Ohm's Law
The relationship E = I × R, where E is voltage in volts, I is current in amperes, and R is resistance in ohms. Given any two values, the third can be calculated.
Power Formula
P = E × I for DC and purely resistive AC circuits. For AC circuits with reactance, true power equals volts times amps times power factor, measured in watts.
Voltage Drop Formula
VD = 2 × K × I × L ÷ CM for single-phase circuits, where K equals 12.9 for copper, I is current, L is one-way length in feet, and CM is circular mils.
Three-Phase Power
P = 1.732 × E × I × power factor. The 1.732 factor is the square root of three, which arises from the 120-degree phase displacement between the three phases.
Box Fill Allowance
Table 314.16(B) assigns volume per conductor: 14 AWG = 2.00 cu in, 12 AWG = 2.25 cu in, 10 AWG = 2.50 cu in. Each device yoke counts as two conductors.
Continuous Load Rule
A continuous load is one operating at maximum current for three hours or more. Its calculated load must be multiplied by 125% for branch-circuit and feeder sizing.
Conductor Derating
When more than three current-carrying conductors share a raceway, ampacity is reduced per Table 310.15(C)(1): 4 to 6 conductors to 80%, 7 to 9 to 70%.
Standard OCPD Ratings
Standard overcurrent device ratings include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, and 100 amperes, then increasing in 10 A steps to 400 A.
NM Cable Support
Nonmetallic-sheathed cable must be secured within 12 inches of every box and at intervals not exceeding 4.5 feet along its run.
EMT Support
Electrical metallic tubing must be supported within 3 feet of a box and at intervals not exceeding 10 feet, with additional support where bends or fittings require it.
Conduit Fill Limits
Conduit fill is limited by conductor count: one conductor may fill 53% of the cross-sectional area, two conductors 31%, and three or more 40%.
NM Cable Bend Radius
Nonmetallic-sheathed cable must be bent to a radius of at least five times the cable diameter, preventing damage to the conductors and sheath.
Grounding Electrode Rule
A single rod, pipe, or plate electrode must have a resistance of 25 ohms or less. If it exceeds 25 ohms, a second electrode must be added.
Box Accessibility
Junction and outlet boxes must remain accessible without removing permanent building finishes. Boxes may not be buried in walls, ceilings, or floors.
Receptacle Configurations
NEMA 5-15R is 15 A/125 V, 5-20R is 20 A/125 V, 6-15R is 15 A/250 V, 14-30R is 30 A/125/250 V, and 14-50R is 50 A/125/250 V.
GFCI Protection Locations
GFCI protection is required for 15 A and 20 A receptacles in bathrooms, garages, outdoors, near sinks within 6 feet, and in unfinished basements.
AFCI Protection
Arc-fault circuit-interrupter protection is required for 15 A and 20 A branch circuits supplying outlets in dwelling unit bedrooms, living rooms, dining rooms, and similar areas.
Tamper-Resistant Receptacles
Tamper-resistant receptacles are required in dwelling units for 15 A and 20 A, 125 V receptacles, with limited exceptions such as dedicated equipment outlets.
Three-Way Switch
A three-way switch has three terminals: one common and two travelers. Two three-way switches control a single load from two different locations.
Service Disconnect
A service disconnect must be provided at the point where service conductors enter the building and must be marked with its ampere rating and be lockable open.
Motor Overload Protection
Motor overload protection is sized from the motor nameplate full-load current. Short-circuit and ground-fault protection follow Article 430, Table 430.52.
Arc-Flash Risk Assessment
NFPA 70E requires an arc-flash risk assessment before energized work. Energized work is allowed only where de-energizing adds hazards or is infeasible.
Limited Approach Boundary
For a 480 V system, the limited approach boundary is 3 feet 6 inches and the restricted approach boundary is 1 foot. Only qualified persons may cross.
Lockout/Tagout
The person performing the work applies the lockout device. The tag must identify that person and the reason for the lockout, and only that person removes it.
PPE Categories
Arc-rated PPE categories by incident energy: Category 1 = 4 cal/cm², Category 2 = 8 cal/cm², Category 3 = 25 cal/cm², Category 4 = 40 cal/cm².
Master Electrician License
A master electrician license typically authorizes the holder to pull permits, contract for electrical work, and supervise journeyman electricians.
Change Order
A change order modifies the scope, price, or schedule of a contract. It must be signed by both parties to be enforceable.
Surety Bond
A surety bond is a three-party agreement guaranteeing that the contractor will perform the work or pay damages if the contractor defaults.
Workers' Compensation
Workers' compensation insurance covers employee injuries and illnesses arising from employment, regardless of fault, and is required in most states.
Circuit Breaker Marking
A circuit breaker must be marked with its ampere rating, voltage rating, and interrupting rating. The interrupting rating must equal or exceed available fault current.
Recessed Luminaire Clearance
Recessed luminaires require clearance from thermal insulation unless listed for direct contact. Their junction boxes must remain accessible for service.