EEA Electrician Exam study materials
EEA Electrician Exam study resources

EEA Electrician Exam flashcards

EEA Electrician Exam · Build recall with a focused review session.

33 cards. Read the term and the definition here. The deck at the top of this page is optional.

Ohm's Law
Current equals voltage divided by resistance (I = E/R). In AC circuits, replace resistance with impedance Z and account for the phase angle between voltage and current.
Three-Phase Power Formula
For a balanced three-phase load, real power P = √3 × line voltage × line current × power factor. Apparent power S = √3 × E × I, expressed in volt-amperes.
Conductor Resistance Formula
R = ρL/A, where ρ is resistivity in circular-mil-ohms per foot, L is length in feet, and A is area in circular mils. Resistance rises with length and temperature and falls with area.
Power Factor
The ratio of real power in kW to apparent power in kVA, equal to the cosine of the phase angle. A low power factor increases current for the same delivered real power.
NM Cable Restrictions
Nonmetallic-sheathed cable is permitted in dry locations and in some concealed spaces but is generally prohibited in wet locations, hazardous locations, and where subject to physical damage.
Raceway Fill Limits
Conductors in a raceway may not exceed a set percentage of interior cross-sectional area: 53% for one conductor, 31% for two, and 40% for three or more.
Box Fill Calculation
Box volume must accommodate each conductor, clamp, support fitting, device, and equipment grounding conductor using table volume allowances based on conductor size.
Conductor Ampacity Adjustment
Ampacity is reduced for high ambient temperature and for more than three current-carrying conductors in a raceway or cable, using adjustment factors from the code tables.
Continuous Load Rule
A continuous load is one expected to operate at maximum current for three hours or more. It is calculated at 125% for branch-circuit and feeder sizing.
Small-Appliance Branch Circuits
Dwelling kitchen small-appliance circuits are 20 A and must not supply other outlets. At least two are required, and each is counted at 1500 VA in the standard calculation.
General Lighting Load
Dwelling general lighting load is based on floor area at 3 VA per square foot (about 33 VA/m²). Other occupancies use different VA per area values from the code table.
Standard Service Calculation
Sum general lighting, small-appliance, laundry, and other loads; apply demand factors; add the largest motor at 125%; then size service conductors and equipment for the result.
Service Neutral Bonding
The grounded service conductor is bonded to the service enclosure and grounding electrode system at the service disconnect only. Downstream panels keep neutral and ground separate.
Equipment Grounding Conductor Sizing
The equipment grounding conductor is sized from the rating of the overcurrent device protecting the circuit, not from the phase conductor ampacity alone.
Grounding Electrode System
Includes metal underground water pipe, metal building frame, concrete-encased electrode, ground ring, rods, pipes, and plates. The grounding electrode conductor connects them to the service.
Bonding Around Water Meter
A bonding jumper is required around water meters and other removable or insulating sections of metallic piping so the grounding path remains continuous when the section is removed.
Next-Higher Overcurrent Rating
Where the calculated load does not exceed 800 A and conditions are met, the next standard overcurrent device rating above the calculated load may be used.
Short-Circuit Current Rating
Equipment SCCR must equal or exceed the available fault current at its installation point. Series-rated combinations must be listed and marked as a series combination.
Interrupting Rating
The maximum short-circuit current a fuse or circuit breaker can safely interrupt at its rated voltage. It must be at least the available fault current at the device terminals.
Overcurrent Coordination
Time-current curves are compared so the downstream device clears a fault before the upstream device operates, limiting the outage to the affected portion of the system.
Motor Branch-Circuit Conductors
Motor branch-circuit conductors are sized at 125% of the motor full-load current from the code table, not from the nameplate current used for overload sizing.
Motor Overload Protection
Overload devices protect the motor from sustained overheating and are set from nameplate current or table values. They are separate from branch-circuit short-circuit protection.
Motor Disconnect Location
A motor disconnecting means must be within sight from the controller and motor, or be lockable where the code permits a remote location.
HVAC Nameplate MCA and MOP
Hermetic refrigerant equipment nameplates give minimum circuit ampacity and maximum overcurrent protective device rating. Conductors are sized from MCA and protection from MOP.
Hazardous Location Classification
Class I covers gases and vapors, Class II dusts, and Class III fibers. Division or Zone and Group further define the hazard, and equipment must be listed for that classification.
Bathroom Receptacle Requirements
Bathroom receptacles require GFCI protection, and receptacles near sinks and in damp locations need GFCI protection and covers suitable for the environment.
Swimming Pool Equipotential Bonding
Metal parts of pool structures, equipment, and associated metal within the specified distance must be bonded together to equalize potential and reduce shock hazard.
Photovoltaic Rapid Shutdown
PV systems require a rapid shutdown function that reduces conductor voltage within the array to a safe level for firefighters, plus listed DC-rated equipment and labeling.
NEC Article 100 Definitions
Article 100 defines terms such as listed, labeled, approved, and identified. These definitions control how requirements are applied throughout the code.
Arc Flash Incident Energy
Calculated energy at a working distance from an arc source, expressed in cal/cm². It determines the arc flash boundary and the required PPE level.
Electrical Working Clearance
The code specifies minimum depth and width of working space in front of electrical equipment based on voltage and condition, so live parts can be worked safely.
Dwelling General Lighting Load
Calculate dwelling general lighting load from floor area at 3 VA per square foot (about 33 VA/m²), then apply the dwelling demand factors to determine the service load.
Panel Schedule Verification
Check connected load, demand load, bus rating, main breaker rating, and spare spaces. Confirm the calculated demand does not exceed the panel and service ratings.