TSSA Gas Technician 3 (G3) study materials
TSSA Gas Technician 3 (G3) study resources

TSSA Gas Technician 3 (G3) flashcards

TSSA Gas Technician 3 (G3) · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Heating value of natural gas
Natural gas, mostly methane, delivers roughly 37-38 MJ/m3 (about 1,000 BTU/ft3) as supplied by Ontario utilities; appliance input ratings assume this value.
Propane relative density
Propane is about 1.5-1.7 times heavier than air and settles in low areas; natural gas is lighter than air and rises when released.
Complete combustion equation
Methane plus oxygen yields carbon dioxide and water: CH4 + 2O2 -> CO2 + 2H2O. Insufficient oxygen produces carbon monoxide instead.
Stoichiometric air requirement
Perfect combustion of natural gas needs about 10 volumes of air per volume of gas; practical systems supply excess air to ensure complete combustion.
Combustion triangle
Fuel, oxygen and an ignition source are required for combustion; removing any one of the three prevents or extinguishes burning.
Yellow flame tip cause
A yellow-tipped flame usually indicates insufficient primary air or a dirty burner; a lifting flame suggests excess primary air or excessive gas pressure.
Water column conversion
One inch of water column equals 0.249 kPa; one psi equals 27.7 in. w.c. or 6.895 kPa. Manifold pressure for natural gas is often 3.5 in. w.c.
Odorant in natural gas
Mercaptan odorant is added so leaks can be detected by smell; the smell is a safety warning and does not indicate concentration.
Ontario gas regulation
The Technical Standards and Safety Act and the Gas Utilization Code regulate gas work in Ontario; TSSA administers licensing and enforcement.
G3 scope of work
A G3 certificate holder works only under supervision; independent work on gas appliances and piping requires a G2 or G1 certificate.
Approved leak detection
Leaks are located with soap solution or an approved electronic detector, never an open flame; new piping is pressure-tested with air or inert gas.
Gas leak emergency response
Evacuate, remove ignition sources, avoid operating electrical switches, and call the gas distributor and emergency services from a safe location.
CO alarm requirement
Dwellings with fuel-burning appliances or attached garages require carbon monoxide alarms under the Ontario Fire Code, installed per manufacturer instructions.
Draft hood spillage meaning
Spillage of flue gases at a draft hood signals a venting or combustion air problem and must be corrected before the appliance is returned to service.
Approved piping materials
Black steel pipe, corrugated stainless steel tubing and copper tubing are used where the Code permits; copper is restricted in some concealed or corrosive locations.
Equivalent length sizing
Pipe sizing uses total load and equivalent length; each fitting, such as a 90-degree elbow, adds equivalent straight-pipe length to the run.
Threaded joint sealing
Approved pipe dope or PTFE tape is applied to male threads only when joining steel gas pipe; excess sealant inside the pipe can block orifices.
Sediment trap purpose
A drip leg installed at the appliance inlet as a capped tee catches debris and moisture before it reaches the gas valve or burners.
Appliance shut-off valve
A manual shut-off valve is installed upstream of each appliance, kept accessible and identified, with a union or approved disconnect for servicing.
Piping pressure test
New or altered gas piping is tested with air or inert gas at Code-specified pressure and duration, then purged of air before gas is introduced.
CSST bonding requirement
Corrugated stainless steel tubing must be bonded and installed with manufacturer-approved fittings per Code requirements to reduce lightning-related arc risk.
Category I appliance
A Category I appliance is non-condensing and operates under negative pressure, venting into a vertical chimney or listed Type B vent.
Category IV appliance
A Category IV appliance is condensing and operates under positive pressure, requiring listed plastic venting such as PVC, CPVC or polypropylene per manufacturer instructions.
Confined space combustion air
Appliances in a confined space need permanent high and low openings sized by Code to total input; a single opening is allowed only under specific conditions.
Direct-vent appliance
A direct-vent or sealed combustion appliance draws combustion air from outdoors and vents outdoors, maintaining manufacturer clearances to openings and intakes.
Vent termination clearance
Vent terminals must keep Code and manufacturer minimum distances from windows, doors, air intakes, grade and adjacent buildings to prevent flue gas re-entry.
Condensate trap requirement
Condensing appliances drain acidic condensate through a trap to an approved location; a blocked or frozen drain can cause appliance lockout.
Rating plate verification
The rating plate gives input, manifold pressure and gas type; the appliance must match the supply, and propane conversion requires an approved kit.
Manifold pressure check
Manifold pressure is measured with a manometer at the appliance regulator; typical values are 3.5 in. w.c. for natural gas and 10-11 in. w.c. for propane, per rating plate.
Load test of supply pressure
Supply pressure is checked with all appliances operating; inlet pressure must stay within the appliance's specified range to prevent incomplete combustion or damage.
Flue CO measurement
Combustion analysis measures CO, CO2 and O2 in flue gases; flue CO above the manufacturer's limit indicates a combustion problem requiring correction.
Thermocouple function
A thermocouple generates millivolts when heated by the pilot flame; low output causes pilot dropout, so the thermocouple and flame sensor must be clean and properly positioned.