32 cards. Read the term and the definition here. The deck at the top of this page is optional.

NFPA 72 pathway Class A
A supervised circuit that continues to operate with a single open or ground fault; the redundant path allows all devices to remain functional.
NFPA 72 pathway Class B
A supervised circuit where a single open fault causes loss of function beyond the fault but does not affect devices ahead of it; no redundant path.
NFPA 72 pathway Class X
A supervised circuit that continues to operate during a single open, short, or ground fault; requires isolation at each device or segment.
Record of completion
A document required by NFPA 72 that records the installed system configuration, sequence of operations, and acceptance test results, signed by the contractor and owner.
Smoke detector spacing rule
On a smooth ceiling, spot smoke detectors are spaced at 30 ft (9.1 m) with 21 ft (6.4 m) between detectors on a row and 10.6 ft (3.2 m) from walls.
Intelligibility requirement
Voice alarm systems must achieve a common intelligibility scale (CIS) or speech transmission index (STI) of at least 0.45 in each occupiable area.
Primary power supply
A dedicated 120 VAC branch circuit for the fire alarm system, marked "FIRE ALARM CIRCUIT CONTROL," with disconnecting means accessible only to authorized personnel.
Secondary power supply
Batteries sized for 24 hours of standby plus 5 minutes of alarm (or 4 minutes for voice systems), per NFPA 72 Table 10.6.7.2.1.
Battery capacity formula
Required Ah = (standby current × standby hours + alarm current × alarm hours) × 1.25, using the manufacturer's end-of-life derating.
Voltage drop formula
Vdrop = 2 × L × I × R, where L is one-way distance in feet and R is resistance per foot; the end-of-line voltage must exceed the appliance minimum.
Ohm's law and power
V = IR; P = VI = I²R = V²/R. A 24 VDC appliance drawing 0.5 A dissipates 12 W and presents 48 Ω.
Ground fault annunciation
The control unit must annunciate a ground fault on any supervised circuit conductor; a single ground must not cause an alarm.
Battery recharge requirement
The charger must restore the battery to 85% capacity within 24 hours after a full discharge; float voltage for a 24 V lead-acid bank is about 27.6 V.
Ionization smoke detector
A detector using a radioactive source to ionize air; it responds better to flaming, fast fires with small particles than to smoldering fires.
Photoelectric smoke detector
A detector using light scattering or obscuration; it responds better to smoldering fires with larger particles than to flaming fires.
Rate-of-rise heat detector
A heat detector that triggers when temperature rises faster than about 15°F per minute, independent of the absolute temperature reached.
Duct smoke detector
A detector installed in an air-handling system rated over 2,000 cfm to shut down the unit and close dampers; sampling tubes must span the duct width.
Manual pull station location
Pull stations must be within 5 ft (1.5 m) of each exit door, mounted 42-48 in. (1.07-1.22 m) above the floor, and unobstructed.
Projected-beam detector spacing
Maximum 60 ft (18.3 m) between units and 30 ft (9.1 m) from walls; the beam path must be unobstructed and the detector listed for the ceiling height.
Heat detector spacing
On a smooth ceiling, 50 ft (15.2 m) for 135°F units and 30 ft (9.1 m) for 194°F units, with the first detector within half the spacing of a wall.
Audible signal level
At least 15 dBA above average ambient or 5 dBA above maximum ambient, whichever is greater, measured 5 ft (1.5 m) from the floor.
Maximum audible level
Public mode audible signals must not exceed 110 dBA at minimum hearing distance; above 105 dBA ambient, visible-only notification may be permitted.
Visible appliance candela
Candela ratings are selected from NFPA 72 Chapter 18 tables based on room size and mounting height; 15 cd minimum for a 20 ft × 20 ft room.
Strobe synchronization
Visible appliances in the same field of view must flash in phase within 10 milliseconds; a listed sync module or the control unit provides synchronization.
Strobe flash rate
Strobes must flash at 1-2 Hz with a pulse duration of at least 0.1 second, maintained for the life of the appliance.
Notification appliance circuit
A supervised circuit (Class A or B) supplying audible and visible appliances; an end-of-line resistor detects open, short, and ground faults.
Wall-mounted strobe height
Wall-mounted visible appliances are installed 80-96 in. (2.03-2.44 m) above the floor; ceiling-mounted units are at the center of the room.
Plenum-rated cable
CMP cable is required in environmental air-handling spaces unless installed in metallic conduit; CMR cable is used in vertical shafts.
Acceptance testing scope
NFPA 72 Chapter 14 requires testing 100% of initiating devices, 100% of notification appliances, and all control unit functions for new installations.
Smoke detector sensitivity testing
Sensitivity must be tested within 1 year of installation and every 5 years thereafter, using a listed test method; the detector must be within its listed range.
Cable support interval
Fire alarm cables must be supported at intervals not exceeding 10 ft (3 m) and within 12 in. (300 mm) of boxes.
ITM frequencies
Monthly for control unit indicators and batteries, quarterly for alarm and supervisory devices, annually for all initiating and notification devices, every 5 years for smoke sensitivity.