TSSA Gas Technician 1 (G1) study materials
TSSA Gas Technician 1 (G1) study resources

TSSA Gas Technician 1 (G1) cheat sheet

TSSA Gas Technician 1 (G1) · Keep the key ideas within reach.

Quick reference

Gas Fundamentals

  • Natural gas is predominantly methane (typically 90-95%); propane (C3H8) and butane (C4H10) are the common LP gases, and all three are colourless and odourless before odorant is added.

  • Complete combustion of methane: CH4 + 2O2 -> CO2 + 2H2O. One volume of methane needs two volumes of oxygen, which is about 10 volumes of air (air is ~21% O2).

  • Propane combustion: C3H8 + 5O2 -> 3CO2 + 4H2O; propane requires roughly 24 volumes of air per volume of gas.

  • Incomplete combustion yields carbon monoxide (CO). CO is colourless, odourless and toxic; it binds haemoglobin far more strongly than oxygen, so even low ppm levels are hazardous.

  • Heating (calorific) values at standard conditions: natural gas roughly 37-39 MJ/m3 (about 1000-1050 Btu/ft3); propane vapour roughly 93-95 MJ/m3 (about 2500 Btu/ft3); butane vapour roughly 120 MJ/m3.

  • Relative density (specific gravity) with air = 1.0: natural gas about 0.60-0.65 (rises and vents upward), propane about 1.5 and butane about 2.0 (both sink and pool in low areas).

  • Flammable limits in air: natural gas roughly 4-15% by volume; propane roughly 2.1-9.5%; butane roughly 1.8-8.4%. Outside those bands the mixture will not sustain ignition.

  • Pressure units and conversions: 1 psi = 27.68 in. w.c. = 2.31 ft of water; 1 in. w.c. = 0.0361 psi = 249 Pa; 1 kPa = 4.02 in. w.c.

  • Ideal gas behaviour: P1V1/T1 = P2V2/T2 with absolute pressure and absolute temperature (K = C + 273.15). Gas volume shrinks as pressure rises and expands as temperature rises, which affects clocking and orifice sizing.

Quick reference

Codes and Regulations

  • In Ontario, the Gas Safety Act and its regulation (O. Reg. 212/01, Gaseous Fuels) plus the CSA B149.1 Natural Gas and Propane Installation Code and B149.2 Propane Storage and Handling Code set the legal requirements; the TSSA administers them.

  • Work on gas appliances and piping must be performed by or under the direction of a certified gas technician holding the correct class; a G1 holder may work on any size and type of gas appliance and may supervise G2 and G3 holders.

  • A G2 technician works on appliances up to and including 400,000 Btu/h input; a G3 is limited to specific lower-risk, smaller equipment. Class limits apply to the appliance input rating, not the building.

  • The Gas Code requires a permit or authorization before installing, altering or replacing gas equipment in most cases; the installer must notify the distributor and arrange inspection as required by the authority having jurisdiction.

  • Every gas installation must be tested for leaks before being placed in service, and the test method and pressure must match code: typically a pressure test with air, inert gas or gas at a specified pressure for a specified duration, with no drop.

  • Venting, clearances and combustion air requirements are code-prescribed: appliance clearances to combustible material come from the manufacturer's certified listing and must not be reduced without an approved method.

  • The code requires that gas appliances be accessible for inspection, servicing and cleaning, and that safety devices such as flame supervision and limit controls not be bypassed or defeated.

  • Documentation duties: leave the manufacturer's literature with the appliance, record start-up readings (manifold pressure, gas input, temperature rise, CO/CO2), and tag or red-tag unsafe equipment taken out of service.

  • Code recognises the authority having jurisdiction for local amendments; where the manufacturer's certified instructions and the code differ on a specific installation detail, the more restrictive requirement governs.

Quick reference

Installation, Servicing and Troubleshooting of Gas-Fired Appliances

  • Gas input (Btu/h) = gas rate (ft3/h) x heating value (Btu/ft3). Clocking the meter over a timed interval gives actual input; compare it with the appliance rating plate.

  • For a clocked test, ft3/h = (ft3 metered x 3600) / seconds of test. Example: 2 ft3 in 60 s = 120 ft3/h; at 1000 Btu/ft3 that is 120,000 Btu/h.

  • Manifold pressure is set to the rating plate value with the appliance firing and, for multi-stage or modulating units, at each stage; natural gas is commonly 3.5 in. w.c. and propane 10-11 in. w.c., but the plate governs.

  • Temperature rise = supply-air temperature minus return-air temperature, measured after steady operation; a rise above the plate range points to low airflow (dirty filter, blocked coil, wrong blower speed, duct restriction).

  • Combustion analysis targets: CO2 in the flue around 8-9.5% for natural gas at normal excess air; CO should stay well under 100 ppm air-free in a properly adjusted appliance; O2 typically 4-6%.

  • Draft measurement: a natural-draft appliance needs a stable negative pressure in the flue (commonly about -0.02 to -0.04 in. w.c. in the vent connector) and a draft hood that relieves stack effect; a blocked flue or spillage is an immediate hazard.

  • Flame appearance is diagnostic: a sharp blue flame with a defined inner cone indicates good primary aeration; yellow tipping, lifting or a lazy flame suggests wrong orifice, low gas pressure, dirty burner ports or excess primary air.

