Specific gravity of gas

The ratio of a gas's density to that of air at the same conditions. Natural gas is roughly 0.60, so it is lighter than air and rises; propane is about 1.52 and settles in low areas.

Related: Heating value, Wobbe index
Heating value (gross and net)

The heat released when a unit volume of gas burns completely. Gross value includes latent heat recovered by condensing water vapour; net value excludes it. Ratings and clocking calculations depend on which basis is used.

Related: Manifold pressure, Gas clocking method
Wobbe index

A number that combines heating value with specific gravity to compare the interchangeability of fuel gases. Gases with similar Wobbe numbers produce similar heat input through the same orifice at the same pressure.

Related: Orifice sizing, Specific gravity of gas
Liquefied petroleum gas (propane)

A fuel stored as a liquid under moderate pressure and vaporized for use. It is heavier than air, has a distinct odour, and requires different orifice sizing and ventilation rules than natural gas.

Related: Specific gravity of gas, Excess flow valve, Regulator lock-up
Complete and incomplete combustion

Complete combustion converts all fuel carbon to carbon dioxide with sufficient oxygen. Incomplete combustion leaves carbon monoxide, soot, or aldehydes, signalling too little air, poor mixing, or a blocked flue.

Related: Excess air, Carbon monoxide safety, Flame characteristics
Excess air

The air supplied beyond the theoretical amount needed for complete combustion, usually expressed as a percentage. Enough excess air keeps carbon monoxide low without excessive dilution of the flue products.

Related: Complete and incomplete combustion, Combustion air, Carbon dioxide reading
Carbon monoxide safety

Carbon monoxide is a colourless, odourless product of incomplete combustion that binds to haemoglobin. Technicians measure it in flue gases and ambient air, and must shut down appliances producing unsafe levels or spilling into the space.

Related: Complete and incomplete combustion, Draft hood, Spillage
Gas clocking method

A field check of appliance input rate. The technician times a known volume of gas through the meter, then converts the result using the gas heating value to compare measured input with the rating plate.

Related: Heating value (gross and net), Manifold pressure, Orifice sizing
Orifice sizing

Selecting the gas jet diameter so the appliance receives its rated input at the available manifold pressure. Orifices are drilled and marked in numbered or letter sizes and must match the fuel and altitude.

Related: Manifold pressure, Wobbe index, Gas clocking method
Manifold pressure

The gas pressure measured at the appliance manifold, downstream of the appliance regulator. It is set by the manufacturer and verified with a manometer while the burner operates at full fire.

Related: Regulator lock-up, Orifice sizing, Gas clocking method
Regulator lock-up

The outlet pressure a gas regulator settles at when flow stops and the seat closes fully. Lock-up pressure is slightly above flowing pressure; excessive lock-up can overfire burners on startup.

Related: Manifold pressure, Gas pressure regulator, Excess flow valve
Gas pressure regulator

A device that reduces higher supply pressure to a steady lower outlet pressure as demand changes. It uses a diaphragm, spring, and seat, and must be vented and installed in the correct flow direction.

Related: Regulator lock-up, Manifold pressure, Relief valve
Excess flow valve

A safety device that restricts or stops gas flow when flow exceeds a set rate, as with a broken line. It is common on propane systems and must be sized so normal appliance demand does not trip it.

Related: Liquefied petroleum gas (propane), Gas pressure regulator, Leak test
Leak test (pressure test)

A documented test of piping tightness using air, inert gas, or fuel gas at a specified pressure for a set duration, with the gauge observed for drop. Test pressure and duration follow the applicable code.

Related: Purging, Excess flow valve, Pipe sizing
Pipe sizing

Choosing pipe and tubing diameters so that pressure loss between the meter or regulator and each appliance stays within code limits at full demand. It accounts for load, length, fittings, and allowable drop.

Related: Leak test (pressure test), Manifold pressure, Gas pipe materials and fittings
Purging

Displacing air from new or reopened gas piping with fuel gas before ignition is attempted. Purging prevents explosive air-gas mixtures in the pipe and appliance, and must be done to a safe location.

