Mistake 1

When computing a short-circuit current, the candidate adds the source, transformer, and cable impedances arithmetically instead of combining them in complex form (R + jX), then reports a current that is noticeably too high.

The habit comes from simple series-resistance exercises where scalar addition works. In power systems the X/R ratio of transformers and cables is large, so scalar addition inflates the total impedance and distorts the current, and candidates rarely convert percent or per-unit impedance to ohms before combining.

What to do instead

Before any fault calculation, convert everything to a common base (per-unit or actual ohms at one voltage level) and keep R and X separate. Sum resistances and reactances independently, compute |Z| = sqrt(R^2 + X^2), and only then divide voltage by impedance. Do a sanity check on the X/R ratio for the equipment type (distribution transformers are typically in the 4-10 range) and confirm the resulting current is within the expected order of magnitude for the transformer kVA.

Mistake 2

The candidate sizes a cable by ampacity alone and ignores voltage drop, or applies the voltage-drop formula without distinguishing single-phase (2-wire) from three-phase circuits, producing a drop that is wrong by roughly a factor of two.

Ampacity tables are easy to look up and feel like the complete answer, while voltage drop is treated as a secondary check. Candidates also forget that a single-phase circuit carries current out and back, so the loop length is twice the run length, and they mix up line-to-line and line-to-neutral voltage in the formula.

What to do instead

Always run both checks and take the larger cable size. For three-phase use dV = sqrt(3) x I x L x (R cos phi + X sin phi); for single-phase use dV = 2 x I x L x (R cos phi + X sin phi). State the permissible drop explicitly (commonly 3 percent for lighting final circuits and 5 percent overall from origin to load) and show the calculation, because partial credit usually depends on the method being visible.

Mistake 3

When checking discrimination, the candidate compares only the pickup (long-time) settings of upstream and downstream breakers and declares selectivity, without checking the instantaneous region, the time-current curves at the actual prospective fault current, or the breaker manufacturer's selectivity tables.

Pickup current is the most visible number on a settings sheet, so it becomes the whole comparison. Candidates do not realise that instantaneous trips often overlap, that current-limiting breakers need manufacturer-tested selectivity limits, and that the fault current at the downstream board, not the transformer terminals, is the value that matters.

What to do instead

Plot or tabulate both curves at the actual fault current at each busbar. Check three regions separately: overload (long-time), short-time/instantaneous, and the high-current region where manufacturer selectivity tables apply. Verify the upstream instantaneous pickup is above the maximum prospective fault current at the downstream busbar, or that a short-time delay with intentional time margin (typically 0.2-0.3 s) is set. State the assumed fault current and the time margin in your answer.

Mistake 4

The candidate computes the number of luminaires from the lumen method but then reports the maintained illuminance without applying the maintenance factor, or applies the utilisation factor and maintenance factor in the wrong direction.

The formula N = (E x A) / (F x UF x MF) is memorised as a string of symbols without understanding that UF and MF both reduce the delivered lumens, so dividing by them increases the fixture count. Candidates also use the initial lamp lumens when the question gives maintained lumens, double-counting the depreciation.

What to do instead

Write the formula with units attached and label each term before substituting: E in lux, A in m2, F in lumens per luminaire, UF dimensionless (from the room index and reflectance table), MF dimensionless (typically 0.7-0.8 for a normal office). Confirm whether the lamp data is initial or maintained output and use one or the other, not both. Then perform the inverse check: recompute E from your N to see that it lands on the target.

Mistake 5

The candidate answers code questions from memory of a foreign code (IEC or NEC) and states a clearance, zone, or earthing value that conflicts with the Egyptian requirements, or cites a clause number that does not exist.

Most study material available online is IEC- or NEC-based, and the Egyptian code adopts IEC heavily but with national amendments, so the two feel interchangeable. Under time pressure candidates invent a plausible clause reference rather than admit uncertainty.

What to do instead

Learn the structure of the Egyptian code and its relationship to IEC 60364 so you know which parts are national amendments. When a question turns on a specific numeric value, state the value you are confident of and name the governing standard family (for example IEC 60364 or the Egyptian code) rather than fabricating a clause number. In practice questions, show the design principle and the check performed, since markers reward correct method even where the exact table value is uncertain.

