- Fire tetrahedron
- Four components needed for combustion: fuel, oxidizer, heat, and an uninhibited chemical chain reaction. Removing any one component extinguishes the fire.
- Flash point
- The lowest temperature at which a liquid gives off enough vapor to form an ignitable mixture with air near its surface, though burning does not necessarily continue once the igniter is removed.
- Lower flammable limit
- The minimum fuel vapor concentration in air, expressed as percent by volume, that will support combustion. Below the LFL the mixture is too lean to burn.
- Heat release rate
- The rate at which energy is released by a burning item, usually in kilowatts, equal to mass loss rate times heat of combustion. It governs fire growth and time to flashover.
- BLEVE
- Boiling liquid expanding vapor explosion: failure of a pressurized vessel holding liquid above its atmospheric boiling point, producing sudden vapor expansion, vessel fragments, and often a fireball.
- Authority having jurisdiction
- The organization, office, or individual responsible for approving equipment, an installation, or a procedure and for enforcing the adopted fire code within its legal boundaries.
- Occupancy classification
- Grouping of a building or space by its use, such as assembly, business, educational, industrial, storage, or residential, which sets the fire safety requirements in NFPA 101 and related codes.
- NFPA 25
- Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems. It specifies frequencies for gauges, valves, sprinklers, main drains, and flow tests.
- Performance-based design
- A design approach using engineering analysis, fire modeling, and documented acceptance criteria to demonstrate that stated fire safety goals and objectives are met, rather than following explicit prescriptive rules.
- Smoke detector spacing
- NFPA 72 allows up to 30 ft spacing and 900 sq ft per spot-type smoke detector on smooth ceilings, with detectors placed within 21 ft of sidewalls unless ceiling height changes the spacing.
- Public mode notification
- Audible alarms meant to alert occupants generally must sound at least 15 dBA above average ambient or 5 dBA above maximum ambient for 60 seconds, and at least 75 dBA at 10 ft.
- Addressable alarm system
- A system in which each initiating and notification device has a unique identifier, so the control panel annunciates the exact device in alarm or trouble instead of only a circuit zone.
- Alarm verification
- A panel feature that delays a smoke detector alarm to confirm it, reducing nuisance alarms. The panel resets and rechecks the detector, typically adding 60 to 180 seconds of delay.
- Sprinkler K-factor
- A discharge coefficient relating sprinkler flow to pressure: flow in gpm equals K times the square root of pressure in psi. A K of 5.6 is typical of a half-inch orifice.
- ESFR sprinkler
- Early Suppression Fast Response sprinkler designed to deliver high-density water and suppress a high-challenge storage fire without in-rack sprinklers, subject to limits on ceiling height and clearance.
- Fire pump churn
- The no-flow operating condition of a fire pump. Churn pressure must not exceed 140 percent of rated pressure so system components are not over-pressurized.
- Sprinkler design density
- The minimum water application rate in gpm per square foot over a specified remote area in a hydraulic calculation. The required density depends on the occupancy hazard classification.
- Class K extinguisher
- A wet chemical extinguisher intended for cooking media fires involving vegetable or animal oils and fats, required near commercial cooking appliances such as deep fryers and ranges.
- Common path of travel
- The single-direction route occupants must travel before two independent ways out are available. Codes cap its length by occupancy, and it counts within the overall travel distance limit.
- Occupant load factor
- The floor area in square feet or square meters assigned per person for a given use. Dividing floor area by the factor yields the occupant load used to size egress components.
- RSET
- Required safe egress time: the interval from ignition until occupants reach a place of safety, including detection, alarm, pre-movement, and travel time. It must be shorter than ASET.
- Exit access
- The portion of a means of egress leading from the occupied space to an exit, such as rooms, aisles, and corridors. Travel distance is measured along this path.
- Dead-end corridor
- A corridor segment with only one direction of escape travel. Its length is limited by code, commonly 20 ft in nonsprinklered and 50 ft in sprinklered business occupancies.
- Hazen-Williams formula
- An empirical pipe friction equation: head loss per foot equals 4.52 times Q to the 1.85 divided by C to the 1.85 times d to the 4.87, with Q in gpm and d in inches.
- Residual pressure
- The pressure remaining at a hydrant or gauge while water is flowing during a flow test. Comparing it with static pressure characterizes the available supply.
- Needed fire flow
- The estimated water rate in gpm required to control a fire in a building, derived from construction, occupancy, exposure, and communication factors and used to judge water supply adequacy.
- Pitot pressure
- Velocity pressure measured at a flowing hydrant or nozzle outlet with a pitot tube. Flow is computed from it as Q equals 29.83 times d squared times the square root of pressure in psi.
- Class IB liquid
- A flammable liquid with a closed-cup flash point below 73 degrees F and a boiling point at or above 100 degrees F, as classified by NFPA 30.
- NFPA 704 diamond
- A hazard identification marking with four colored quadrants rating health, flammability, and instability from 0 to 4, plus white for special hazards such as water reactivity or oxidizing ability.
- Kst
- The deflagration index: maximum rate of pressure rise normalized to vessel volume for a dust, expressed in bar-meters per second and used to assign St-1, St-2, or St-3 explosibility classes.
- Risk
- Risk is the product of an event's probability and the severity of its consequences. Risk management compares the evaluated risk against tolerable criteria and then selects controls.
- Deflagration venting
- Relief openings sized per NFPA 68 that let combustion gases and pressure escape an enclosure during a dust or gas deflagration, protecting the structure from catastrophic failure.