- Ohm's law
- For a linear conductor at constant temperature, voltage equals current times resistance (V = I × R). Power dissipated is P = V × I = I²R = V²/R.
- Kirchhoff's current law
- At any node in an electrical circuit, the algebraic sum of currents entering the node equals zero (sum of currents in = sum of currents out). This expresses conservation of charge.
- Thevenin's theorem
- Any linear two-terminal network can be replaced by an equivalent voltage source V_th in series with resistance R_th. V_th is the open-circuit voltage; R_th is the resistance seen with all independent sources killed.
- Resonance in series RLC
- Series resonance occurs at f₀ = 1/(2π√(LC)), where inductive and capacitive reactances cancel. Impedance is purely resistive and current is maximum. Quality factor Q = (1/R)√(L/C).
- Three-phase power
- In a balanced three-phase system, total active power P = √3 × V_L × I_L × cos φ, where V_L is line voltage, I_L line current, and φ the phase angle between phase voltage and current.
- DC machine EMF equation
- Generated EMF in a DC machine is E = (p Φ N Z)/(60 A), where p is poles, Φ flux per pole, N speed in rpm, Z total armature conductors, and A number of parallel paths.
- Transformer EMF equation
- RMS induced EMF in a transformer winding is E = 4.44 f N Φ_max, where f is frequency, N turns, and Φ_max peak core flux. Voltage ratio equals turns ratio.
- Induction motor slip
- Slip s = (n_s − n_r)/n_s, where n_s is synchronous speed (120f/p) and n_r rotor speed. At standstill s = 1; at synchronous speed s = 0. Rotor frequency equals s × f.
- Synchronous machine power-angle
- For a cylindrical-rotor synchronous machine neglecting resistance, active power per phase P = (E_f V / X_s) sin δ, where E_f is excitation EMF, V terminal voltage, X_s synchronous reactance, δ load angle.
- Cable current-carrying capacity rule
- Protective device rated current I_n must satisfy I_b ≤ I_n ≤ I_z, where I_b is design current and I_z the cable capacity after applying correction factors for ambient temperature, grouping, and thermal insulation.
- TN earthing system
- A system where the installation's exposed conductive parts are connected to the earthed neutral of the supply. Subtypes: TN-S (separate PE and N), TN-C (combined PEN), TN-C-S (combined then separate).
- RCD 30 mA protection
- A residual current device with rated residual operating current 30 mA provides additional protection against electric shock for socket outlets up to 32 A and mobile equipment. It does not protect against overload.
- Voltage drop limit
- For low-voltage installations, voltage drop from the origin to the load should not exceed 3% for lighting and 5% for other uses, per IEC 60364. Higher drops may affect equipment performance.
- Buck converter voltage ratio
- A step-down DC-DC converter has output voltage V_out = D × V_in, where D is the duty cycle (0 ≤ D ≤ 1). It operates by switching and energy storage in an inductor.
- Thyristor phase control
- In a fully controlled full-wave rectifier with resistive load, average output voltage V_dc = (2V_m/π) cos α, where α is the firing angle. For α > 90°, output becomes negative (inverter mode).
- PWM inverter fundamental voltage
- With sinusoidal PWM, the fundamental phase voltage peak is V₁ = (V_dc/2) × m_a, where m_a is the modulation index (ratio of reference to carrier amplitude). Linear range m_a ≤ 1.
- V/f control
- Variable frequency drive control that keeps the ratio of stator voltage to frequency constant to maintain constant air-gap flux in an induction motor. At low speeds, voltage boost compensates stator resistance drop.
- Moving-coil instrument
- A permanent-magnet moving-coil (PMMC) meter deflects proportional to average current and measures DC only. The scale is linear. It is used in ammeters, voltmeters, and galvanometers.
- Two-wattmeter method
- For a balanced three-phase load, total power P = W₁ + W₂. Power factor can be derived from cos[tan⁻¹(√3 (W₁ − W₂)/(W₁ + W₂))]. Readings may be negative for low power factor.
- Current transformer safety
- A current transformer secondary must never be open-circuited while primary current flows, because dangerous high voltage would be induced. Short the secondary before removing the meter.
- Insulation resistance test
- Apply a DC test voltage (e.g., 500 V) for 1 minute and measure resistance. Minimum acceptable value for low-voltage installations is typically 1 MΩ. Polarization index (R10min/R1min) above 2 indicates good insulation.
- Earth fault loop impedance
- The impedance Z_s of the path from the point of fault through the protective conductor and earth back to the source. Disconnection is assured if Z_s ≤ U_0 / I_a, where I_a is the current causing disconnection in the required time.
- Protective earthing conductor sizing
- For copper, the protective conductor cross-section equals the phase conductor up to 16 mm²; 16 mm² for phase conductors 16–35 mm²; and half the phase conductor above 35 mm², per IEC 60364.
- Fuse gG characteristic
- A gG fuse provides general-purpose protection with inverse time-current characteristics: it carries overloads for a limited time and clears short circuits. It protects cables and lines against overload and short circuit.
- SELV system
- Safety extra-low voltage system with voltage not exceeding 50 V AC or 120 V ripple-free DC, electrically separated from earth and other circuits. It is used in wet locations and for portable tools.
- Load factor
- The ratio of average load to maximum demand over a period. A high load factor indicates efficient use of generation and distribution assets. It is used in power system planning and tariff design.
- Per-unit system
- A normalization method where quantities are expressed as fractions of base values. Z_base = V_base²/S_base. Per-unit transformer impedance = (Z% / 100) × (S_base / S_rated). It simplifies power system calculations.
- Surge impedance
- For a lossless transmission line, surge impedance Z_c = √(L/C), where L and C are inductance and capacitance per unit length. Overhead lines are about 400 Ω; cables about 50 Ω. Surge impedance loading SIL = V²/Z_c.
- Betz limit
- The maximum theoretical power coefficient C_p of a wind turbine is 16/27 ≈ 0.593. Power extracted is P = ½ ρ A v³ C_p, where ρ is air density, A rotor swept area, v wind speed.
- Single-line diagram
- A simplified drawing of a three-phase power system using one line to represent all phases. It shows generators, transformers, busbars, circuit breakers, and protection devices for analysis and documentation.
- IEC 60617 symbols
- International standard for graphical symbols used in electrotechnical diagrams. Examples: resistor as rectangle, capacitor as two parallel lines, diode as triangle with bar, earth as three horizontal lines.
- Reference designation
- Component identification per IEC 61346 using a letter code (e.g., Q for circuit breaker, F for fuse, K for relay, M for motor) followed by a number, used consistently in schematics and documentation.