Red Seal Industrial Electrician flashcards
Red Seal Industrial Electrician · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Test-before-touch procedure
- Confirm the voltage tester on a known live source, test the isolated conductor, then re-test the source; a single zero reading does not prove the circuit is de-energized.
- Arc flash boundary
- The distance at which a person without arc-rated protective equipment would receive second-degree burns, defined as an incident energy of 1.2 cal/cm².
- Class A GFCI trip level
- Personnel-protection ground-fault circuit interrupters trip at 5 mA plus or minus 1 mA and must be tested before each use on construction sites.
- Rule 8-104 continuous load
- Continuous loads are limited to 80% of the rating of the conductor or overcurrent device unless the assembly is approved for 100% loading.
- Rule 8-102 voltage drop
- The maximum permitted voltage drop is 3% on a branch circuit and 5% total measured from the service entrance to the load.
- Table 16 bonding conductor
- Used to size the bonding conductor from the ampere rating of the overcurrent device protecting the circuit, expressed in square millimetres or AWG.
- Three-phase power formula
- Real power equals the square root of three times line voltage times line current times power factor for a balanced three-phase load.
- Inductive reactance formula
- Reactance in ohms equals two pi times frequency in hertz times inductance in henries; it rises with frequency and opposes changes in current.
- Transformer turns ratio
- Primary voltage divided by secondary voltage equals primary turns divided by secondary turns, and the current ratio is the inverse of that value.
- Capacitor power factor correction
- The required capacitive kVAR equals real power P times the difference between the tangents of the original and target power-factor angles.
- Conduit fill percentage
- A raceway may be filled to 53% of its interior area with one conductor, 31% with two conductors, and 40% with three or more.
- 360-degree bend rule
- No more than four quarter bends, totaling 360 degrees, are permitted between pull points in a single raceway run.
- TECK90 cable use
- Armoured cable with a moisture-resistant jacket, approved for dry, damp, and wet locations and for direct burial where so listed.
- Percent impedance and fault current
- Bolted fault current equals full-load current divided by the per-unit impedance, so a 5% transformer delivers about 20 times rated current.
- Transformer inrush current
- Energizing a transformer can draw 8 to 12 times rated current for several cycles, so time-delay overcurrent protection is normally used.
- Delta-wye phase shift
- A delta primary with a wye secondary shifts the secondary voltage by 30 electrical degrees relative to the primary voltage.
- Synchronous speed calculation
- Synchronous speed in rpm equals 120 times frequency in hertz divided by the number of poles; 60 Hz with four poles gives 1800 rpm.
- Motor slip percentage
- Slip equals synchronous speed minus rotor speed, divided by synchronous speed and multiplied by 100; rotor frequency equals slip times line frequency.
- Motor overload sizing
- Overload protection is normally set at 115% to 125% of nameplate full-load current, the exact value depending on service factor and temperature rise.
- Overload relay class
- The class number is the maximum trip time in seconds at six times rated current: Class 10 for standard loads, Class 20 or 30 for high inertia.
- Wye-delta starting torque
- Wye-delta starting applies 58% of line voltage to each winding during start and delivers one third of direct-on-line starting torque.
- VFD volts per hertz
- Below base speed a drive holds voltage proportional to frequency to keep motor flux, and therefore available torque, essentially constant.
- PLC scan cycle
- The processor reads input status, executes the ladder program from top to bottom, then updates outputs; the total elapsed time is the scan time.
- Sourcing versus sinking input
- A sourcing PNP sensor supplies positive voltage to the input terminal, while a sinking NPN sensor switches the input terminal down to common.
- Retentive timer instruction
- An RTO accumulates time while its rung is true and retains that accumulated value when the rung goes false, until a reset is executed.
- Live-zero 4-20 mA signal
- 4 mA represents 0% of span and 20 mA represents 100%; a reading of 0 mA indicates an open loop or a lost supply.
- Pt100 RTD resistance
- A platinum resistance detector reads 100 ohms at 0 degrees Celsius and rises about 0.385 ohms per degree Celsius, giving a nearly linear output.
- Thermocouple cold junction
- The reference junction temperature must be measured and compensated because the output voltage depends on the difference between hot and cold junctions.
- RS-485 termination resistor
- A 120 ohm resistor is placed across each physical end of the bus to prevent signal reflections; the bus supports up to 32 unit loads.
- Online double-conversion UPS
- The load runs continuously from the inverter, so transfer to battery is immediate and the output is isolated from input sags and transients.
- Inverting amplifier gain
- Voltage gain equals the negative of feedback resistance divided by input resistance; the minus sign indicates a 180 degree phase inversion.
- Diode bridge ripple frequency
- A full-wave bridge rectifier fed from a 60 Hz supply produces 120 Hz ripple, which a filter capacitor smooths into a steadier DC voltage.