32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Concurrently maintainable
A design property where any planned maintenance activity on one infrastructure path can be performed without affecting the IT load, typically achieved with physically separate redundant paths.
Fault tolerant
A design property where any single unplanned failure in the infrastructure does not interrupt the IT load, requiring redundant and independent paths at every level.
Uptime Tier III
Certification level requiring concurrently maintainable infrastructure with no shutdown for planned maintenance; distinct from TIA-942 Rated-3 and assessed by Uptime Institute.
PUE
Power usage effectiveness equals total facility power divided by IT equipment power; a value of 1.0 is theoretical best and overhead comes from cooling and electrical losses.
Double-conversion UPS
An online UPS that converts AC to DC and back to AC, isolating the load from all utility disturbances including sags, surges, and frequency variation.
Static transfer switch
A solid-state device that transfers a load between two power sources in a few milliseconds, faster than a mechanical automatic transfer switch.
Generator walk-in
The gradual ramp of UPS rectifier load after a generator picks up, which must be matched to generator step-loading capability to avoid stalling.
Affinity laws
For pumps and fans, flow varies linearly with speed, pressure with the square, and power with the cube of speed.
Low delta-T syndrome
A condition where chilled water return temperature is lower than design, reducing plant capacity, often caused by coil fouling or three-way valve misuse.
Water-side economizer
A cooling mode using a cooling tower or fluid cooler to produce chilled water without running the chiller when outdoor wet-bulb temperature is low enough.
ASHRAE recommended envelope
The inlet air temperature and humidity range for efficient, reliable IT operation, roughly 18-27 °C and 8-60% relative humidity for Class A1.
Hot-aisle containment
An enclosure over the hot aisle that captures exhaust air and returns it to air handlers, preventing mixing with cold-aisle supply air.
CRAH unit
A chilled-water air handling unit with no compressor; it uses chilled water from a central plant and a fan to cool IT equipment.
Rack Cooling Index
A metric quantifying how well rack inlet temperatures stay within ASHRAE recommended or allowable limits; higher values indicate better airflow management.
MDA
Main distribution area in structured cabling, the space housing the core switches and main cross-connect for the data center.
OM4 multimode fiber
Laser-optimized multimode fiber supporting 10GBASE-SR to about 400 m and 40/100GBASE-SR to shorter distances in data center backbones.
Spine-leaf architecture
A two-layer network topology where every leaf switch connects to every spine switch, providing predictable low-latency east-west traffic.
Pre-action sprinkler
A water-based suppression system that requires two events, detection and a sprinkler head activation, before water enters the piping, reducing accidental discharge risk.
Cross-zoning
A suppression release logic requiring two independent detectors to alarm before agent discharges, reducing false discharge risk in a data hall.
Room integrity test
A door fan test that measures enclosure leakage to verify the space can hold the suppression agent concentration for the required hold time.
Anti-passback
An access control rule preventing a credential from being used to enter twice without an intervening exit, reducing card sharing and tailgating.
Mantrap
An interlocking two-door entry where only one door can open at a time, preventing piggybacking into a secure data hall.
Multi-factor authentication
Access control requiring two or more independent credential types, such as a card plus a PIN or biometric, to verify identity.
Integrated systems test
A commissioning test proving that electrical, mechanical, and controls systems operate together under load, including generator and UPS transitions.
Method of procedure
A document describing step-by-step work on critical infrastructure, including prerequisites, rollback steps, and approvals before execution.
Infrared thermography
A predictive maintenance technique using thermal imaging to detect loose electrical connections and overheating before failure.
Recovery time objective
The maximum acceptable time to restore a critical process after disruption, derived from a business impact analysis.
Recovery point objective
The maximum acceptable data loss measured in time, determining whether synchronous or asynchronous replication is required between sites.
Availability in nines
Uptime expressed as a percentage: 99.9% allows about 8.77 hours downtime per year, 99.99% about 52.6 minutes.
Hot site
A recovery facility with live replicated infrastructure and data, enabling rapid failover with minimal downtime and near-zero data loss.
Business impact analysis
A process identifying critical business processes and their dependencies, used to set recovery time and recovery point objectives.
ISO/IEC 27001
An international standard for information security management systems, requiring risk assessment, controls, and continuous improvement.