Quick reference

Power System Planning, Load Forecasting, and Resource Adequacy

  • Reserve margin = (installed capacity − peak demand) / peak demand; planning reserve margin targets commonly fall in the 15–20% range for summer-peaking systems, set by the applicable balancing authority or state commission.

  • Loss of Load Expectation (LOLE) is expressed in days per year (common target: 0.1 day/yr, i.e., one event in ten years); Loss of Load Probability (LOLP) is the hourly or daily probability summed over the study period.

  • Expected Unserved Energy (EUE) is in MWh/yr and captures outage magnitude, not just frequency; a system can meet LOLE and still fail an EUE criterion.

  • Effective load-carrying capability (ELCC) credits a variable resource by the peak-load increase it can reliably serve; solar ELCC is typically far below nameplate and lower than wind in a summer-peaking system.

  • Hourly load shapes drive planning more than annual energy: coincident peak contribution, not capacity factor, determines capacity value of demand response and storage.

  • Forecast error compounds with horizon: near-term (1–5 yr) forecasts anchor on econometric and end-use models, long-range (10–20 yr) on scenario and weather-normalized trend methods.

  • Weather normalization regresses load against heating/cooling degree days; failing to normalize biases the forecast and distorts the load growth rate used in integrated resource plans.

  • Transmission and generation must be planned together: a resource adequacy study that ignores deliverability can count capacity that cannot reach load under contingency conditions.

Quick reference

Generation, Transmission, and Distribution Engineering

  • Three-phase power: S = √3 · V_LL · I · (cos θ + j sin θ); per-phase analysis uses V_LN = V_LL / √3 and total S = 3 · V_LN · I*.

  • Per-unit conversion: Z_pu = Z_actual / Z_base, with Z_base = V_base² / S_base; changing base requires Z_pu,new = Z_pu,old · (S_new/S_old) · (V_old/V_new)².

  • Voltage drop on a feeder approximates ΔV ≈ I·R·cos θ + I·X·sin θ per phase; distribution feeders are resistance-dominated, transmission lines reactance-dominated.

  • Surge impedance loading (SIL) = V_LL² / Z_c; a line loaded near SIL has flat voltage profile and minimal reactive requirement.

  • Transformer impedance and MVA rating set fault current: I_sc ≈ I_rated / Z_pu (for a source of infinite strength), so lower percent impedance raises available fault current.

  • Corona and radio interference rise with surface voltage gradient; conductor bundling and larger diameter reduce gradient and audible noise at EHV.

  • Distribution reliability indices: SAIDI = total customer-minutes interrupted / total customers served; SAIFI = total customer interruptions / total customers served.

  • Ampacity is set by conductor temperature limit under worst-case ambient and wind; reconductoring or dynamic line rating can raise transfer capability without new right-of-way.

Quick reference

Power System Analysis, Protection, and Control

  • Power flow (load flow) solves bus voltage magnitudes and angles from P-Q injections; the slack bus fixes V and θ, PV buses fix P and |V|, PQ buses fix P and Q.

  • N-1 criterion: the system must survive the loss of any single element without cascading or uncontrolled loss of load; N-1-1 adds a second contingency during repair.

  • Symmetrical components: positive, negative, and zero sequence networks; zero-sequence current flows only where a ground path exists, so a delta winding blocks it.

  • Protection zones must overlap; overlapping CTs and redundant schemes ensure no fault is unprotected and no zone trips for an out-of-zone fault.

  • Distance relay reach is set in secondary ohms and scaled by the CT/VT ratio; Zone 1 typically covers about 80% of the line to avoid overreaching into the next line.

  • Differential protection compares currents entering and leaving a zone; it is the standard for transformers, buses, and generators because it is inherently selective.

  • Stability: the equal-area criterion shows the critical clearing time is the fault duration beyond which the accelerating area exceeds the decelerating area and the generator loses synchronism.

  • Automatic voltage regulators and power system stabilizers damp oscillatory modes; undamped inter-area oscillation appears as low-frequency (0.1–1 Hz) power swings.