Related: Leak test (pressure test), Lighting and ignition sequence, Gas pipe materials and fittings
Gas pipe materials and fittings

Approved components for gas piping, such as steel pipe, corrugated stainless steel tubing, and copper where permitted, joined with approved fittings. Unlisted materials, excessive thread engagement, and concealed unions are not acceptable.

Related: Pipe sizing, Purging, Sediment trap
Sediment trap

A dirt pocket installed on the gas line close to the appliance so debris and pipe dope settle out instead of reaching the controls. It is required by code and must be accessible for cleaning.

Related: Gas pipe materials and fittings, Appliance connector
Appliance connector

A listed flexible connector, often corrugated stainless steel or coated brass, used to join the fixed piping to a movable or vibration-prone appliance. It must be sized, protected, and not pass through walls.

Related: Sediment trap, Gas pipe materials and fittings
Combustion air

The air an appliance needs for burning fuel, distinct from dilution and ventilation air. It may be drawn from the room or ducted from outdoors, and openings must remain unobstructed.

Related: Confined and unconfined space, Excess air, Make-up air
Confined and unconfined space

Code terms describing whether a room's volume is large enough to supply combustion, dilution, and ventilation air for the appliances in it. Confined spaces require two permanent openings or dedicated air ducts.

Related: Combustion air, Make-up air, Spillage
Make-up air

Air supplied to replace air exhausted by fans, dryers, or other equipment so the building does not develop negative pressure. Without it, flue gases can be pulled back down vents.

Related: Combustion air, Depressurization, Confined and unconfined space
Depressurization

A condition where indoor pressure is lower than outdoors, often from exhaust fans or unbalanced air systems. It can reverse draft, causing spillage or backdrafting of combustion products into the building.

Related: Make-up air, Spillage, Draft hood
Draft hood

A device at the appliance flue outlet that limits draft, allows dilution air, and lets flue gases spill rather than pressurize the vent. It is not a substitute for a blocked or undersized chimney.

Related: Spillage, Draft pressure, Depressurization
Spillage

Flue gases escaping from the draft hood or burner area instead of rising up the vent. Spillage signals a blocked flue, inadequate draft, or depressurization and requires immediate correction.

Related: Draft hood, Depressurization, Carbon monoxide safety
Draft pressure

The negative pressure, measured in inches of water column, that pulls flue gases through the vent. It is checked with a manometer at the appliance outlet or test port and compared with manufacturer values.

Related: Draft hood, Spillage, Vent connector
Vent connector

The pipe or flue section that carries combustion products from the appliance to the chimney or vent. It must slope upward, be securely joined, and be kept clear of combustible materials at required clearances.

Related: Draft hood, Type B vent, Clearance to combustibles
Type B vent

A listed double-wall metal vent with an inner liner and outer casing, used for venting category I gas appliances. It relies on an air space for insulation and must be installed with listed fittings and clearances.

Related: Vent connector, Category I appliance, Clearance to combustibles
Category I appliance

A gas appliance that operates with non-positive vent pressure and a flue gas temperature high enough to avoid condensation in the vent. It is vented with listed venting and checked for draft and spillage.

Related: Type B vent, Draft pressure, Spillage
Clearance to combustibles

The minimum distance, specified by listing and code, between heat-producing equipment or venting and combustible materials. Reduced clearance requires listed protection; clearance is not the same as safe working access.

Related: Type B vent, Vent connector
Flame characteristics

The appearance of a burner flame as a diagnostic. A steady blue flame with a defined inner cone indicates good combustion; yellow tips, lifting, or floating flames suggest air, pressure, or orifice problems.

Related: Excess air, Complete and incomplete combustion, Primary and secondary air
Primary and secondary air

Primary air mixes with gas before the burner port and shapes the flame; secondary air surrounds the flame to finish combustion. Wrong proportions cause yellowing, lifting, or carbon monoxide.

