- CFM50
- The blower-door airflow required to maintain a 50 Pa pressure difference across the building envelope; the primary single-point envelope tightness metric.
- ACH50
- Air changes per hour at 50 Pa, calculated as CFM50 times 60 divided by conditioned volume in cubic feet; a size-normalized envelope leakage metric.
- Power law leakage
- Leakage airflow relates to pressure by Q equals C times pressure difference raised to exponent n; n near 0.5 is orifice flow and near 1.0 is crack flow.
- Effective leakage area
- ELA converts measured leakage into an equivalent orifice area, commonly referenced at 4 Pa, allowing comparison of envelope tightness across homes.
- CFM25
- The duct-leakage reference airflow at 25 Pa pressure difference, used for total duct leakage and leakage-to-outdoors reporting.
- Duct leakage percentage
- Duct leakage CFM25 divided by system airflow at the same pressure, expressed as a percent; normalizes leakage to system size.
- Infiltration load
- Outdoor air entering through envelope leaks that must be heated or cooled; increases energy use and can carry moisture and pollutants indoors.
- n-factor
- A climate-dependent divisor used to estimate natural air changes from ACH50; typical values range from about 10 to 20.
- Blower door baseline
- Static pressure readings recorded before the fan runs, then subtracted from test readings to remove stack and wind bias.
- Multi-point test
- Recording airflow at several induced pressures, then fitting the power law to derive C and n for extrapolation to other pressures.
- Single-point test
- A blower-door test using one induced pressure near 50 Pa, valid only when wind is low and the reading is stable.
- Duct pressurization setup
- Sealing registers and connecting the test fan to the air handler or a register, then pressurizing the duct system to 25 Pa.
- Total duct leakage
- Duct leakage measured at 25 Pa with the house open to outdoors, capturing leakage to both conditioned space and outside.
- Leakage to outdoors
- Duct leakage measured at 25 Pa with the house sealed and pressurized, isolating leakage paths that connect ducts to outside.
- Reference pressure tap
- The hose connection sensing outdoor or reference pressure; if obstructed or misrouted, every gauge reading becomes unreliable.
- Fan ring selection
- Choosing the correct gauge ring for the expected airflow range; a wrong ring or kinked hose corrupts all airflow readings.
- Pressure pan test
- A pan placed over a register or outlet to read pressure while the house is depressurized; elevated readings indicate a leak path.
- Zonal pressure testing
- Measuring pressure differences between rooms or zones with doors closed to locate connected zones and hidden leakage paths.
- Thermal imaging survey
- Infrared camera use during depressurization to reveal air leakage and missing insulation, since leaks appear as temperature anomalies.
- Smoke pencil tracing
- A smoke source moved along suspected paths to visualize leakage direction and confirm ambiguous pressure readings.
- Unconditioned duct leakage
- Leakage from ducts in attics, crawlspaces, or garages; it is effectively outdoor leakage and is the highest-priority repair.
- Return-side leakage
- Leaks on the return duct that can draw attic or garage air into the supply stream, harming indoor air quality and pressure balance.
- Room pressure imbalance
- Closed-door pressure differences caused by supply and return mismatch, producing comfort complaints and possible backdrafting.
- Combustion appliance spillage
- Flue gas escaping into the space rather than up the vent; depressurization from testing can cause it, so appliances are monitored.
- Test conditions record
- Documentation of indoor and outdoor temperature, wind, baseline pressures, gauge model, ring, and fan configuration for each test.
- Reference pressure statement
- Every reported airflow must state the pressure at which it was measured, such as CFM50 or CFM25, to be meaningful.
- ASTM E779
- A standard test method for determining air leakage rate of buildings by fan pressurization, commonly cited for envelope testing.
- ASTM E1554
- A standard test method for determining air leakage of HVAC air distribution systems, commonly cited for duct leakage testing.
- Pre/post retrofit comparison
- Reporting before and after values measured with the same protocol so that improvement can be verified and attributed.
- Anomaly documentation
- Recording open windows, obstructed registers, wind gusts, or other conditions that could invalidate results, along with corrective actions.
- Raw data retention
- Keeping gauge readings, calculations, and notes so third-party verification and program compliance can audit the result.
- Blower door safety rule
- Never leave the blower door running unattended; secure the panel and fan and protect openings and occupants during testing.