CT Electrician study materials
CT Electrician study resources

CT Electrician cheat sheet

CT Electrician · Keep the key ideas within reach.

Quick reference

General Electrical Knowledge and Electrical Theory

  • Ohm's law: E = I × R, with rearranged forms I = E/R and R = E/I for DC and resistive AC circuits.

  • Power relationships: P = E × I = I² × R = E²/R; 1 horsepower = 746 watts; 1 kWh = 1,000 watts for one hour.

  • Balanced three-phase power: P = √3 × E(line) × I(line) × power factor.

  • Single-phase voltage drop: VD = (2 × K × I × L) ÷ circular mils, where K = 12.9 for copper and 21.2 for aluminum.

  • Conductors in parallel must be 1/0 AWG or larger and identical in material, size, length, insulation, and termination method.

  • In a 3-wire 120/240 V single-phase system the neutral carries only the unbalanced current; a 240 V load connects line-to-line.

  • Ampacity is first corrected for ambient temperature, then derated when more than three current-carrying conductors share a raceway.

  • Skin effect raises effective AC resistance above the DC value listed in Chapter 9, Table 8, especially in large conductors.

Quick reference

Wiring and Protection

  • GFCI protection is required for 125 V, 15- and 20-A receptacles in bathrooms, garages, outdoors, crawl spaces, unfinished basements, and kitchen countertop areas.

  • AFCI protection is required for branch circuits supplying outlets in dwelling unit kitchens, bedrooms, living rooms, laundry areas, and similar rooms.

  • Dwelling receptacle spacing: no point along a wall line may be more than 6 ft from a receptacle, and wall spaces 2 ft or wider require one.

  • The next-size-up rule allows an overcurrent device rated 800 A or less to exceed conductor ampacity where ampacity falls between standard ratings.

  • Working space at electrical equipment: 3 ft deep, 30 in wide, 6½ ft high, with depth increased for exposed live parts.

  • Equipment grounding conductors are sized from Table 250.122 using the rating of the circuit overcurrent protective device.

  • Up to six service disconnects are permitted in a single service, grouped in one location and marked as service equipment.

  • The grounding electrode conductor is sized from Table 250.66 based on the largest service-entrance conductor.

Quick reference

Wiring Methods and Materials

  • Conduit fill limits: 53% for one conductor, 31% for two conductors, 40% for three or more, based on Chapter 9, Table 1.

  • Box fill: each 14 AWG conductor counts 2.0 cu in, 12 AWG counts 2.25, 10 AWG counts 2.5; each yoke counts as two of the largest conductor.

  • Type NM cable must be secured within 12 in of a box and supported at intervals not exceeding 4½ ft.

  • Type NM cable is not permitted in wet locations, in masonry or concrete, or where subject to physical damage.

  • Direct-buried residential branch circuits at 120/240 V need 24 in of cover, reduced to 18 in with GFCI protection and a 20 A maximum.

  • EMT must be supported at intervals not exceeding 10 ft and within 3 ft of each box or fitting.

  • Rigid metal conduit must be supported within 3 ft of termination and at intervals not exceeding 10 ft.

  • The grounded conductor is identified by white or gray; the equipment grounding conductor by green, green with yellow stripes, or bare.

Quick reference

Equipment for General Use

  • Motor branch-circuit conductors are sized at 125% of the full-load current taken from the code tables, not the nameplate current.

  • Motor overload protection is sized to nameplate current; short-circuit and ground-fault protection is selected from Table 430.52.

  • A motor disconnecting means must be within sight of the motor and controller, or capable of being locked in the open position.

  • Flexible cords may not be used as a substitute for the fixed wiring of a structure or run through walls, ceilings, or floors.

  • Switches and circuit breakers must be installed so the highest position does not exceed 6 ft 7 in above the floor.

  • Receptacles installed in dwelling units must be listed tamper-resistant.

  • Transformer overcurrent protection must comply with Table 450.3(B), which sets the permitted primary-only and primary-and-secondary arrangements.

  • Luminaires in clothes closets must maintain the storage-space clearances specified by code.

Quick reference

Special Occupancies

  • Class I locations contain flammable gases or vapors; Class II locations contain combustible dust; Class III locations contain easily ignitable fibers or flyings.

  • Division 1 covers conditions expected under normal operation; Division 2 covers conditions expected only under abnormal operation.

  • Zone systems classify gases as Zone 0, 1, or 2 and dusts as Zone 20, 21, or 22.

  • Patient care areas of health care facilities require redundant grounding: a metallic raceway or armored cable plus an insulated copper conductor.

  • Critical care areas use isolated power systems with line isolation monitors that alarm at 5 mA.

  • In commercial garages the space within 18 in of the floor is classified as a Class I, Division 2 location.

  • Assembly occupancies require emergency lighting and exit illumination with an approved power source.

Quick reference

Special Equipment

  • Swimming pools require an equipotential bonding grid for the shell, metal fittings, ladders, and adjacent metal, using copper not smaller than 8 AWG.

  • Receptacles are prohibited within 6 ft of a pool's inside wall, and receptacles within 20 ft require GFCI protection.

  • Photovoltaic systems require a rapid shutdown function that limits conductor voltage within the array boundary.

  • A PV system disconnecting means must be installed at a readily accessible location and marked with a plaque.

  • Fire pump conductors must have continuity of power and may not be protected by a ground-fault device that opens the circuit.

  • Electric vehicle supply equipment rated over 60 A or over 150 V to ground requires a listed disconnecting means.

  • Elevators, escalators, and moving walks are covered by Article 620, including traveling cables and machine room bonding.