Quick reference

Utility Economics, Cost of Service, and Ratemaking

  • Revenue requirement = operating expenses + depreciation + taxes + (rate base × authorized rate of return); rate base is net plant in service plus working capital less accumulated depreciation.

  • Cost-of-service study allocates costs by function (production, transmission, distribution, customer), then by classification (demand, energy, customer), then to rate classes by responsibility.

  • Demand allocators use class contribution to system peak, class noncoincident peak, or average-and-excess methods; the choice shifts cost between classes and is litigated.

  • Rate design: two-part tariff = customer charge + volumetric energy charge; demand charge recovers demand-related cost and is set from class coincident or noncoincident peak.

  • Straight-fixed-variable and three-part rates recover fixed cost through fixed charges, reducing the cross-subsidy from low-use to high-use customers under volumetric rates.

  • Depreciation uses straight-line remaining-life or whole-life methods; depreciation expense plus return on rate base is the annual carrying cost of plant.

  • Test year selection (historical, future, or hybrid) determines whether known-and-measurable cost changes enter the revenue requirement; attrition relief addresses lag between rate cases.

  • Decoupling and revenue stabilization mechanisms break the link between sales volume and revenue, removing the utility incentive to oppose efficiency.

Quick reference

Regulatory Framework, Tariffs, and Compliance

  • Filed tariffs govern service; a utility may not charge outside its filed tariff, and deviations require commission approval or a tariff-authorized exception.

  • Cost-of-service ratemaking requires just and reasonable rates, no undue discrimination between similarly situated customers, and recovery of prudently incurred costs.

  • Rate case procedure: file, notice, intervention, discovery, hearings, proposed decision, commission vote; interim rates may be authorized subject to refund.

  • Fuel and purchased-power adjustment clauses pass through variable costs with a reasonableness review; prudency challenges can disallow recovery.

  • Federal versus state jurisdiction: wholesale sales and interstate transmission are federally regulated; retail sales, distribution, and siting are generally state-regulated.

  • Compliance obligations include FERC reporting, NERC reliability standards with auditable evidence, and state-mandated renewable portfolio targets with alternative compliance payments.

  • Tariff riders recover specific costs (storm, environmental, energy efficiency) outside base rates; each rider has eligibility, true-up, and reconciliation requirements.

  • Confidentiality rules govern critical energy infrastructure information and customer data; unauthorized disclosure is a compliance violation, not just a policy breach.

Quick reference

Safety, Reliability, and Power Quality Standards

  • Voltage limits: ANSI Range A service voltage is ±5% of nominal; Range B allows ±10% excursions of limited duration. Utilization voltage limits are tighter at the service entrance.

  • Frequency deviation is governed by balancing area control; normal interconnection frequency is 60 Hz in North America, with underfrequency load shedding staged below nominal.

  • Harmonics: IEEE 519 limits voltage distortion at the point of common coupling (typically 5% THD) and current distortion by customer size relative to short-circuit ratio.

  • Flicker is assessed by short-term and long-term Pst/Plt indices; arc furnaces and welders are the usual sources and may require mitigation as a condition of service.

  • Reliability standards set transmission planning and operations requirements; violations carry monetary penalties scaled by severity and duration.

  • Temporary protective grounding, minimum approach distances, and equipotential zones govern live-line work; approach distances increase with voltage class.

  • Arc flash incident energy determines PPE category; an energized-work permit is required when work inside the arc flash boundary cannot be de-energized.

  • Momentary interruptions (sags, recloser operations) are counted separately from sustained interruptions; a sustained interruption typically exceeds five minutes.

Quick reference

Environmental Permitting, Siting, and Grid Interconnection

  • Interconnection process: feasibility, system impact, and facilities studies; the interconnection agreement and cost allocation follow the study results.

  • Interconnection queue rules govern study order and deposit forfeiture; cluster-study approaches process many requests together to reduce serial study delay.

