Ohm's law
Current equals voltage divided by resistance (I = E/R); it lets you solve for any one of the three values when the other two are known in a DC or resistive AC circuit.
Three-phase power formula
For a balanced three-phase load, true power in watts equals 1.732 times line voltage times line current times the power factor of the load.
Voltage-drop formula
Single-phase voltage drop equals two times K times current times length in feet, divided by conductor circular mils, where K is 12.9 for copper and 21.2 for aluminum.
GFCI requirements
Ground-fault circuit-interrupter protection is required for 125-volt, 15- and 20-ampere receptacles in bathrooms, kitchens, garages, outdoors, crawl spaces, and unfinished basements of dwellings.
AFCI requirement
Arc-fault circuit-interrupter protection is required on branch circuits supplying outlets in dwelling unit kitchens, bedrooms, living rooms, laundry areas, and similar rooms.
Working clearance rule
Switchboards and panelboards need a clear working space at least 3 feet deep, 30 inches wide, and 6½ feet high, increased where live parts are exposed.
Conduit fill percentages
A raceway may be filled to 53 percent for one conductor, 31 percent for two conductors, and 40 percent for three or more, based on Chapter 9 tables.
Box fill counting
Each 14 AWG conductor counts 2.0 cubic inches, 12 AWG 2.25, and 10 AWG 2.5; each device yoke counts as two conductors of the largest size.
NM cable support
Nonmetallic-sheathed cable must be secured within 12 inches of each box and supported at intervals not exceeding 4½ feet along its run.
Motor branch-circuit sizing
Branch-circuit conductors supplying a single motor are sized at 125 percent of the motor full-load current taken from the code tables, not the nameplate current.
Motor disconnecting means
A disconnecting means must be within sight of the motor and its controller, or capable of being locked in the open position, so maintenance is safe.
Flexible cord restriction
Flexible cords and cables may not be used as a substitute for the fixed wiring of a structure, nor run through walls, ceilings, or floors.
Class I Division 1
A location where flammable gases or vapors are present under normal operating conditions, or frequently during repair and maintenance, is Class I, Division 1.
Health care redundant ground
Patient care areas require an insulated copper equipment grounding conductor terminating at the receptacle grounding terminal, in addition to the metallic raceway or cable armor ground.
Pool equipotential bonding
Pool shells, metal fittings, ladders, and adjacent metal must be connected to a common bonding grid with a solid copper conductor not smaller than 8 AWG.
PV rapid shutdown
Photovoltaic systems must provide a rapid shutdown function that reduces conductor voltage within the array boundary to a safe level for firefighters.
Emergency versus standby
Emergency systems protect life safety and egress lighting under Article 700; legally required standby is Article 701; optional standby for convenience loads is Article 702.
Class 2 circuit limit
A Class 2 circuit supplied by a listed Class 2 power source is limited to 100 volt-amperes, which permits smaller conductors and less stringent installation rules.
Primary protector
A listed primary protector is required on communications conductors entering a building where they are exposed to lightning or to contact with power conductors.
Communications bonding
Communications cable must be bonded to the building grounding electrode system with an insulated copper conductor not smaller than 14 AWG.
Lump-sum contract
A contract stating one fixed price for the complete scope of work, placing the risk of quantity errors and rising material costs on the contractor.
Retainage
A percentage of each progress payment, commonly 5 to 10 percent, withheld by the owner until final completion is accepted.
Change order
A written, signed modification to the contract scope, price, or schedule; work performed without one may not be paid.
Scale reading
On a drawing marked 1/8 inch equals 1 foot, one inch measured on the plan represents 8 feet of actual building dimension.
Bid components
A bid price equals direct materials plus direct labor plus subcontractors plus overhead plus profit, with contingency added where the scope is uncertain.
Riser diagram
A single-line drawing showing the service entrance, feeders, panelboards, disconnects, and grounding, without physical dimensions or exact routing.
Lockout/tagout
The procedure of opening the disconnect, applying a personal lock and tag, and verifying the circuit is de-energized before work begins.
Limited approach boundary
For exposed live parts at 750 volts or less, the limited approach boundary is 10 feet, and only qualified persons may cross it.
Ladder 4-to-1 rule
The base of a ladder is set out 1 foot for every 4 feet of working height, and the ladder extends 3 feet above the landing.
Connecticut licensing agency
Electrical contractor and journeyman licenses in Connecticut are issued and renewed by the Department of Consumer Protection under Chapter 393 of the General Statutes.
E-1 and E-2 licenses
The E-1 license permits a contractor to perform and contract for unlimited electrical work; the E-2 journeyman license permits work under an E-1 contractor.
Permit and inspection
A local building official issues the electrical permit and the electrical inspector approves the work, which must be inspected before it is concealed.