TSSA Gas Technician 3 (G3): Gas Piping, Tubing and System Installation

TSSA Gas Technician 3 (G3) · Work through your exam, one topic at a time.

All guide sections

Gas Piping, Tubing and System Installation

Gas Piping, Tubing and System Installation tests materials, sizing, routing, protection, and pressure testing. The exam expects you to read a simple system, choose an approved material, size the line for the load, and install it so it can be tested, purged, and serviced.

Materials and fittings

  • Approved materials include Schedule 40 black steel pipe, wrought-iron pipe, CSA-certified CSST, and copper tubing where the code and local utility permit it. Propane systems commonly use copper; many Ontario natural gas utilities restrict or prohibit it.
  • Use malleable iron or forged steel fittings. Dielectric unions prevent galvanic corrosion. Never use cast iron, aluminum, or plastic fittings indoors unless specifically listed.
  • Join steel pipe with approved thread compound or tape applied to male threads only, leaving the first two threads bare. Do not put compound on flare faces.
  • CSST must be listed, installed with the manufacturer's strike plates and sleeves, and bonded to the electrical grounding system with a conductor sized per the Canadian Electrical Code.

Sizing and layout

Use the longest-run method: measure from the meter to the farthest appliance, add equivalent length for fittings and valves, and apply the code's allowable pressure drop (commonly 0.5 in. w.c. for low-pressure natural gas). Size each section for the connected load downstream. Provide a shutoff valve, union, and sediment trap (drip leg) at each appliance; slope horizontal piping to the trap and support it at code intervals.

Worked example

A 1/2-in. steel branch with an equivalent length of 30 ft has a table capacity of 65,000 Btu/h at 0.5 in. w.c. drop. It serves a 45,000 Btu/h range and a 35,000 Btu/h water heater, total 80,000 Btu/h. Because 80,000 > 65,000, the branch is undersized; increase to 3/4-in. or reduce the load. Recheck the table after adding fittings.

Traps

  • Sizing on developed length only and ignoring fittings.
  • Forgetting the sediment trap or installing it in the wrong direction.
  • Using thread compound on flare seats.
  • Concealing a union or valve where it cannot be accessed.
  • Bonding CSST to a water line instead of the electrical grounding electrode.