Inspection Findings and Impaired Protection
During a routine fire inspection of a four-story office building, you find the following: the sprinkler control valve in the basement is closed and tagged 'shut' with a date three days earlier; a stairwell door on the third floor is wedged open with a wooden wedge; a portable electric space heater sits under a desk in a records room, plugged into an extension cord; the fire alarm control panel shows a 'trouble' signal that has been present for two weeks; and the building's last fire drill was 14 months ago. The building has 120 occupants, a single interior stair, and a working elevator. The property manager says the valve was closed for plumbing repairs and will be reopened 'soon.' You must decide immediate actions, notifications, and how to manage the risk until corrections are complete.
1. Prioritize the deficiencies and state the immediate actions for each.
Read the worked answer
Priority 1 is the closed sprinkler valve: a building with 120 occupants and no suppression protection is unprotected. Reopen the valve immediately; if that cannot be done, start a fire watch and notify the fire department. Priority 2 is the wedged stair door, which defeats the smoke separation for the only stair; remove the wedge and repair the closer. Priority 3 is the space heater and extension cord in the records room; unplug and remove them, and inspect for other unlisted heaters. Priority 4 is the alarm trouble; have a qualified technician repair it. Schedule a fire drill within the required interval.
2. What notifications and documentation are required?
Read the worked answer
Notify the property manager, building owner, fire department, and insurer in writing. The fire department should know about the impaired sprinkler system and the single stair. Document each deficiency with a photograph, code reference, responsible person, and correction deadline. Re-inspect after corrections and keep records. If the valve remains closed, the fire watch must be documented with patrol times and names. The alarm trouble should be tracked until the panel is normal. The drill record should be retained.
3. If a fire occurs before corrections are complete, how should incident management proceed?
Read the worked answer
If a fire occurs, activate the nearest manual pull station, call 911, and announce evacuation. Occupants should use the interior stair, not the elevator, and close doors behind them. Because there is only one stair, assign staff to check floor areas and report to the assembly point. The fire department should be met at the entrance with a description of the closed valve and any remaining occupants. Establish incident command, account for all occupants, and do not reenter until the fire department authorizes it. Document the event and the status of the impaired systems.