Type I - Small Appliances

  • Type I appliance: hermetically sealed, factory-charged, containing 5 lb (2.3 kg) or less of refrigerant - household refrigerators, freezers, room air conditioners, dehumidifiers, vending machines, drinking water coolers.

  • Motor vehicle air conditioners are not Type I appliances; they fall under Section 609 rules and separate certification.

  • Disposal recovery target for a small appliance: 80% of the charge if the compressor is not operating, 90% if the compressor is operating.

  • No specific vacuum level is mandated for Type I recovery, but the recovery equipment itself still must be EPA-certified.

  • System-dependent (passive) recovery equipment is permitted on Type I appliances and may rely on the appliance compressor, internal system pressure, or a vacuum pump attached to the system.

  • Recovered small-appliance refrigerant must be recycled, reclaimed to AHRI 700 purity, or destroyed; deliberate venting to the atmosphere is prohibited.

  • Small sealed systems commonly use a capillary tube (fixed restriction) and have no service valves; access is gained through a piercing valve or process stub that must be sealed afterward.

  • Recovery cylinders must be DOT-approved, labeled for the refrigerant they contain, and filled to no more than 80% of capacity by weight.

Quick reference

Type II - High-Pressure Appliances

  • Type II appliance: uses a refrigerant with a boiling point below 32°F at atmospheric pressure - R-22, R-134a, R-410A, R-404A, R-407C, R-502.

  • Evacuation level for appliances under 200 lb of charge: 10 in Hg vacuum with recovery equipment built after November 15, 1993; 4 in Hg for CFC/HCFC or 0 psig for HFC-134a/PFC with older equipment.

  • Appliances containing 200 lb or more of refrigerant must be evacuated to 15 in Hg vacuum before opening.

  • Very-high-pressure refrigerants (R-13, R-23, R-503): evacuate to 0 psig with pre-1993 recovery equipment and to 10 in Hg vacuum with post-1993 equipment.

  • Leak repair rule for appliances of 50 lb or more: repair within 30 days when the annual leak rate exceeds 15% (comfort cooling) or 35% (commercial refrigeration or industrial process).

  • An initial verification test is required within 30 days of completing a leak repair on a 50 lb or larger appliance, followed by a follow-up verification test 30 days later.

  • R-410A is a near-azeotropic 50/50 blend of R-32 and R-125: charge it as a liquid, expect roughly 60% higher pressures than R-22, and use POE oil.

  • Never pressure-test with oxygen or compressed air; use dry nitrogen with a regulator. Recovery cylinders must not exceed 80% fill by weight.

  • Records of refrigerant purchased, recovered, recycled, and disposed of must be retained for at least three years.

Quick reference

Type III - Low-Pressure Appliances

  • Type III appliance: uses a refrigerant whose boiling point is at or above 32°F at atmospheric pressure - R-11, R-113, R-123 - typically centrifugal chillers.

  • Low-pressure appliances must be evacuated to 25 mm of mercury absolute (about 29.6 in Hg vacuum) before being opened or disposed of.

  • Never use the appliance's own compressor to evacuate or recover refrigerant; a certified recovery unit is required.

  • Because the machine operates below atmospheric pressure, air and moisture leak inward; a high-efficiency purge unit removes noncondensables.

  • Never pressurize a low-pressure chiller with air; use dry nitrogen through a regulator. The shell carries a rupture disc that typically bursts near 15 psig.

  • R-11 (CFC, ODP 1.0) boils at about 75°F at atmospheric pressure; R-123 (HCFC, ODP about 0.02) is its low-pressure replacement.

  • Recover liquid refrigerant first, then vapor; confirm dryness with a standing (decay) vacuum test read on a micron gauge.

  • Moisture inside a chiller forms acids and sludge; oil testing and moisture indicators are the standard detection methods.

Quick reference

Universal (Types I, II, and III)

  • Universal certification covers Type I, Type II, and Type III; a technician certified in only one type may not service another type's appliances.

  • The venting prohibition applies to ozone-depleting refrigerants and their HFC substitutes; only de minimis releases during good-faith service are permitted.

  • Refrigerant contacting flame or hot metal decomposes into hydrogen fluoride, hydrogen chloride, and phosgene - ventilate the area and avoid breathing the products.

  • Reclaimed refrigerant must meet AHRI 700 purity; recycled refrigerant is cleaned on site and reused in the same owner's equipment.

  • CFCs carry the highest ODP (R-11 = 1.0), HCFCs far less (R-123 about 0.02), and HFCs zero ODP but high GWP.

  • Never mix different refrigerants in one recovery cylinder; a mixed cylinder cannot be reclaimed and generally must be destroyed.

  • Recovery and recycling equipment must be EPA-certified and used only for the appliance type it is certified for; certification records must be kept.

  • Liquid refrigerant causes frostbite and eye damage; wear gloves and goggles and flush exposed skin with lukewarm, not hot, water.