Quick reference

Special Conditions

  • Emergency systems (Article 700) serve life-safety loads; legally required standby is Article 701; optional standby is Article 702.

  • Emergency system wiring must be kept independent of normal wiring and protected against fire damage.

  • A Class 2 circuit supplied by a listed Class 2 power source is limited to 100 VA, permitting smaller conductors and reduced installation rules.

  • Fire alarm circuits are covered by Article 760 and must use listed fire-protection cable or raceway.

  • Class 1 remote-control and signaling circuits are limited only by their overcurrent protection, unlike Class 2 and 3 circuits.

  • Interconnected electric power production sources are governed by Article 705 and require a dedicated disconnecting means.

  • Sensitive electronic equipment branch circuits are addressed by Article 647 for separately derived systems.

Quick reference

Communication Systems

  • Article 800 covers communications circuits, Article 820 covers coaxial cable distribution, and Article 830 covers network-powered broadband.

  • A listed primary protector is required where communications conductors enter a building and are exposed to lightning.

  • Communications cable must be bonded to the building grounding electrode system with copper not smaller than 14 AWG.

  • Communications cables must be separated from power conductors by at least 2 in where they run in close parallel paths.

  • Abandoned communications cable that cannot be identified for future use must be removed.

  • Communications cables may not occupy the same raceway or enclosure as light, power, Class 1, or non-power-limited fire alarm conductors.

Quick reference

Business Management

  • A lump-sum contract fixes one price for the entire scope, shifting quantity and price risk to the contractor.

  • Time-and-materials contracts bill actual labor hours at a stated rate plus material cost and markup.

  • Retainage is a portion of each progress payment, commonly 5% to 10%, held until final acceptance.

  • A change order must be written and signed before the work proceeds to protect the right to payment.

  • Overhead covers indirect costs such as insurance, vehicles, rent, and licenses; profit is added after direct and indirect costs.

  • A mechanics lien is a claim against the property for unpaid labor and materials, with deadlines set by statute.

  • Employers in Connecticut must carry workers' compensation insurance and register for unemployment tax.

  • The licensed contractor obtains permits before work starts; permit fees are set by the local authority.

Quick reference

Estimating and Plan Reading

  • A drawing scale of 1/8 in = 1 ft means one inch on the plan equals 8 feet of actual dimension.

  • Conductor takeoff typically adds 5% to 10% waste; boxes and devices typically add 2% to 5%.

  • Bid price = direct material + direct labor + subcontractors + overhead + profit, plus contingency for uncertain scope.

  • A riser diagram shows the service, feeders, panelboards, disconnects, and grounding without physical dimensions.

  • A panel schedule lists circuit numbers, breaker ratings, connected loads, and phase balance.

  • Floor plan symbols identify lighting outlets, receptacles, switches, and special equipment locations.

  • Labor units expressed in hours per item are multiplied by the loaded hourly rate to produce labor cost.

  • Quantities are counted by item and extended to price using current supplier quotations, not catalog list prices.

Quick reference

Safety Practices

  • Lockout/tagout: open the disconnect, apply a personal lock and tag, then verify the circuit is de-energized with a tester before work.

  • Rubber insulating glove classes: Class 00 rated 500 V AC, Class 0 rated 1,000 V AC, Class 2 rated 17,000 V AC.

  • The limited approach boundary for exposed live parts at 750 V or less is 10 ft; only qualified persons may cross it.

  • On construction sites all 125 V, 15- and 20-A receptacle outlets must have GFCI protection or an assured equipment grounding conductor program.

  • Ladder setup follows the 4-to-1 rule, with the ladder extending 3 ft above the landing.

  • Test the tester on a known live source before and after verifying a circuit is de-energized.

  • Confined space entry requires atmospheric testing, an attendant, and permit documentation before entry.

  • Head protection, eye protection, and arc-rated clothing are selected from the incident energy and hazard risk category of the task.

Quick reference

Connecticut Electrical Regulations

  • Connecticut adopts NFPA 70 with Connecticut amendments; the amended State Building Code governs permitting and inspection.

  • Electrical licenses are issued and renewed by the Department of Consumer Protection under Chapter 393 of the Connecticut General Statutes.

  • License classes include the E-1 electrical contractor and E-2 journeyman electrician, plus the limited L-5 and L-6 licenses.

  • Apprentices must be registered with the state and work under the supervision of a licensed electrician.

  • Local building officials issue electrical permits and the electrical inspector approves the work before it is concealed.

  • Only a licensed electrical contractor may offer or contract to perform electrical work for the public.

  • License renewal requires payment of the renewal fee and completion of the continuing education required for that license class.

Quick reference

General Electrical Knowledge and Electrical Theory

  • Ohm's law: E = I × R, with rearranged forms I = E/R and R = E/I for DC and resistive AC circuits.

  • Power relationships: P = E × I = I² × R = E²/R; 1 horsepower = 746 watts; 1 kWh = 1,000 watts for one hour.

  • Balanced three-phase power: P = √3 × E(line) × I(line) × power factor.

  • Single-phase voltage drop: VD = (2 × K × I × L) ÷ circular mils, where K = 12.9 for copper and 21.2 for aluminum.

  • Conductors in parallel must be 1/0 AWG or larger and identical in material, size, length, insulation, and termination method.

  • In a 3-wire 120/240 V single-phase system the neutral carries only the unbalanced current; a 240 V load connects line-to-line.

  • Ampacity is first corrected for ambient temperature, then derated when more than three current-carrying conductors share a raceway.

  • Skin effect raises effective AC resistance above the DC value listed in Chapter 9, Table 8, especially in large conductors.