Related: Flame characteristics, Excess air, Burner
Burner

The component that mixes gas with air and delivers a stable flame at its ports. Burners may be inshot, ribbon, or power types, and must be aligned, clean, and correctly positioned for ignition and flame sensing.

Related: Primary and secondary air, Flame characteristics, Flame sensor
Thermocouple

A safety device that generates a small voltage from the heat of a standing pilot flame. That signal holds the gas valve open; if the pilot goes out, the valve closes to prevent unburned gas release.

Related: Thermopile, Standing pilot, Gas valve
Thermopile

A device of several thermocouples in series that produces enough voltage to power a millivolt gas valve or control. Output is checked in millivolts under load, with the pilot lit and the valve connected.

Related: Thermocouple, Standing pilot, Gas valve
Flame sensor

A probe or rod that detects flame presence by sensing current through the flame. A dirty, corroded, or poorly positioned sensor causes nuisance lockouts, so the rod and its ground are cleaned and checked first.

Related: Flame rectification, Ignition control module, Burner
Flame rectification

The principle behind electronic flame sensing, where the flame conducts current in one direction between the sensor and ground. The control module reads this small direct current to prove flame before opening the valve.

Related: Flame sensor, Ignition control module
Ignition control module

The electronic control that sequences ignition, proves flame, and supervises the gas valve. It enforces trial-for-ignition time and lockout, and its fault codes guide troubleshooting.

Related: Flame rectification, Direct spark ignition, Hot surface ignition
Direct spark ignition

An ignition method where a high-voltage spark at the burner lights the gas directly, with flame proved by a sensor. It avoids a standing pilot but requires correct spark gap and clean electrodes.

Related: Hot surface ignition, Ignition control module, Flame sensor
Hot surface ignition

An ignition method using a silicon nitride or carbide igniter that glows to light the burner. The igniter also often serves as the flame-proving element, so its resistance and warm-up time matter.

Related: Direct spark ignition, Ignition control module
Standing pilot

A small continuously burning flame that lights the main burner and powers a thermocouple or thermopile safety circuit. Its pilot orifice and flame impingement must be kept clean and correctly adjusted.

Related: Thermocouple, Thermopile
Gas valve

A valve, often with an integral regulator and redundant operators, that controls gas flow to the burner. It opens only when the safety circuit and control call for heat, and it must close fully when de-energized.

Related: Thermocouple, Ignition control module, Manifold pressure
Limit switch

A temperature- or pressure-actuated safety control that interrupts the burner circuit when a safe limit is exceeded, such as high plenum temperature. It is a safety device and must never be bypassed.

Related: Gas valve, High limit lockout, Thermostat
Thermostat

The temperature-responsive control that calls for heat and ends the call when the setpoint is met. It may be low-voltage or millivolt, and its heat anticipator or cycle settings affect comfort and cycling.

Related: Limit switch, Gas valve
Lighting and ignition sequence

The ordered steps an appliance follows: call for heat, safety checks, ignition, flame proving, main burner operation, and shutdown. Understanding the sequence lets a technician locate a fault quickly.

Related: Ignition control module, Flame sensor, Purging
Gas code and permit requirements

Rules requiring installation, alteration, and replacement work to comply with the gas code and to be authorized by permit and inspection where the authority having jurisdiction requires it. Unpermitted work creates liability and unsafe conditions.

Related: Authority having jurisdiction, Clearance to combustibles
Authority having jurisdiction

The organization or official responsible for enforcing the gas code and approving equipment, installations, and inspections. Where the code and manufacturer instructions differ, the more stringent requirement generally applies.

Related: Gas code and permit requirements, Certification and licensing
Certification and licensing

The regulatory requirement that gas work be performed by a certified technician holding the appropriate class of licence, and that appliances be certified for the fuel and application. Working beyond your class is a violation.

Related: Authority having jurisdiction, Gas code and permit requirements