  • Ohm's law: E = I × R; power in watts: P = E × I = I²R = E²/R. Single-phase power in watts equals volts times amps times power factor.

  • Voltage drop (single phase, copper or aluminum): VD = 2 × K × I × L ÷ CM, where K = 12.9 ohms-cmil/ft for copper and 21.2 for aluminum; L in feet, CM = circular mils of the conductor.

  • Three-phase formulas: VD = 1.732 × K × I × L ÷ CM; three-phase power P = 1.732 × E × I × power factor.

  • Ampacity adjustment: conductors in a raceway or cable are derated per Table 310.15(C)(1) - 4 to 6 current-carrying conductors = 80%, 7 to 9 = 70%, 10 to 20 = 50%.

  • Continuous loads are calculated at 125% of the load for branch-circuit and feeder sizing; the neutral need not be counted as a current-carrying conductor when it carries only unbalanced linear load.

  • Standard overcurrent device ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 A, then in 10 A steps to 400 A, then in 50 A steps to 1200 A.

  • Receptacle branch circuits: 15 A and 20 A, 125 V receptacles require 20 A circuits for small-appliance, laundry, and bathroom branch circuits; bathroom receptacles require GFCI protection.

  • Box fill uses Table 314.16(B) volume allowances: 14 AWG = 2.00 cu in, 12 AWG = 2.25 cu in, 10 AWG = 2.50 cu in; each device yoke counts two conductor volumes, all equipment grounds count as one.

Quick reference

Wiring Methods and Installation Practices

  • NM-B cable (Romex) is permitted in one- and two-family dwellings and multifamily dwellings not exceeding three floors, but is prohibited in hazardous locations, wet locations, and most commercial structures.

  • Support intervals: NM cable every 4.5 ft and within 12 in of every box; rigid metal conduit every 10 ft; EMT within 3 ft of a box and every 10 ft; PVC Schedule 40 every 3 ft.

  • Conduit fill: 1 conductor = 53%, 2 conductors = 31%, over 2 conductors = 40% of the conduit's internal cross-sectional area.

  • Bend radius for nonmetallic-sheathed cable must be at least 5 times the cable diameter; for MC cable it is 7 times the cable diameter.

  • Boxes must be accessible; junction boxes cannot be buried in walls or ceilings. A box must be large enough for the conductors, devices, and fittings per Article 314.

  • Conductors in a raceway must be de-rated for ambient temperature per Table 310.15(B)(1) and for the number of current-carrying conductors.

  • Recessed luminaires require minimum clearances from thermal insulation unless listed for direct contact (IC-rated); junction boxes must remain accessible.

  • Grounding electrode system: a single rod, pipe, or plate requires 25 ohms or less, or a second electrode must be added; the grounding electrode conductor is sized per Table 250.66.

Quick reference

Electrical Equipment and Devices

  • Receptacle configurations: 5-15R is 15 A/125 V; 5-20R is 20 A/125 V; 6-15R is 15 A/250 V; 6-20R is 20 A/250 V; 14-30R is 30 A/125/250 V; 14-50R is 50 A/125/250 V.

  • AFCI protection is required for 15 A and 20 A branch circuits supplying outlets in dwelling unit bedrooms, living rooms, dining rooms, kitchens, laundry, and similar areas; GFCI is required for bathrooms, garages, outdoors, and within 6 ft of sinks.

  • Tamper-resistant receptacles are required in dwelling units for 15 A and 20 A, 125 V receptacles, with limited exceptions such as dedicated equipment outlets.

  • Switch loops, three-way switches, and four-way switches: three-way switches have three terminals (common plus two travelers); four-way switches have four terminals and are placed between two three-way switches.

  • Panelboard: the service disconnect must be marked with its ampere rating and be capable of being locked open; a service disconnect must be provided at the point of entrance of the service conductors.

  • Ampacity of a receptacle is limited by the branch-circuit overcurrent device; a 15 A receptacle may be installed on a 20 A circuit only where the load is limited to 15 A.

  • Motors require overload protection sized per the motor nameplate full-load current and short-circuit/ground-fault protection per Article 430, Table 430.52.

Quick reference

Safety, Licensing Law, and Business Practices

  • NFPA 70E requires an arc-flash risk assessment before work on or near energized equipment; energized work is permitted only where de-energizing introduces additional hazards or is infeasible.

  • Approach boundaries: the limited approach boundary for a 480 V system is 3 ft 6 in; the restricted approach boundary is 1 ft; the arc-flash boundary depends on the calculated incident energy.

  • Lockout/tagout: a lockout device must be applied by the person performing the work, and the tag must identify the person and the reason for the lockout.

  • Personal protective equipment is selected by incident energy (cal/cm²); Category 1 = 4 cal/cm², Category 2 = 8 cal/cm², Category 3 = 25 cal/cm², Category 4 = 40 cal/cm².

  • Licensing: most states require electricians to be licensed, with separate journeyman and master classifications; a master electrician typically may pull permits and supervise journeymen.

  • Contract law: a written contract should identify scope, price, schedule, payment terms, and change-order procedures; a change order must be signed by both parties to be enforceable.

  • Bonding and insurance: a surety bond guarantees performance or payment; general liability insurance covers third-party bodily injury and property damage; workers' compensation covers employee injuries.