Sensible heat ratio
Ratio of sensible cooling to total cooling. In a data hall it is typically 0.90-1.00 because IT equipment releases almost no latent heat.
ASHRAE A1 envelope
Recommended IT inlet range of 18-27 C dry-bulb and 5.5-15 C dew point. Operation outside it raises failure rates and can void warranties.
Dew point control
Keeping supply air dew point below the coldest surface in the hall. It prevents condensation and avoids simultaneous humidification and dehumidification.
Air density correction
Cooling capacity depends on mass flow, not volumetric flow. At 2,000 m altitude, density is about 1.0 kg/m3 versus 1.2 at sea level, cutting capacity roughly 17%.
Sensible cooling formula
Q_s = 1.08 x CFM x delta-T in Btu/h, or Q_s = 1.21 x L/s x delta-T in watts. It gives coil sensible capacity from airflow and temperature difference.
Latent load sources
In a tight hall, latent load comes mainly from infiltration through doors, people, and open humidifiers. Most halls need humidification only in dry climates.
CRAC versus CRAH
CRAC is a self-contained DX unit with a compressor inside the hall. CRAH is a chilled-water coil unit fed by a central plant and has no compressor.
Redundancy nomenclature
N is minimum capacity, N+1 adds one unit, 2N duplicates the full path, and 2(N+1) duplicates plus one spare. Concurrent maintainability allows servicing without dropping load.
Fan affinity laws
Flow scales with speed, head with speed squared, and power with speed cubed. A 50% speed cut leaves about 12.5% of design power.
Water-side economizer
A plate heat exchanger between cooling-tower water and the chilled-water loop. It provides free cooling when outdoor wet-bulb is low enough.
Cooling tower approach
Leaving condenser water temperature minus entering wet-bulb temperature. A good design approach is 3-5 K; a larger approach raises chiller kW per ton.
Three-way versus two-way valves
Three-way valves keep constant plant flow but waste pump energy. Two-way valves with variable flow save pump energy but need minimum-flow control.
Air-cooled versus water-cooled
Air-cooled chillers avoid water and towers but have lower efficiency and depend on ambient dry-bulb. Water-cooled chillers need make-up water and treatment.
Hot-aisle and cold-aisle layout
Racks face front-to-front in cold aisles and back-to-back in hot aisles. Servers draw from the cold aisle and exhaust into the hot aisle.
Bypass and recirculation
Bypass is cold supply air that never reaches IT intake. Recirculation is hot exhaust that reaches IT intake. Both raise intake temperature or waste cooling.
Rack Cooling Index
RCI measures how well rack intakes stay within the temperature envelope. A value of 100% means every rack is within limits.
Cold-aisle containment
Enclosing the cold aisle with roof panels and end doors. It stops hot-air recirculation and allows higher supply temperatures and more economizer hours.
Hot-aisle containment
Enclosing the hot aisle and returning exhaust air directly to the CRAC or CRAH. It captures hot air at the source and reduces mixing.
Blank panels and brush strips
Lowest-cost containment measures. An open 1U slot can leak a large fraction of a rack's cold air, so unused spaces must be sealed.
Raised-floor plenum velocity
Plenum velocity should stay under about 2.5 m/s to limit friction loss and turbulence. Cable trays under the floor block flow and should be minimized.
Ton refrigeration conversion
One ton of refrigeration equals 3.517 kW and 12,000 Btu/h. A 1 kW IT load needs roughly 0.28 tons of cooling plus overheads.
Power Usage Effectiveness
PUE is total facility energy divided by IT equipment energy. Annualized PUE covers 12 months and includes cooling, losses, and lighting.
Partial PUE
pPUE scopes a boundary such as one hall or module. It is useful when plant is shared across tenants and full-facility PUE hides local performance.
DCiE
DCiE is the reciprocal of PUE expressed as a percentage. A PUE of 1.5 equals 66.7% DCiE.
Water Usage Effectiveness
WUE equals liters of water divided by IT kWh. Evaporative cooling can push WUE to 2-5 L/kWh, so it must be read alongside PUE.
Carbon Usage Effectiveness
CUE equals carbon emissions divided by IT kWh. It depends on grid carbon intensity and on-site fuel use.
Part-load chiller efficiency
Chillers are most efficient at 40-70% load. Oversizing moves operation away from this band, so IPLV/NPLV is a better comparison than full-load COP.
Supply air temperature reset
Raising supply air temperature while all rack intakes remain inside the envelope. Each 1 K rise can meaningfully extend economizer hours.
Economizer high-limit lockout
A switch or enthalpy comparison that stops outside-air free cooling above a set condition. A failed damper actuator is a common cause of frozen coils.
Filter differential pressure trending
Monitoring pressure rise across filters to detect loading. Filters should be changed on pressure rise, and fan curves verified after each change.
Low delta-T syndrome
Chilled-water delta-T falls below design while flow rises. Causes include fouled coils, three-way valves, and control valve bypass; plant kW/ton worsens.
Condenser water reset
Lowering tower water temperature where the chiller allows, often to 20-24 C, to cut compressor lift and kW/ton, subject to minimum condenser temperature limits.