Low-pressure appliance definition
An appliance using a refrigerant with a boiling point at atmospheric pressure at or above 0 degrees Celsius at 14.7 psia, such as CFC-11, CFC-113, HCFC-123, or HCFC-124.
Required evacuation level
Low-pressure appliances must be evacuated to 25 mm Hg absolute, roughly 0.5 inches of mercury vacuum, before opening or disposal.
Recovery unit for low pressure
Low-pressure recovery requires a compressor-driven unit with a condenser or subcooler to condense low-pressure vapor, since the refrigerant's low vapor pressure prevents simple pumping.
Recycling versus reclamation
Recycling cleans refrigerant on site for reuse by the same owner; reclamation restores refrigerant to ARI 700 purity and is required for sale or transfer to a different owner.
Cylinder fill limit
Recovery cylinders must not be filled beyond 80 percent of their capacity by weight, verified with a scale, to allow for liquid expansion.
Never mix refrigerants
Mixing different refrigerants in a recovery cylinder prevents recycling or reclamation and may make the entire cylinder a hazardous waste.
Charging a low-pressure chiller
Charge refrigerant as a liquid or vapor per the manufacturer's instructions, verifying the charge by weight and by subcooling, superheat, or liquid level.
Purge unit function
A purge unit removes non-condensable gases such as air and moisture from the condenser; excessive purging indicates a leak or purge unit problem.
Non-condensables in low-pressure systems
Because the evaporator operates under vacuum, air and moisture can enter through leaks; non-condensables raise condenser pressure and reduce efficiency.
Moisture and acid formation
Moisture combined with chlorine or fluorine refrigerants forms hydrochloric and hydrofluoric acids, causing corrosion and oil breakdown; keep moisture below the manufacturer's limit.
Leak detection for HCFC-123
HCFC-123 is detected with an electronic leak detector sensitive to HCFC-123 or a colorimetric indicator tube; a halide torch is not suitable for all refrigerants.
Opening a low-pressure system
Recover refrigerant to the required vacuum, isolate the machine, remove residual refrigerant, then break the vacuum with dry nitrogen before service.
Leak rate formula
Leak rate equals pounds of refrigerant added over the past 12 months divided by the total charge, expressed as a percentage.
Repair trigger thresholds
Repair is required when the leak rate exceeds 15 percent for commercial refrigeration or 35 percent for comfort cooling appliances with 50 or more pounds of charge.
Repair deadline
A leak exceeding the threshold must be repaired within 30 days of discovery, with a possible 30-day extension if parts are unavailable or the appliance is temporarily shut down.
Verification of repair
Initial verification must occur within 30 days after repair, with follow-up verification within 30 days after the initial verification if the leak rate remains above the threshold.
Retrofit or retirement plan
If an appliance cannot be repaired, the owner must develop a retrofit or retirement plan within 30 days and keep it on site for EPA review.
Recordkeeping period
Service records, leak rate calculations, and retrofit or retirement plans must be kept for at least 3 years and made available to EPA upon request.
Recurring leak rule
If the same leak recurs within 12 months after verification, the appliance is again subject to leak repair requirements and may require retrofit or retirement.
Evacuation before disposal
Before dismantling or disposing of a low-pressure appliance, recover refrigerant to 25 mm Hg absolute and verify the level with a vacuum gauge.
Vacuum verification
Final evacuation must be verified with a micron gauge or manometer capable of reading the required vacuum range; a compound gauge alone is insufficient.
Recovered refrigerant handling
Refrigerant recovered during disposal must be recycled, reclaimed, or destroyed; it may not be vented to the atmosphere.
Disposal documentation
The technician must provide documentation of refrigerant recovery, including the amount recovered and the evacuation level achieved, to the owner or disposal facility.
Recovery equipment capability
Recovery equipment used for disposal must be able to reach 25 mm Hg absolute; a unit that cannot achieve this level is not acceptable for low-pressure appliances.
Sealing after evacuation
After evacuation, seal the service ports or tag the appliance as evacuated; open the system to atmosphere only after evacuation is complete.
Section 608 venting prohibition
Section 608 of the Clean Air Act prohibits venting ozone-depleting refrigerants and their substitutes, codified at 40 CFR Part 82, Subpart F.
Type III certification
Type III certification covers low-pressure appliances; technicians must pass a proctored exam covering recovery, recycling, reclamation, leak detection, and disposal.
Universal certification
Universal certification covers all appliance types, including low-pressure appliances, and is obtained by passing the Type I, Type II, and Type III exams.
Refrigerant sales restriction
Ozone-depleting refrigerants may be sold only to certified technicians, and the seller must verify the buyer's certification before the sale.
Reclaimer certification
Reclaimed refrigerant must be processed by an EPA-certified reclaimer and meet ARI Standard 700 purity, with the reclaimer's name and purity level on the label.
Recordkeeping requirement
Owners of appliances with 50 or more pounds of refrigerant must keep service records, leak rate calculations, and retrofit plans for at least 3 years.
Small appliance threshold
Small appliances contain less than 5 pounds of refrigerant and have separate recovery requirements; low-pressure chillers generally exceed this threshold and face full requirements.