BC Class B-R Electrical FSR flashcards
BC Class B-R Electrical FSR · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Class B-R FSR
- A certified field safety representative authorized to take out permits and supervise regulated electrical work for a licensed contractor, within the class and scope stated on the certificate.
- Permit before work
- Regulated electrical work may not begin until a permit is issued, and the FSR named on that permit is accountable for all work performed under it.
- Single-phase current formula
- Current equals power divided by the product of voltage and power factor: I = P / (V × PF). Use for resistive and single-phase motor or appliance load calculations.
- Three-phase power formula
- Power equals the square root of three times voltage times current times power factor: P = √3 × V × I × PF. Rearrange to solve for current when sizing conductors.
- Voltage drop single-phase
- Approximate drop equals two times resistivity times current times length divided by circular mils; the factor two accounts for the outgoing and return conductor path.
- Voltage drop three-phase
- Approximate drop equals the square root of three times resistivity times current times length divided by circular mils; the return path is not counted separately.
- Bonding versus grounding
- Bonding connects non-current-carrying metal parts to provide a fault current path; grounding connects the electrical system to earth. Both are required and serve distinct functions.
- Continuous load factor
- A load expected to operate three hours or more is continuous and is calculated at 125 percent of its rating for conductor and overcurrent sizing.
- Termination temperature limit
- Conductor ampacity is limited by the temperature rating of the terminations; where terminations are rated lower than the conductor, the lower column governs the final ampacity.
- Box fill counting
- Each conductor counts once, each device counts as two conductors per strap, grounding conductors count once, and the largest conductor sets the base volume allowance.
- Conduit fill percentages
- Permitted conductor area is 53 percent of conduit interior area for one conductor, 31 percent for two, and 40 percent for three or more conductors.
- Motor branch conductor sizing
- Branch-circuit conductors supplying a single motor are sized at not less than 125 percent of the motor full-load current rating from the applicable table.
- Motor overload protection
- Overload devices protect the motor from sustained excess current and are selected based on the motor's service factor or temperature rise, separate from short-circuit protection.
- Transformer primary-only protection
- Primary-only protection is allowed only within specified rating limits relative to the transformer; outside those limits both primary and secondary protection are required.
- Working space clearance
- A defined depth, width, and height of clear space must be maintained in front of electrical equipment to permit safe operation and maintenance without contacting live parts.
- Lockout tagout default
- Electrical work is performed de-energized with locks and tags applied by default; energized work requires documented justification, hazard assessment, and authorization.
- Concealed work notice
- The FSR must request inspection before covering concealed wiring, boxes, or raceways so the safety authority can verify compliance while the work is still visible.
- Incident reporting duty
- Electrical contact, arc flash, or fire events must be reported to the safety authority within the regulated timeframe, with the scene preserved for investigation.
- Arc flash hazard label
- Equipment likely to be examined while energized must carry a label identifying arc flash and shock hazards, with incident energy or PPE category information.
- Service demand calculation
- Sum connected loads, apply permitted demand factors for lighting, ranges, and dryers, then size service conductors and equipment to the resulting calculated demand.
- Grounding electrode supplement
- Where a single grounding electrode such as a rod exceeds the specified resistance, a supplemental electrode is required and must be bonded to the first.
- GFCI protection purpose
- Ground-fault circuit interrupter protection limits fault current to a low level to reduce shock hazard, and is required in specified wet or high-risk locations.
- AFCI protection purpose
- Arc-fault circuit interrupter protection detects characteristic arcing signatures and opens the circuit, reducing fire risk on specified branch circuits.
- Overcurrent device coordination
- The overcurrent device rating must not exceed the conductor ampacity after adjustment and correction factors, and must carry the calculated load continuously.
- Ambient temperature correction
- Conductor ampacity is corrected for ambient temperature using table factors, because higher ambient reduces the heat a conductor can dissipate safely.
- Conductor bundling adjustment
- Where multiple current-carrying conductors share a raceway or cable without spacing, ampacity is reduced by adjustment factors based on conductor count.
- Hazardous location classification
- Class and division or zone designations define the flammable hazard present, and the classification determines permitted wiring methods, enclosures, and sealing requirements.
- Wet location wiring
- Wet and damp locations require wiring methods and enclosures rated for moisture exposure, with listed fittings and drain provisions where water can enter.
- FSR delegation limits
- An FSR may delegate supervision only to another qualified FSR within the same class of work, and the delegation must be documented and accepted.
- Compliance order authority
- The safety authority may issue compliance orders requiring correction of unsafe or non-compliant work, and failure to comply can lead to certificate suspension or cancellation.
- Record retention duty
- Permits, inspection records, test results, and as-built drawings must be retained and produced on request during an inspection or investigation.
- Neutral conductor sizing
- The neutral must carry the maximum unbalanced load and may be reduced only where the code permits, such as for service calculations with restricted harmonic content.