TSSA Gas Technician 2 (G2) key terms
TSSA Gas Technician 2 (G2) · Get comfortable with the vocabulary.
- Specific gravity of gas
- Related: Heating value, Combustion air
The ratio of a gas's density to the density of air at the same temperature and pressure. Natural gas is roughly 0.60, so it is lighter than air and tends to rise and collect at high points.
- Heating value (MJ/m³)
- Related: Specific gravity of gas, Manifold pressure, Orifice sizing
The amount of heat released when a unit volume of gas burns completely. In Canada it is usually quoted at standard conditions, and appliances are rated and orifice-sized against a declared value.
- Wobbe index
- Related: Heating value (MJ/m³), Specific gravity of gas, Orifice sizing
A number that combines heating value and specific gravity to describe how much heat an appliance receives through a fixed orifice. Gases with similar Wobbe index can be interchanged without changing burner jets.
- Flammable limits (LFL/UFL)
- Related: Combustion air, Gas detector, Complete combustion
The range of gas concentration in air that will ignite. Below the lower limit the mixture is too lean, above the upper limit too rich. Natural gas is roughly 4.5 to 15 percent by volume.
- Complete combustion
- Related: Excess air, Carbon monoxide (CO), Combustion air
Burning in which all fuel carbon becomes carbon dioxide and all hydrogen becomes water vapour, producing maximum heat and no carbon monoxide. It requires adequate oxygen, mixing and flame stability.
- Excess air
- Related: Complete combustion, Combustion air, Draft
Air supplied beyond the theoretical amount needed for complete combustion. Some excess is needed for safety and mixing, but too much cools the flame and lowers efficiency, raising stack temperature.
- Carbon monoxide (CO)
- Related: Complete combustion, Spillage, Gas detector
A colourless, odourless, toxic gas produced by incomplete combustion. Even low concentrations cause symptoms, so any CO reading in flue gas or room air must be investigated and corrected.
- Combustion air
- Related: Excess air, Confined space, Make-up air
The air supplied to a burner to support burning. It must be drawn from outdoors or from a space large enough to supply the appliance without depressurizing the building or starving other appliances.
- Make-up air
- Related: Combustion air, Depressurization, Confined space
Outdoor air introduced to replace air exhausted by fans, dryers or ventilation so that building pressure stays near neutral and appliance venting and combustion are not affected.
- Depressurization
- Related: Spillage, Make-up air, Draft
A condition where indoor pressure is lower than outdoors, often caused by exhaust fans. It can reverse chimney draft, cause spillage and draw flue products into the living space.
- Manifold pressure
- Related: Lock-up pressure, Orifice sizing, Heating value (MJ/m³)
The gas pressure measured at the appliance manifold, downstream of the regulator, while the appliance operates. It is set to the rating plate value and verified with a manometer during commissioning.
- Lock-up pressure
- Related: Manifold pressure, Service regulator, Over-pressure protection
The outlet pressure of a gas regulator when flow stops and the valve seats. It is normally slightly above the flowing pressure and must not exceed the appliance's maximum allowable inlet pressure.
- Gas detector
- Related: Flammable limits (LFL/UFL), Carbon monoxide (CO), Purging
A portable instrument that senses combustible gas or carbon monoxide in air and alarms at a set threshold. It is used for leak surveys, purging checks and confined-space entry before work begins.
- Purging
- Related: Gas detector, Leak test, Blowdown
Displacing air from a pipe or appliance with gas, or displacing gas with air before repair, so that no flammable mixture remains in the system. It must be done to a safe location outdoors.
- Blowdown
- Related: Purging, Isolation valve
Releasing gas from a section of piping to atmosphere, usually outdoors through a controlled valve, to empty the line before maintenance or to reduce pressure.
- Code adoption and amendments
- Related: Authority having jurisdiction (AHJ), Standard reference
The process by which a jurisdiction adopts a model gas code and adds local amendments. The edition in force, plus the authority having jurisdiction's amendments, governs every installation decision.
- Authority having jurisdiction (AHJ)
- Related: Code adoption and amendments, Permit, Inspection
The official body or person responsible for enforcing the gas code and approving installations. Where the code is silent or ambiguous, the AHJ's interpretation and permission govern the work.
