Nuisance Tripping on a 5 HP Single-Phase Compressor
A 5 HP, 230 V single-phase capacitor-start air compressor serves a commercial shop. The nameplate reads 26.0 A, service factor 1.15, 40 °C ambient. The installing contractor ran 10 AWG THWN-2 copper in EMT, protected by a 30 A inverse-time breaker, and set the overload relay at 30 A. The compressor starts and runs fine most of the time, but the breaker trips on roughly one start in five; measured inrush is 112 A for about 0.4 seconds. The panel is 60 ft from the motor and sits in a hot mechanical room. The shop owner says, 'Just put in a bigger breaker until it stops tripping.'
1. Verify the branch-circuit conductor size and the short-circuit and ground-fault protection against Article 430. What is wrong with the installation as built?
Read the worked answer
Motor full-load current: Table 430.248 for a 5 HP, 230 V single-phase motor gives FLC = 28 A (use the table value, not the nameplate, for conductor and branch-circuit protection sizing).
Conductors (430.22): 28 A × 125% = 35 A required ampacity.
- 10 AWG Cu THWN-2 at 75 °C = 35 A - it just makes it in a 30 °C ambient.
- But the raceway runs through a 40 °C mechanical room. Applying the 310.15(B)(2)(a) correction factor of 0.88 for the 75 °C column: 35 A × 0.88 = 30.8 A, which is below the required 35 A. The 10 AWG is therefore undersized; 8 AWG Cu (50 A × 0.88 = 44 A) is required.
Short-circuit and ground-fault protection (430.52(C)(1), Table 430.52): An inverse-time breaker may be sized at 250% of FLC = 28 × 2.5 = 70 A. The 30 A breaker installed is only 107% of FLC - roughly one-third of what the code permits and far too small to ride through a 112 A inrush.
Diagnosis: The breaker is tripping because it is the wrong device for the duty, not because the motor is bad. Replacing it with a 70 A inverse-time breaker sized per 430.52 is the code-correct fix. The overload relay is a separate issue and does not protect against short circuits.
2. How should the overload relay be set, and why is the existing 30 A setting questionable?
Read the worked answer
Rule (430.32(A)(1)): For a motor with a marked service factor of 1.15 or greater, overload protection is set at no more than 125% of the nameplate full-load current. This is a maximum, not a target.
- 26.0 A × 1.25 = 32.5 A maximum.
- The installed 30 A setting is only 115% of nameplate, and the motor is running in a 40 °C ambient where its actual winding temperature and running current will be at the top of the range. A 30 A overload on a 26 A motor with a 1.15 SF will nuisance trip during long, hot run cycles or after a hard start.
Correct approach:
- Set the overload to the maximum permitted value from the manufacturer's selection table for this motor - typically the 32.5 A (or next standard device) point.
- Measure actual running current under load. If running current is well under 26 A, the overload can be set lower for better protection; if it approaches 26–28 A, the compressor may be over-loaded or the supply voltage low.
- 430.32 permits the overload to be increased beyond 125% only where the manufacturer's data or a documented engineering evaluation supports it - do not simply crank it up.
Key distinction to explain to the owner: The overload relay protects the motor winding from sustained overcurrent. The branch breaker protects the conductors from short circuit and ground fault. Setting both at 30 A confuses the two functions.
3. The owner insists on 'a bigger breaker until it stops tripping.' What is your response, and what is the absolute maximum permitted?
Read the worked answer
Response: Increasing the breaker is only legitimate up to the limits in 430.52 - and only if the conductor ampacity is also correct. Oversizing a breaker past the code maximum leaves the conductors unprotected against overload and creates a fire hazard, and the inspector will red-tag it.
Permitted maximums for this motor (FLC = 28 A):
- Standard rating: 250% = 70 A. That is the normal design point and is almost certainly enough here, since inrush is 112 A (160% of a 70 A breaker) - well within a thermal-magnetic breaker's instantaneous trip range.
- If the motor still will not start: 430.52(C)(1) Exception No. 1 allows the next higher standard rating, and Exception No. 2 allows up to 400% of FLC (112 A) where the need is demonstrated. Beyond 400%, the protection must be selected under engineering supervision with documented evidence.
Before going above 250%, investigate the real cause:
- Voltage drop on the 60 ft run - low voltage lengthens the start and raises current.
- Breaker located in a hot mechanical room - a breaker's thermal calibration derates at elevated ambient; consider a breaker rated for the environment or a different enclosure location.
- A tired or wrong-size run capacitor causing hard starting.
- Unloader valve not functioning, so the compressor starts against head pressure.
Document the decision and the measured starting current; an inspector or the owner's insurer may ask for it.