EPA 608 Type III key terms
EPA 608 Type III · Get comfortable with the vocabulary.
- Low-pressure appliance
- Related: Low-pressure refrigerant, Purge unit
Under EPA rules, refrigeration or air-conditioning equipment that operates at a suction pressure below atmospheric pressure, typically using refrigerants such as R-11, R-123, or R-113.
- Low-pressure refrigerant
- Related: Low-pressure appliance, Air infiltration
A refrigerant whose boiling point at atmospheric pressure is high enough that the system runs in a vacuum, so air and moisture tend to leak inward rather than refrigerant leaking outward.
- ASME vessel
- Related: Recovery cylinder, DOT cylinder
A storage tank or receiver built to the American Society of Mechanical Engineers pressure-vessel code, required for holding recovered refrigerant at rated pressure and temperature.
- Recovery cylinder
- Related: ASME vessel, DOT cylinder, Cylinder filling limit
A refillable container used to hold refrigerant removed from equipment; it must be DOT-approved or ASME-rated, properly marked, and never filled beyond its rated capacity.
- DOT cylinder
- Related: Recovery cylinder, Cylinder filling limit
A refillable pressure container manufactured and marked to U.S. Department of Transportation specifications, used for transporting recovered refrigerant and subject to periodic requalification.
- Cylinder filling limit
- Related: Recovery cylinder, Liquid expansion
The maximum weight of refrigerant allowed in a recovery container, commonly 80 percent of the cylinder's water capacity for low-pressure refrigerants, to leave room for liquid expansion.
- Liquid expansion
- Related: Cylinder filling limit, Hydrostatic pressure
The increase in refrigerant volume as it warms; in a sealed cylinder this raises pressure, so containers must be filled to leave a vapor space and never overfilled.
- Recovery
- Related: Recycling, Reclamation, Recovery machine
The act of removing refrigerant from an appliance and storing it in an external container, without necessarily cleaning it, so it can be reused, recycled, or reclaimed later.
- Recycling
- Related: Recovery, Reclamation, Filter-drier
Cleaning recovered refrigerant for reuse by removing oil, moisture, and particulates, typically by filtering and separating in the field; it does not restore the refrigerant to a specified purity standard.
- Reclamation
- Related: Recycling, AHRI 700, Certified refrigerant reclaimer
Reprocessing refrigerant to meet a published purity specification, such as AHRI Standard 700, using laboratory-verified analysis; it must be done by an EPA-certified reclaimer.
- AHRI 700
- Related: Reclamation, Noncondensable gas
The industry standard that specifies purity limits for reclaimed refrigerants, including allowable moisture, acidity, and noncondensable gas content, used to certify reclaimed product.
- Certified refrigerant reclaimer
- Related: Reclamation, AHRI 700
A company or facility certified by EPA to reprocess used refrigerant to AHRI 700 purity and to accept refrigerant for reclamation, as listed in EPA's reclaimer registry.
- Recovery machine
- Related: Recovery, Vapor recovery, Liquid recovery
A mechanical system, often a compressor-driven unit, that pulls refrigerant vapor from an appliance and condenses it into a recovery container for storage.
- Vapor recovery
- Related: Liquid recovery, Recovery machine
Removing refrigerant from an appliance as a gas, which is slower than liquid recovery but leaves the system at a lower final pressure and is used for the final portion of evacuation.
- Liquid recovery
- Related: Vapor recovery, Recovery machine
Removing refrigerant from an appliance as a liquid, which is much faster than vapor recovery and is used first when the system contains a large liquid charge.
- Noncondensable gas
- Related: Air infiltration, Purge unit, AHRI 700
Air or another gas that does not condense at normal system temperatures; in low-pressure systems it collects in the condenser and raises head pressure, reducing efficiency.
- Air infiltration
- Related: Noncondensable gas, Purge unit, Moisture contamination
The inward leakage of air and moisture into a low-pressure system because it operates below atmospheric pressure, a common cause of noncondensables and acid formation.
- Purge unit
- Related: Noncondensable gas, Air infiltration
A device that removes noncondensable gases from a low-pressure system's condenser; older units vented refrigerant, while modern units recover refrigerant before exhausting air.
- Moisture contamination
- Related: Air infiltration, Filter-drier, Acid test
Water that enters a system, often with infiltrating air, causing corrosion, ice formation at orifices, and acid formation when combined with refrigerant and oil.
