General Gas Knowledge

  • Natural gas is predominantly methane (CH4); typical Ontario utility-delivered heating value is about 37-38 MJ/m3 (roughly 1,000 BTU/ft3), so appliance input ratings assume that range.

  • Propane (C3H8) has a heating value near 93-95 MJ/m3 (about 2,500 BTU/ft3) and is roughly 1.5-1.7 times heavier than air; natural gas is about 0.6 times the density of air and rises when released.

  • Complete combustion: CH4 + 2O2 -> CO2 + 2H2O. Incomplete combustion produces carbon monoxide (CO), a colourless, odourless gas that is toxic by displacing oxygen in blood.

  • Perfect (stoichiometric) combustion of natural gas needs about 10 volumes of air per 1 volume of gas; excess air is supplied in practice to ensure complete combustion.

  • The three legs of the combustion triangle are fuel, oxygen and ignition source; removing any one prevents or extinguishes combustion.

  • Odorant added to natural gas is typically mercaptan (ethyl mercaptan); propane also carries an odorant. A gas smell is a safety signal, not a measure of concentration.

  • Flame characteristics: a properly adjusted natural gas flame is blue with a slightly soft inner cone; yellow tipping suggests insufficient primary air, while lifting or flashback suggests excess primary air or excessive pressure.

  • Gas pressure units: 1 inch water column (in. w.c.) = 0.249 kPa; 1 psi = 27.7 in. w.c. = 6.895 kPa. Manifold pressure for natural gas appliances is commonly 3.5 in. w.c. (about 0.87 kPa).

  • Gas laws: at constant temperature, pressure times volume is constant (Boyle); at constant pressure, volume is proportional to absolute temperature (Charles). These explain why pipe sizing and venting depend on gas density and temperature.

Quick reference

Safety and Regulations

  • In Ontario, the Technical Standards and Safety Act and the Gas Utilization Code (a regulation under that Act) govern gas work; the TSSA administers licensing and enforcement.

  • A G3 certificate of qualification permits work only under supervision; independent work on gas appliances and piping requires a higher class (G2 or G1), and the scope of permitted work is defined by regulation.

  • The Gas Utilization Code sets clearance, ventilation, piping, and appliance installation requirements; manufacturer's certified installation instructions also apply and must be followed.

  • Before any gas work: locate and identify the gas shut-off, verify the appliance is de-energized, and confirm no ignition sources. Purge and test with an approved leak-detection method, never with an open flame.

  • Leak testing of new or altered piping is done with air or inert gas at the pressure and duration specified by the Code; soap solution or an approved electronic detector is used to locate leaks.

  • A gas leak response: evacuate, eliminate ignition sources, do not operate electrical switches, call the gas distributor and emergency services from a safe location; the utility controls the meter/service shut-off.

  • Carbon monoxide alarms are required in dwellings with fuel-burning appliances or attached garages per the Ontario Fire Code; CO alarms must be located per manufacturer instructions and kept clear of dead air spaces.

  • Combustion air and clearance requirements protect against spillage of flue gases; a draft hood or draft proving device must not be obstructed, and spillage at the draft hood indicates a venting or air-supply problem.

  • Documentation: permits, inspection records, and pressure-test records are part of compliant gas work; work must be inspected by the authority having jurisdiction before being placed in service where required.

Quick reference

Gas Piping, Tubing and System Installation

  • Approved piping materials include black steel pipe, corrugated stainless steel tubing (CSST) and copper tubing where permitted by the Code; each has specific restrictions (e.g., copper not permitted in some concealed or corrosive locations).

  • Pipe sizing uses the Code's sizing tables based on total connected load, allowable pressure drop, and equivalent length; each fitting adds an equivalent length (a 90-degree elbow is commonly counted as several feet of straight pipe).

  • Jointing: steel pipe uses threaded joints with approved pipe dope or PTFE tape applied to male threads only; CSST uses manufacturer-approved fittings and must be bonded per manufacturer and Code requirements.