- Standard reference
- Related: Code adoption and amendments, Certification mark
A published technical standard cited by the gas code, such as appliance, piping or venting standards. Code compliance includes meeting the referenced standards that apply to the equipment installed.
- Certification mark
- Related: Standard reference, Rating plate, Inspection
A label from a recognized testing agency showing an appliance or component has been tested to a standard and approved for its intended use. Uncertified equipment normally cannot be installed.
- Permit
- Related: Authority having jurisdiction (AHJ), Inspection
Written authorization from the AHJ to perform gas work. It establishes scope and triggers inspections, and work must not proceed or be concealed until required inspections are complete.
- Inspection
- Related: Permit, Pressure test, Authority having jurisdiction (AHJ)
A review by the AHJ of installed work for code compliance, often at stages such as rough-in and final. Failed items must be corrected and reinspected before gas is turned on.
- Pressure test
- Related: Leak test, Inspection, Test gauge
A strength or leak test of piping performed with air, inert gas or gas at a specified pressure for a set duration, with the gauge observed and results recorded before covering or commissioning.
- Leak test
- Related: Pressure test, Soap bubble test, Test gauge
A test of an installed system or joint for gas leakage, using pressure decay on a gauge or a bubble solution on joints. It is required after assembly and before the appliance is placed in service.
- Test gauge
- Related: Pressure test, Leak test, Manometer
A pressure gauge of suitable range and accuracy used for strength and leak tests. The range must be small enough to show the specified pressure drop clearly, and it must be in calibration.
- Soap bubble test
- Related: Leak test, Gas detector
Applying a leak-detection solution to a joint and watching for growing bubbles. It is a simple, reliable check for small leaks on threaded, flanged and compression joints at operating pressure.
- Pipe sizing
- Related: Pressure drop, Load calculation, Sizing table
Selecting pipe or tubing diameter so that pressure loss at the maximum connected load stays within the code allowance. It depends on gas type, length, load, fittings and allowable pressure drop.
- Load calculation
- Related: Pipe sizing, Rating plate, Sizing table
Adding the rated input of every connected appliance, with diversity allowances where the code permits, to determine the total gas demand used for sizing meters, service lines and headers.
- Pressure drop
- Related: Pipe sizing, Sizing table, Manifold pressure
The loss of pressure along a piping run caused by friction in pipe, tubing and fittings. The code sets a maximum allowable drop from the meter or regulator to the appliance inlet.
- Sizing table
- Related: Pipe sizing, Pressure drop, Load calculation
A code table listing capacity for each pipe or tubing size at given lengths and pressure drops. Using the correct table and gas type is essential to a compliant sizing decision.
- Sediment trap (drip leg)
- Related: Drip leg, Appliance connector, Isolation valve
A capped vertical drop installed at the appliance connection so dirt, scale and condensate fall out of the gas stream before reaching the controls. It must be installed and left accessible.
- Appliance connector
- Related: Sediment trap (drip leg), Isolation valve, Bonding
A listed flexible or semi-rigid connector between the rigid piping and the appliance, of limited length and not concealed. It must be protected from damage and not used to correct misalignment.
- Isolation valve
- Related: Appliance connector, Blowdown
A manual shut-off valve at or near an appliance that stops gas flow for service. It must be accessible, listed for gas service and clearly identified so it can be found quickly in an emergency.
- Bonding
- Related: Appliance connector, CSST
Electrically connecting gas piping to the building grounding system so it cannot become energized or act as a conductor. Bonding is required by electrical code and is separate from grounding the pipe itself.
- CSST
- Related: Bonding, Appliance connector, Pipe sizing
Corrugated stainless steel tubing, a flexible gas piping material. It must be installed per its listing, with approved fittings, protection from damage and the manufacturer's required bonding.
- Vent connector
- Related: Draft, Spillage, Vent termination
The pipe or duct that carries flue products from the appliance outlet to the chimney or vent. It must be sized, sloped, supported and joined to the vent without reducing the appliance's draft.
