Light hazard density
Design density of 0.10 gpm/ft² over a 1,500 ft² remote area for light hazard occupancies such as offices, schools, and churches under NFPA 13 design rules.
Ordinary Hazard Group 2
Design density of 0.20 gpm/ft² over 1,500 ft²; applies to occupancies with moderate combustibility such as mercantile storage and parking garages.
Hazen-Williams formula
Friction loss formula p = 4.52 Q^1.85 / (C^1.85 d^4.87), giving psi per foot when Q is in gpm and inside diameter d is in inches.
Elevation pressure change
Pressure changes 0.433 psi per foot of elevation; add for rises and subtract for drops when calculating available pressure at a sprinkler.
Minimum residual pressure
NFPA 13 requires at least 7 psi (0.5 bar) residual pressure at the hydraulically most remote sprinkler to ensure adequate discharge from the head.
Dry system area increase
Dry pipe and double-interlock preaction systems require a 30 percent increase in the remote area because water delivery is delayed compared with wet systems.
Hanger spacing steel pipe
NFPA 13 permits hangers at 12 ft for pipe 1 in and smaller and up to 15 ft for larger Schedule 40 steel pipe, depending on diameter.
Sway bracing intervals
For seismic restraint of steel sprinkler pipe, lateral braces are spaced at 40 ft maximum and longitudinal braces at 80 ft maximum along the run.
Thrust block purpose
A concrete block installed at underground changes in direction, tees, and reducers to resist the unbalanced hydraulic thrust force and prevent joint separation.
Groove depth gauge
A gauge used to verify that the roll-groove or cut-groove depth matches the coupling manufacturer's specification before assembly of the joint.
NPT thread taper
National Pipe Taper threads have a 1:16 taper; proper engagement seals the joint, and thread sealant is applied to male threads only.
Concrete anchor listing
Fasteners used to support hangers in concrete must be listed for the application and installed per the manufacturer's edge distance and embedment requirements.
Lockout tagout
A procedure that isolates all energy sources, including water pressure, air, and electricity, and verifies zero energy before maintenance work begins.
Confined space oxygen range
Acceptable oxygen concentration for entry is 19.5 to 23 percent; outside this range entry is prohibited without supplied air and appropriate rescue provisions.
Hot work fire watch
A permit-based procedure requiring a fire watch, removal of combustibles within 35 ft (11 m), and a charged extinguisher during cutting, brazing, or welding.
Sprinkler temperature color code
Bulb or fusible link colors identify temperature rating: orange 135°F, red 155°F, yellow 175°F, green 200°F, blue 286°F, purple 360°F, black 440°F.
Quick-response sprinkler RTI
A sprinkler with a response time index of 50 (m·s)^0.5 or less, which activates faster and is required in certain occupancies for life safety.
Deflector distance
Standard spray pendent and upright deflectors are typically installed 1 to 12 in below noncombustible ceilings; combustible ceilings require 1 to 6 in.
Spare sprinkler inventory
At least six spare sprinklers of each type and temperature rating, plus a wrench, must be kept in a cabinet near the riser for replacement.
Inspector's test connection
A valve at the hydraulically most remote point, at least 1 in in size, used to simulate a single sprinkler flow and verify the waterflow alarm.
Main drain test
A flow test at the riser main drain that records static and residual pressure; a large drop from baseline indicates a supply or valve problem.
Tamper switch supervision
A device that sends a supervisory signal to the fire alarm panel when a control valve is not fully open, ensuring the valve position is monitored.
Fire pump churn pressure
The pressure produced by a fire pump at zero flow; it typically ranges from 100 to 140 percent of the rated head and must not exceed 140 percent.
Fire pump 150% point
At 150 percent of rated flow, a centrifugal fire pump must still produce at least 65 percent of its rated head per NFPA 20 testing requirements.
Jockey pump set points
The jockey pump starts at a pressure above the fire pump start point so it maintains system pressure without causing the main fire pump to start.
Dry pipe valve trip test
A test that opens the inspector's test valve to verify the dry pipe valve trips, water reaches the test connection within the allowed time, and alarms operate.
Hydrostatic test pressure
Systems are tested at 200 psi for two hours when working pressure is 150 psi or less, or at 50 psi above working pressure for higher-rated systems.
Underground flushing velocity
Underground mains are flushed at a minimum velocity of 10 ft/s to remove debris before connection to aboveground sprinkler piping and final testing.
Clean agent hold time
The period for which a clean agent concentration is maintained in an enclosure, typically 10 minutes, to ensure extinguishment before occupants re-enter.
Deluge system operation
A deluge valve is opened by a detection system, allowing water to flow to open sprinklers or nozzles that simultaneously discharge over the protected area.
Double-interlock preaction
A preaction system that requires both a detection signal and a sprinkler operation before the valve opens, reducing accidental water discharge.