Mistake 6

The candidate designs or checks a earthing system using only the electrode resistance and never verifies touch and step voltage, or treats the earth-fault loop impedance check and the earth electrode resistance as the same quantity.

Earth resistance is the number everyone measures and quotes, so it becomes the only criterion. Candidates conflate the resistance to earth of an electrode (relevant to lightning and MV earthing) with the fault loop impedance that determines disconnection time in a TN system, and they forget that a low electrode resistance does not by itself guarantee safe touch voltage during a fault.

What to do instead

Separate the two concepts explicitly. For TN systems, verify the fault loop impedance Zs against the disconnection time using the protective device curve. For TT and MV installations, compute the prospective touch voltage as the fault current times the electrode resistance and confirm it is below the permissible touch voltage for the clearing time. For substations, check step and touch potential with the surface layer resistivity included, not just the grid resistance.

Mistake 7

The candidate confuses the roles of the engineer, the contractor, and the employer in a contract question, and answers a claim or variation scenario by describing what is technically fair rather than what the contract entitles the parties to.

Engineers are trained to solve the technical problem, so the instinct is to propose the sensible outcome. Contract questions test the allocation of risk and the procedural steps (notice periods, instruction in writing, valuation basis), and candidates skip these because they seem like paperwork.

What to do instead

For every contract scenario, identify three things before answering: which party bears the risk under the contract, what procedural step was required and whether it was taken in time, and what the engineer's authority is (certify, instruct, determine, or merely recommend). Answer in that order. If a notice period or a written instruction is missing, say so, because that usually determines the outcome regardless of the technical merits.

Mistake 8

The candidate sizes a photovoltaic or wind system from the load energy alone and omits the system losses, derating, and the difference between peak sun hours and installed capacity, then reports a payback period without discounting or without accounting for tariff structure.

The basic energy balance (daily kWh divided by irradiance) looks complete and gives a neat number. Candidates forget inverter efficiency, temperature derating, soiling, cable losses, and battery round-trip efficiency, and they compute simple payback while the question asks for a lifecycle or discounted measure.

What to do instead

Build the calculation as a chain with each loss factor written down: array DC energy, then derate for temperature, soiling, mismatch, and cable loss, then apply inverter efficiency, then battery round-trip efficiency if storage is present. For economics, state which metric is requested (simple payback, discounted payback, NPV, IRR) and use the corresponding formula, including the tariff and any feed-in rate separately for self-consumed and exported energy.

Mistake 9

The candidate describes a test procedure without stating the instrument, the safety precautions, and the acceptance criterion, or confuses an insulation resistance test with a continuity or a polarity test.

Commissioning questions are answered from general familiarity with multimeters and meggers, and the candidate jumps to the expected reading. The purpose of each test (verifying insulation integrity versus verifying conductor continuity and correct connection) is not distinguished, and the prerequisite of isolating and proving dead is treated as obvious and omitted.

What to do instead

For every testing question, structure the answer as: purpose, instrument and its voltage/range, prerequisite safety steps (isolate, lock off, prove dead, discharge, isolate electronics), test connections, acceptance criterion with the standard reference, and interpretation of a failing result. Learn the insulation resistance test voltages by circuit nominal voltage and the minimum acceptable values, and keep continuity, polarity, and insulation tests clearly separate in your notes.

Mistake 10

The candidate selects switchgear and protective devices by nominal current only, ignoring the short-circuit withstand, the making capacity, the IP rating, the form of separation, and the ambient temperature derating of the enclosure.

Nominal current is the headline rating on a datasheet, and the other ratings appear as a block of numbers that candidates skim. The consequence is a board that carries the load but cannot withstand the fault level, or a device derated by a hot enclosure that was never accounted for.

What to do instead

For any switchgear selection, run a checklist in a fixed order: system voltage, nominal and design current, prospective short-circuit current versus rated short-circuit withstand and making capacity, protective device rating and breaking capacity, ambient and enclosure derating factors, IP and form of separation for the location, and coordination with upstream and downstream devices. Write the checklist out in the answer so the marker can see each item was considered.