- Draft
- Related: Vent connector, Spillage, Depressurization
The movement of air and flue products through an appliance and vent, created by buoyancy in a chimney or by a fan. Adequate draft removes combustion products and supplies air to the burner.
- Spillage
- Related: Draft, Carbon monoxide (CO), Depressurization
Flue products escaping from the appliance's draft hood or relief opening into the room instead of going up the vent. It indicates poor draft and is a serious carbon monoxide hazard.
- Vent termination
- Related: Vent connector, Direct-vent appliance, Draft
The point where a vent or flue ends outdoors. Location must meet clearance rules from windows, doors, intakes and property lines to keep flue products out of the building and away from people.
- Direct-vent appliance
- Related: Vent termination, Combustion air, Depressurization
An appliance that takes combustion air from outdoors through one pipe and discharges flue products outdoors through another, isolated from indoor air. It is less affected by building depressurization.
- Confined space
- Related: Combustion air, Make-up air, Depressurization
A room or enclosure with limited volume relative to appliance input, where the code requires dedicated openings or ducts to supply combustion and ventilation air from outdoors.
- Clearance to combustibles
- Related: Rating plate, Vent connector, Certification mark
The minimum distance an appliance or vent must be kept from combustible material, stated on the rating plate and in the listing. Reduced clearance requires an approved protective assembly.
- Rating plate
- Related: Manifold pressure, Clearance to combustibles, Load calculation
The manufacturer's label giving model, input rate, gas type, manifold pressure, clearances and venting requirements. It is the primary reference for installation and for verifying correct operation.
- Orifice sizing
- Related: Manifold pressure, Heating value (MJ/m³), Wobbe index
Choosing the burner jet diameter that delivers the rated input at the available manifold pressure and gas heating value. Converting between gas types usually requires changing orifices and resetting pressure.
- Manometer
- Related: Manifold pressure, Test gauge, Draft
A pressure-measuring instrument, often a U-tube or digital gauge, used to read gas supply, manifold and draft pressures. It is the tool for verifying pressures against the rating plate.
- Clock test
- Related: Orifice sizing, Heating value (MJ/m³), Manifold pressure
Timing the gas meter dial while the appliance runs to measure actual gas input, then comparing it with the rated input. It verifies orifice sizing, pressure and gas heating value together.
- Flame rectification
- Related: Thermocouple, Ignition control, Safety shut-off valve
A flame-sensing method where the flame conducts current between an igniter and burner, proving flame to the control. Loss of signal shuts the gas valve within the safety timing.
- Thermocouple
- Related: Flame rectification, Safety shut-off valve, Pilot
A device that generates a small voltage when heated by a pilot flame, holding a safety valve open. If the flame is lost, the voltage falls and the valve closes.
- Safety shut-off valve
- Related: Thermocouple, Flame rectification, Ignition control
A valve that closes automatically on flame failure, power loss or a safety limit trip, stopping gas to the burner. It must be tested for tightness and correct response during servicing.
- Ignition control
- Related: Flame rectification, Safety shut-off valve, Lockout
The electronic module that sequences ignition, proves flame, supervises the burner and locks out on failure. Its timing and retry behaviour must match the appliance's listing.
- Lockout
- Related: Ignition control, Safety shut-off valve, Troubleshooting sequence
A control state after failed ignition or flame loss in which gas is shut off and the appliance stops trying until manually reset. Repeated lockouts point to a fault that must be found.
- Troubleshooting sequence
- Related: Lockout, Manometer, Flame rectification
A systematic diagnostic order: confirm the complaint, check gas supply and pressure, verify electrical power and controls, then test ignition, flame and venting before replacing parts.
- Service regulator
- Related: Lock-up pressure, Manifold pressure, Over-pressure protection
The regulator that reduces distribution pressure to the pressure delivered to the building's piping. Its outlet setting and lock-up determine the supply available for appliance regulators.
- Over-pressure protection
- Related: Service regulator, Lock-up pressure, Safety shut-off valve
A device or arrangement that limits downstream pressure if a regulator fails, protecting appliances and piping from excess pressure. It may be a relief valve, monitor regulator or vent limiter.