  • Support and protection: piping must be supported at Code-specified intervals, protected from physical damage, and sleeved where it passes through masonry or concrete.

  • Sediment trap (drip leg) is required at the appliance connection to catch debris and moisture; it is installed as a tee with a capped nipple below the appliance inlet.

  • A manual shut-off valve must be installed upstream of each appliance, accessible, and identified; a union or approved disconnect is provided for servicing.

  • Purging and leak testing: after assembly, the system is pressure-tested with air or inert gas, then purged of air before gas is introduced; air in the line can cause unsafe ignition or flame failure.

  • Underground and concealed piping requires approved coatings, sleeving and protection from corrosion; CSST and copper must not be buried or embedded where the Code prohibits it.

  • Pipe identification: gas piping must be identified (e.g., yellow marking or labelling) where required by the Code; valves and regulators must be accessible and labelled.

Quick reference

Venting and Combustion Air

  • Category I appliances are negative-pressure, non-condensing appliances that vent into a vertical chimney or Type B vent; Category IV appliances are positive-pressure condensing appliances requiring listed plastic venting (e.g., PVC/CPVC/PP) per manufacturer instructions.

  • Vent sizing and height follow the Code and manufacturer tables based on appliance input, vent diameter, and equivalent length; a vent that is too large or too short can cause condensation and spillage.

  • Draft hoods and draft proving switches protect against backdraft; a spillage test (e.g., flame or smoke at the draft hood) confirms the vent is drawing properly.

  • Combustion air: appliances in a confined space need two permanent openings (one high, one low) sized per Code based on total input; a single opening may be permitted under specific conditions.

  • Direct-vent (sealed combustion) appliances take combustion air from outdoors and vent outdoors; they must maintain clearances to windows, doors, and air intakes specified by the manufacturer and Code.

  • Vent termination clearances: minimum distances from windows, doors, air intakes, grade, and adjacent buildings are specified; a vent must not terminate where flue gases can re-enter the building.

  • Condensate from condensing appliances must drain to an approved location through a trap per manufacturer instructions; freezing or blocked drains can cause appliance lockout.

  • Venting a fan-assisted appliance into a masonry chimney requires a listed liner if the chimney is not suitable; a chimney must be inspected for condition and sized for the appliance.

  • Common venting of multiple appliances requires Code/manufacturer-approved manifold design; appliances must not be common-vented with unlisted combinations.

Quick reference

Basic Gas Appliance Installation and Servicing

  • Appliance installation requires the certified rating plate data (input, manifold pressure, gas type) to match the supply; an appliance rated for natural gas must not be connected to propane without an approved conversion kit.

  • Manifold pressure is set with a manometer at the appliance regulator; natural gas typically 3.5 in. w.c. and propane typically 10-11 in. w.c., but always follow the rating plate.

  • Check gas supply pressure with all appliances operating (load test); inlet pressure must be within the appliance's specified range, neither too low (incomplete combustion) nor too high (damage).

  • Combustion analysis: measure CO, CO2, and O2 in flue gases; a CO reading in the flue above the manufacturer's limit indicates a combustion problem requiring correction.

  • Ignition systems: standing pilot, intermittent pilot, hot surface ignition (HSI), and direct spark. Servicing includes cleaning flame sensors, checking thermocouples, and verifying ignition sequence.

  • Thermocouple/thermopile testing: a thermocouple generates millivolts when heated; low output causes pilot dropout. Flame sensors must be clean and positioned in the flame for reliable sensing.

  • Gas valve and regulator servicing: verify inlet and outlet pressures, check for debris, and confirm the valve opens and closes; never bypass safety devices such as the high-limit or spill switch.

  • After service: leak test all joints, verify venting and combustion air, perform a spillage/combustion check, and confirm the appliance cycles through its full sequence of operation.

  • Preventive maintenance includes cleaning burners and orifices, checking for corrosion, verifying clearances, and confirming the appliance is listed and installed per manufacturer instructions.