TSSA Gas Technician 2 (G2): Venting, Combustion Air and Appliance Installation

TSSA Gas Technician 2 (G2) · Work through your exam, one topic at a time.

All guide sections

Venting, Combustion Air and Appliance Installation

Domain 4 - Venting, combustion air and appliance installation

This domain tests whether an appliance can safely get air in and flue gases out. Exam questions centre on vent categories, connector slope and clearance, termination height, confined-space calculations and free area.

Venting systems

  • Natural draft (Category I) appliances need a draft hood and a vertical gravity vent. The connector slopes upward toward the vent at not less than 20 mm/m (1/4 in/ft), is as short and direct as possible, is supported, and is never reduced in size.
  • Clearance to combustibles: single-wall connector 6 in (150 mm); listed Type B vent 1 in (25 mm). Where the rating plate asks for more, the plate wins.
  • Positive-pressure (Category III) and condensing (Category IV) appliances use the vent material named in their instructions - commonly PVC, CPVC or polypropylene for Cat IV - slope back to the appliance, and must never be common-vented with natural draft appliances.
  • Termination height: at least 3 ft above the highest point where it passes through the roof and 2 ft above anything within 10 ft, kept clear of windows, doors and air intakes.

Combustion air

  • A space is confined if its volume is less than 50 ft³ per 1,000 Btu/h (4.8 m³/kW) of the total input of every appliance in it.
  • Confined spaces need two permanent openings, one within 12 in of the top and one within 12 in of the bottom, sized from the code tables by whether air comes from indoors or outdoors.
  • Size to free area, not the grille's nominal dimensions. A louver with 75% free area must be about one third larger than the calculated figure.
  • Watch building pressure: exhaust fans, dryers and HRVs can reverse draft. Room-sealed direct-vent appliances take outside air and avoid the problem.

Worked example

A 120,000 Btu/h boiler and a 40,000 Btu/h water heater share a 4 m × 5 m × 2.4 m room. Volume = 48 m³. Total input = 160,000 Btu/h ≈ 46.9 kW; required volume = 46.9 × 4.8 ≈ 225 m³. The room is far below that, so the space is confined and needs correctly sized openings, or a change to direct-vent. Sizing on the boiler alone would undersize the openings by 25%.

Traps

Using room volume without adding every appliance; sizing openings for one appliance only; substituting louver frame dimensions for free area; sloping a natural draft connector the wrong way or letting it sag; and reusing an existing chimney without checking its size, lining and condition.