  • Network upgrade costs are allocated by the interconnection tariff; identifying which upgrades are caused by the generator versus needed for reliability is the central dispute.

  • Siting approvals typically require a certificate of public convenience and necessity plus separate environmental permits for air, water, wetlands, and endangered species.

  • National Environmental Policy Act review triggers an environmental assessment or a more extensive environmental impact statement for major federal actions.

  • Endangered species and cultural resource surveys must precede construction; a late finding can halt a project mid-schedule.

  • Clean Air Act permitting distinguishes minor sources from major sources; new-source review can require best available control technology and emission offsets.

  • Transmission line siting considers right-of-way width, electromagnetic field exposure, visual impact, and landowner compensation; eminent domain is a last resort requiring statutory authority.

Quick reference

Renewable and Distributed Energy Resources Integration

  • IEEE 1547 governs DER interconnection to the distribution system: voltage and frequency ride-through, anti-islanding, and power quality requirements apply at the point of common coupling.

  • Smart inverter functions (volt-var, volt-watt, frequency-watt) let DER support voltage and frequency rather than trip offline, reducing aggregate loss during disturbances.

  • Hosting capacity is the DER penetration a feeder can accommodate without violating voltage, thermal, or protection limits; it is computed per feeder and per location.

  • Duck curve: midday solar depresses net load and the evening ramp steepens; ramping capability, not total energy, becomes the binding constraint.

  • Inverter-based resources lack physical inertia; grid-forming inverters and synchronous condensers provide synthetic inertia and short-circuit strength.

  • Net metering and successor tariffs determine DER compensation; the compensation method affects the cross-subsidy between DER owners and non-owners.

  • Aggregated DER can provide capacity, frequency response, and voltage support; qualification requires telemetry, dispatchability, and performance testing.

  • Curtailment is a cost of oversupply; the economic curtailment threshold compares the value of energy against the cost of the upgrade that would avoid it.

Quick reference

Asset Management, Operations, and Maintenance

  • Health index scoring combines condition, age, loading, and failure history to rank assets; the score drives repair, refurbish, or replace decisions.

  • Risk = probability of failure × consequence (safety, environmental, reliability, financial); risk-ranked portfolios allocate limited capital to the highest-risk assets first.

  • Condition monitoring: dissolved gas analysis for transformers, partial discharge testing for cables and switchgear, thermography for connections.

  • Preventive maintenance intervals are set by manufacturer guidance, regulatory requirements, and observed failure modes; time-based and condition-based programs are combined.

  • Critical spares strategy weighs lead time, failure rate, and outage cost; long-lead transformers justify strategic spares or sharing agreements.

  • Outage management coordinates clearances, switching orders, and restoration; switching orders are written, checked, and read back to prevent misoperation.

  • Vegetation management is a leading driver of distribution reliability; cycle trimming intervals are set by species growth rate and clearance requirements.

  • End-of-life replacement planning uses failure probability curves and expected outage cost to time replacement before reliability degrades.

Quick reference

Professional Ethics, Records, and Public Interest Obligations

  • The engineer's paramount obligation is public health, safety, and welfare; a client or employer instruction does not override it.

  • Seal only work you prepared or directly supervised; sealing another's work without review is a violation regardless of employment relationship.

  • Disclose conflicts of interest, including financial interests in suppliers or contractors, in writing before participating in a procurement decision.

  • Records retention: calculations, test results, and design bases must be retained for the period required by statute and by the utility's records schedule, and produced on request in rate cases and litigation.

  • Ex parte communication rules restrict contact with commissioners and staff during contested proceedings; violations can taint a proceeding.

  • Whistleblower and reporting duties: report known violations of reliability, environmental, or safety requirements to the appropriate authority even if internal channels fail.

  • Testimony and discovery require truthful, complete disclosure; withholding adverse data from a regulatory filing is a professional misconduct issue, not a strategy.

  • Competence limits: accept assignments only within your competence, and obtain qualified review when a task exceeds your expertise.