- Filter-drier
- Related: Moisture contamination, Recycling, Acid test
A replaceable device containing desiccant that removes moisture and captures particulates and acids from refrigerant circulating in a system.
- Acid test
- Related: Moisture contamination, Filter-drier
A field or laboratory check of refrigerant or oil for acidity, used to decide whether a charge can be recycled or must be reclaimed and whether system cleanup is needed.
- Dehydration
- Related: Deep vacuum, Micron gauge, Moisture contamination
The process of removing moisture from a system, usually by deep evacuation with a vacuum pump and by replacing filter-driers, before recharging refrigerant.
- Deep vacuum
- Related: Micron gauge, Dehydration, Triple evacuation
Evacuation of a system to a very low absolute pressure, measured in microns, to boil off moisture and verify that the system is tight and dry.
- Micron gauge
- Related: Deep vacuum, Standing vacuum test
An electronic instrument that measures absolute pressure in microns, used to confirm that evacuation has reached the required vacuum level and that the system holds it.
- Standing vacuum test
- Related: Deep vacuum, Micron gauge, Leak detection
A test in which the system is isolated under deep vacuum and observed; a rapid pressure rise indicates a leak, while a slow rise suggests remaining moisture.
- Triple evacuation
- Related: Deep vacuum, Dehydration, Dry nitrogen
A procedure that evacuates the system, breaks the vacuum with dry nitrogen, and repeats, helping to sweep moisture and noncondensables out of the system.
- Dry nitrogen
- Related: Triple evacuation, Pressure test
Nitrogen gas free of moisture, used to pressurize systems for leak testing and to break a vacuum during evacuation without introducing water or oxygen.
- Pressure test
- Related: Dry nitrogen, Leak detection, Standing vacuum test
A leak check in which dry nitrogen or another inert gas raises system pressure while the outside of joints and components is checked for escaping gas.
- Leak detection
- Related: Standing vacuum test, Pressure test, Leak repair
The process of finding refrigerant or vacuum leaks using methods such as electronic detectors, soap bubbles, ultrasonic tools, or pressure and vacuum decay tests.
- Leak repair
- Related: Leak detection, Leak rate calculation
Correcting a refrigerant leak, such as by tightening, brazing, or replacing a component, and then verifying the repair with a follow-up leak check before recharging.
- Leak rate calculation
- Related: Leak repair, Chronic leak
Computing the percentage of a full charge lost per year, used to determine whether an appliance exceeds the regulatory leak-rate threshold and triggers repair obligations.
- Chronic leak
- Related: Leak rate calculation, Leak repair
A leak that persists after repair attempts or that causes an appliance to exceed the applicable leak-rate threshold repeatedly, potentially requiring retrofit or retirement.
- Section 608
- Related: 40 CFR Part 82 Subpart F, Technician certification
The Clean Air Act provision that governs refrigerant handling, requiring technician certification, safe disposal, leak repair, and recordkeeping for ozone-depleting refrigerants.
- 40 CFR Part 82 Subpart F
- Related: Section 608, Technician certification
The EPA regulation implementing Section 608, setting the rules for refrigerant recovery, recycling, reclamation, leak repair, recordkeeping, and technician certification.
- Technician certification
- Related: Section 608, 40 CFR Part 82 Subpart F
The credential required by EPA for people who service, maintain, repair, or dispose of appliances containing regulated refrigerants; Type III covers low-pressure appliances.
- Safe disposal
- Related: Recovery, Recordkeeping
The requirement that refrigerant be recovered from appliances before they are scrapped or dismantled, and that the recovery be documented to show compliance.
- Recordkeeping
- Related: Safe disposal, Leak repair
Maintaining required documents such as service records, refrigerant purchase and disposal records, leak repair records, and disposal certifications for the required retention period.
- Hydrostatic pressure
- Related: Liquid expansion, Cylinder filling limit
Pressure exerted by liquid refrigerant trapped in a closed section of piping or a cylinder as it warms, which can rupture components and cause serious injury.
- Recovery efficiency
- Related: Recovery, Vapor recovery
The percentage of the original refrigerant charge that a recovery process removes, with EPA rules setting minimum evacuation levels for low-pressure appliances.