.0 indicates laminar/crack flow.

  • Duct leakage is expressed as CFM25 total, CFM25 to outdoors, or as a percentage of system airflow at the same pressure.

  • Envelope leakage raises infiltration load, drives moisture transport, and can destabilize pressure balance and combustion appliance venting.

Quick reference

Blower Door and Duct Leakage Measurement Procedures

  • Blower door setup: seal the door frame with the panel, install the gauge, and confirm the reference (outside) pressure tap is unobstructed.

  • Baseline (bias) pressures are recorded before the fan runs and subtracted from test readings to remove stack and wind effects.

  • Multi-point testing records airflow at several pressures (e.g., 15-60 Pa) and fits the power law to derive C and n for extrapolation.

  • Single-point CFM50 reading is valid only when the induced pressure is at least about 50 Pa and wind is low enough to keep readings stable.

  • Duct pressurization: seal registers, connect the fan to the air handler or a register, and pressurize the duct system to 25 Pa.

  • Total duct leakage is measured with the house (envelope) open to outdoors; leakage to outdoors is measured with the house sealed and pressurized.

  • Duct leakage to outdoors = total duct leakage minus leakage to the conditioned space; both are reported at 25 Pa.

  • Gauge calibration, hose routing, and ring selection must be checked, since a wrong ring or kinked hose corrupts every reading.

Quick reference

Building Envelope and Duct System Diagnostics

  • Zone pressure testing (door closure, zonal pressure) locates connected zones and hidden leakage paths between rooms, attics, and garages.

  • A pressure pan over a register or outlet shows whether that penetration is connected to the outside; readings above roughly 1-2 Pa suggest a leak path.

  • Thermal imaging paired with a blower door reveals air leakage and missing insulation, since depressurization makes leaks cold in winter and warm in summer.

  • Smoke pencils and theatrical fog trace leakage direction and confirm the path when pressure readings are ambiguous.

  • Duct leakage in unconditioned spaces (attics, crawlspaces, garages) is the highest priority because it is effectively outdoor leakage.

  • Return-side leakage in a depressurized house can draw attic or garage air into the supply, degrading indoor air quality and pressure balance.

  • Pressure imbalance between supply and return, or between rooms, causes closed-door pressure differences and comfort or backdrafting problems.

  • Combustion safety: depressurization can backdraft natural-draft appliances; test with the blower door running and check for spillage.

Quick reference

Documentation, Standards, and Safety

  • Record test conditions: indoor and outdoor temperature, wind, baseline pressures, gauge model, ring, and fan configuration.

  • Report both measured values and derived metrics (CFM50, ACH50, CFM25, leakage percentage) with the reference pressure stated.

  • Standard references include RESNET/ANSI and ASTM E779 for envelope testing and ASTM E1554 for duct leakage; cite the version used.

  • The test report should document pre- and post-retrofit values so improvement can be verified against the same protocol.

  • Safety: never leave the blower door running unattended; secure the panel and fan, and protect openings and occupants.

  • Before testing, confirm combustion appliances are off or monitored, and check for spillage after depressurization.

  • Document anomalies (open windows, obstructed registers, wind gusts) that could invalidate results, and note corrective actions.

  • Retain raw data and calculations for traceability, since third-party verification and program compliance require an auditable record.