CA Fire Sprinkler study materials
CA Fire Sprinkler study resources

CA Fire Sprinkler flashcards

CA Fire Sprinkler · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Design density
The minimum flow rate in gallons per minute per square foot that must be discharged over the design area, determined by occupancy hazard classification in NFPA 13.
Remote area
The hydraulically most demanding area of sprinkler operation used in calculations; its size depends on hazard, ceiling slope, and sprinkler response type.
Hazen-Williams formula
An empirical equation relating friction loss to flow, pipe diameter, and a roughness coefficient; used to compute pressure loss in sprinkler piping.
Velocity pressure
The pressure associated with the speed of water in a pipe, calculated as 0.001123 times flow squared divided by diameter to the fourth power.
Balancing a junction
Adjusting flow in one branch so its pressure matches the other branch at a common junction, using flow proportional to the square root of pressure.
Hose stream allowance
The flow in gallons per minute reserved for fire department hose use, added to sprinkler demand and applied for a specified duration.
Fire pump churn
The pump's shutoff condition with no flow; churn pressure is typically 110 to 140 percent of rated pressure and must be considered in system design.
Standpipe Class I
A standpipe system with 2½-inch outlets intended for fire department use, requiring 100 psi residual pressure at the topmost outlet.
Water supply curve
A plot of available pressure versus flow at the point of connection, derived from static and residual readings taken during a flow test.
Hanger spacing
The maximum distance between supports for sprinkler pipe, typically 12 feet for pipe up to 1¼ inch and 15 feet for larger sizes.
Sway bracing
A seismic restraint system that limits lateral and longitudinal pipe movement, installed at specified intervals along the piping.
Deflector distance
The required distance between a sprinkler deflector and the ceiling, typically 1 to 4 inches below noncombustible ceilings and up to 12 inches below combustible ceilings.
Trapeze hanger
A support consisting of a horizontal member suspended from two rods, used where individual hangers cannot be attached or where multiple pipes are supported.
NFPA 13
The standard for the installation of sprinkler systems in commercial and industrial occupancies, covering design, installation, and acceptance testing.
NFPA 25
The standard for inspection, testing, and maintenance of water-based fire protection systems, specifying frequencies for gauges, alarms, and main drains.
Hydrostatic test
A pressure test of piping at 200 psi for two hours, or 50 psi above working pressure if higher, to verify the system is leak-free before acceptance.
Plan submittal
The package of drawings, hydraulic calculations, water supply data, and manufacturer information submitted to the authority having jurisdiction for review and approval.
Unit price contract
A contract where the contractor is paid a fixed price per unit of work installed, requiring accurate quantity tracking for final billing.
Retainage
A percentage of each payment withheld by the owner until substantial completion, providing security for completion of the work.
Change order
A written modification to the contract scope, price, or schedule, signed by authorized parties, used to document and bill extra work.
Schedule of values
A breakdown of the contract price by work items, used as the basis for progress payments and tracking of completed work.
Main drain flow test
A test that opens the main drain to measure static and residual pressure and confirm the water supply can deliver the required flow.
Waterflow alarm test
An annual test that activates a flow switch or pressure switch to verify the alarm signals properly and is received at the monitoring location.
Impairment procedure
A documented process for taking a system out of service, including notification of the authority having jurisdiction and posting of a fire watch.
Dry-pipe trip test
A test that opens the dry-pipe valve to confirm it trips at the design air pressure and that water reaches the system within the required time.
CSLB
The California Contractors State License Board, which licenses contractors, administers exams, and enforces contractor law in the state.
Qualifying individual
The person who passes the trade and law exams and is listed on a contractor's license, responsible for the licensee's operations.
Contractor bond
A surety bond required by California law, typically $25,000, that provides protection to consumers for certain violations by a licensed contractor.
Down payment limit
A California rule limiting the down payment on home improvement contracts to 10 percent of the contract price or $1,000, whichever is less.
Grooved coupling
A mechanical pipe joint that connects grooved pipe ends with a gasket and clamp, allowing some movement and commonly used in seismic areas.
Alarm check valve
A valve that opens to allow water into the system and directs flow to an alarm device when a sprinkler operates, used in wet-pipe systems.
Temperature rating
The maximum ambient temperature at which a sprinkler is designed to operate, color-coded and selected based on the expected ceiling temperature.