Connecticut Low Voltage Practice flashcards
Connecticut Low Voltage Practice · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's Law
- V = I × R. Voltage equals current times resistance. Used to calculate voltage drop, current draw, and resistance in low-voltage circuits.
- Power formula
- P = V × I = I²R = V²/R. Determines wattage, heat, and power supply sizing for low-voltage devices.
- Series circuit
- Components connected end-to-end; current is constant, voltage divides. Total resistance is the sum of individual resistances.
- Parallel circuit
- Components connected across the same voltage; voltage is constant, current divides. Total resistance is less than the smallest branch.
- Voltage drop formula
- VD = 2 × K × I × L / CM for single-phase. K=12.9 copper, 21.2 aluminum. Keep branch drop ≤3%, total ≤5%.
- Class 2 circuit
- NEC Article 725 power-limited circuit up to 100 VA and 30 V. Used for low-voltage control, signaling, and communications.
- Plenum-rated cable
- CMP cable listed for air-handling spaces. Required by NEC 300.22(C) in ducts and plenums to limit smoke and flame spread.
- Bend radius
- Minimum curve radius for cable; typically 4× diameter for UTP, 10× for coax/fiber. Exceeding causes attenuation and signal loss.
- Cable separation
- Low-voltage cables must be at least 2 in. (50 mm) from power conductors, or separated by a barrier, per NEC 725.136 and 800.133.
- NEC Article 725
- Covers Class 1, 2, and 3 remote-control, signaling, and power-limited circuits. Defines wiring methods and separation requirements.
- NEC Article 760
- Covers fire alarm systems. Defines NPLFA and PLFA circuits and requires listed FPL, FPLR, or FPLP cable.
- NEC Article 800
- Covers communications circuits (telephone, data). Requires separation from power and grounding/bonding of cable shields.
- NEC Article 820
- Covers community antenna television (CATV) and radio distribution systems. Requires bonding of coaxial cable shield to ground.
- Connecticut L-1 license
- Low-voltage electrical license allowing installation and service of fire alarm, security, data, and communications systems; no line-voltage work.
- Connecticut CEU requirement
- Licensed electricians must complete 7 hours of continuing education annually, including code update and safety hours. Verify with DCP.
- Connecticut fire alarm permit
- Required for fire alarm installation; issued by local AHJ under Connecticut Fire Safety Code and NFPA 72.
- Smoke detector spacing
- NFPA 72: 30 ft (9.1 m) on smooth ceilings up to 10 ft high; use 0.7× ceiling height for higher ceilings, minimum 30 ft.
- NAC voltage drop
- Notification appliance circuit voltage drop must not exceed 10% of rated voltage at the last appliance. Calculate using device current draw.
- Class A vs Class B
- Class A fire alarm circuit returns to panel and survives one open. Class B does not return; an open disables downstream devices.
- Fire alarm battery sizing
- Calculate standby (24 h) plus alarm (5 min) load per NFPA 72; add 20% derating for battery aging.
- Access control fail-safe
- Lock releases on power loss. Required for egress doors per NFPA 101; must interface with fire alarm for release on alarm.
- PoE standards
- IEEE 802.3af (15.4 W), 802.3at (30 W), 802.3bt (60/90 W). Used for IP cameras, access control, and VoIP phones over UTP.
- Wiegand protocol
- Access control communication standard using 26-bit or 34-bit format. Cable distance limited to 500 ft (150 m) with 22 AWG.
- CCTV storage calculation
- GB = bitrate (Mbps) × 3600 × hours × days / 8 / 1000. Determines hard drive size for video retention.
- TIA-568 channel length
- Maximum 100 m (328 ft) total: 90 m horizontal cable plus 10 m patch cords. Applies to twisted-pair Ethernet.
- Fiber loss budget
- Sum of connector loss (0.75 dB each), splice loss (0.3 dB), and fiber attenuation (0.35 dB/km SM; 3.5 dB/km OM). Must be below link budget.
- HDBaseT
- Audio/video extension standard over Cat cable up to 100 m. Transmits HDMI, Ethernet, power, and control.
- TIA-607 bonding
- Requires telecommunications bonding backbone (TBB) and grounding busbar (TGB) bonded to service ground with minimum 6 AWG copper.
- Ground resistance
- NEC 250.53 requires ≤25 ohms for a single electrode; add a second if higher. Telecom ground typically ≤5 ohms.
- Lockout/tagout
- OSHA 1910.147 procedure to isolate energy before work. Verify absence of voltage with a meter before touching conductors.
- Connecticut contractor bond
- Surety bond required for electrical contractor registration in Connecticut; amount varies by license type. Verify with DCP.
- Division 27 and 28
- MasterFormat divisions for Communications (27) and Electronic Safety and Security (28). Define low-voltage scope in construction documents.