  • Service sequence for a no-heat call: confirm gas supply and meter valve position, verify 24 V control power and thermostat call, check ignition sequence and flame sensor signal, then measure manifold pressure and gas input before condemning a component.

  • A flame sensor reading below the control's threshold (often around 1 microamp or more required) causes short-cycling lockout; clean the sensor rod and check the ground path before replacing the control board.

Quick reference

Piping, Tubing, Fittings and Gas Supply Systems

  • Pipe sizing uses the longest-run method: measure from the meter or regulator to the farthest outlet, total the connected load in ft3/h, then read the capacity table for the pipe size, material and allowable pressure drop.

  • Natural gas piping tables in CSA B149.1 are based on a pressure drop of 0.5 in. w.c. for low-pressure systems and on the specific gravity of the gas; propane tables use the propane values.

  • Typical allowable pressure: natural gas at the meter outlet commonly 7 in. w.c. (range roughly 6-7.5 in. w.c.), with appliance manifold pressure set lower by the appliance regulator.

  • Black steel pipe is joined by threaded fittings; approved sealant must be applied to the male threads only, leaving the first two threads bare, and the pipe must be reamed and free of cuttings.

  • CSST and copper tubing require listed fittings and, for CSST, bonding to the electrical grounding system per the manufacturer's instructions and code; copper must not be used where the gas contains more than a trace of hydrogen sulphide.

  • Every appliance connection needs a manual shutoff valve in the same room and within reach, an approved union or connector, and a sediment trap (drip leg) ahead of the appliance controls where required.

  • A regulator vent must terminate outdoors in a location protected from rain, snow and blockage, and away from openings, windows and intake air; regulators must be sized for the connected load and inlet pressure.

  • Leak testing: isolate the section, apply test pressure (commonly 10-15 psi for a short duration on new steel piping, or the code-specified value), and hold with a gauge; soap-bubble test individual joints at operating pressure.

  • Underground piping requires coated or approved material, cathodic protection considerations, and must be buried at the code-specified depth; a tracer wire and riser protection are commonly required.

Quick reference

Venting, Combustion Air and Flue Gas Management

  • Category I appliances are non-condensing, negative-pressure vented and rely on a vertical chimney or vent; Category III is positive-pressure non-condensing; Category IV is positive-pressure condensing (common high-efficiency furnaces).

  • Combustion air for a confined space is provided by two permanent openings: one near the top and one near the bottom, each sized per code (often 1 in2 free area per 1000 Btu/h for inside air, or per 2000 Btu/h for outside air through horizontal ducts).

  • For a naturally vented appliance, the vent must terminate above the roof at the code height relative to the roof slope (typically 1 ft above the roof within 10 ft horizontally, and 2 ft above a roof ridge within 10 ft).

  • A draft hood is a dilution device: it relieves stack effect and downdraft, mixes room air with flue gases, and must not be modified or blocked; a spill switch or blocked-vent safety switch protects against spillage.

  • Condensing appliances produce acidic condensate (pH around 3-5) that must be neutralised where required and drained through corrosion-resistant pipe with a trap; the flue is typically PVC or CPVC rated for the temperature.

  • Vent connectors must slope upward toward the chimney at a minimum of 1/4 in. per foot of run, be as short and direct as possible, and be supported; a single-wall connector needs clearance from combustibles per code.

  • A blocked or undersized flue causes spillage of flue gases into the space, a CO hazard; test with a smoke or flame test at the draft hood and confirm spillage does not occur after several minutes of operation.

  • Direct-vent appliances draw combustion air from outdoors through a dedicated pipe and vent flue gases outside; the intake and exhaust terminals must respect the manufacturer's and code clearances to windows, doors, meters and other appliances.

Quick reference

Electrical Controls, Ignition Systems and Safety Devices

  • Standard 24 V control circuit: R is 24 V hot, C is common, W calls for heat, G runs the indoor blower, Y calls for cooling, and the thermostat closes R to W to start a heating cycle.

  • Ignition sequence: thermostat calls for heat, induced-draft blower proves via pressure switch, ignition source energises, gas valve opens, flame is proven by the flame sensor, and the blower starts after a timed delay.

  • The flame sensor (flame rectification) must see a microamp DC signal; a dirty rod, poor ground or cracked insulator causes lockout. The hot-surface igniter draws several amps and is fragile; check resistance against the manufacturer's value.

  • A pressure switch proves the draft blower is running and the vent is not blocked; it must close before ignition and stay closed during operation. A stuck-closed switch or blocked port causes lockout or a hazardous condition.

  • Safety devices that must never be bypassed: high-limit switch, rollout switch, flame rollout and blocked-vent switches, pressure switches, and the gas valve's redundant/regulator section.

  • A rollout switch is a manual-reset device that trips when flame rolls out of the burner box, usually due to a blocked flue, dirty burners or a cracked heat exchanger; it should be investigated, not simply reset.

  • The high-limit switch is an automatic-reset (or manual-reset on some models) temperature safety that opens the control circuit if the appliance overheats, typically from low airflow; it is not a substitute for proper temperature rise adjustment.

  • Typical control voltages: 24 V AC for the thermostat and gas valve operator, 120 V AC for the blower and ignition module supply, and low-voltage transformer ratings sized to the connected load.

  • Diagnose with a multimeter: verify 24 V at the gas valve during a call, check continuity of safety switches in series, and confirm the control board's fault code before replacing parts.