Quick reference

Energy Systems and Grid Integration

  • Power triangle: apparent power S (VA) = √(P² + Q²); real power P = S·cosφ; reactive power Q = S·sinφ. Power factor cosφ below ~0.9 increases line losses and may trigger utility penalties.

  • Three-phase power: P = √3 · V_LL · I_L · cosφ. For a balanced load, per-phase analysis uses phase voltage V_LN = V_LL/√3.

  • Per-unit system: Z_pu = Z_actual / Z_base, with Z_base = V_base² / S_base. Per-unit values are identical across transformer voltage levels, which is why fault and load-flow studies use them.

  • Synchronous generator swing equation: (2H/ω_s)·d²δ/dt² = P_m − P_e. Inertia constant H (s) sets frequency response speed; low-inertia grids with inverter-based resources have faster, larger frequency excursions (higher RoCoF).

  • Transmission line surge impedance loading: SIL ≈ V_LL² / Z_c, with Z_c ≈ √(L/C) (about 400 Ω overhead, ~40 Ω cable). Loading near SIL minimizes reactive absorption/export.

  • Transformer and line losses scale with current squared: P_loss = I²R. Doubling current quadruples resistive losses; voltage upgrade by factor k reduces losses by roughly k² for the same power.

  • Load flow (power flow) solves nodal complex power balance using bus types: slack (V, θ set), PV (P, V set), PQ (P, Q set). Newton-Raphson converges quadratically; Gauss-Seidel converges linearly.

  • Frequency droop control: Δf = −R·ΔP for a governor with droop R (e.g., 5% droop means 100% power change for 5% frequency change). Inverter-based resources emulate droop via grid-forming or fast frequency response.

  • Reliability metrics: SAIDI = Σ(customer-minutes interrupted)/total customers; SAIFI = Σ(customer interruptions)/total customers. N-1 contingency criterion requires the system to survive loss of any single element without cascading.

Quick reference

Renewable Energy Technologies

  • Wind power available in the wind: P = ½·ρ·A·v³. Power scales with the cube of wind speed and linearly with air density; a 10% wind-speed error produces roughly a 33% power error.

  • Betz limit: maximum fraction of kinetic energy extractable by an ideal rotor is 16/27 ≈ 0.593 of the incoming wind power. Practical turbines reach Cp ≈ 0.35–0.50.

  • Tip-speed ratio λ = ωR/v; turbines operate near an optimal λ (typically 6–8 for three-blade horizontal-axis machines). Cp depends on λ and blade pitch angle β.

  • Solar PV: module power depends on irradiance and cell temperature; power temperature coefficient is typically −0.3% to −0.45% per °C above 25 °C STC.

  • PV cell equivalent circuit: photocurrent source in parallel with a diode and shunt resistance, in series with series resistance. Fill factor FF = P_max/(V_oc·I_sc).

  • Solar geometry: solar declination δ ≈ 23.45°·sin[360°·(284 + n)/365]. Air mass AM = 1/cos(zenith); AM1.5 is the standard spectrum reference.

  • Concentrated solar power (CSP) with thermal storage (molten salt) provides dispatchable output; parabolic trough and power tower are the dominant designs.

  • Hydropower: P = ρ·g·Q·H·η. Head H and flow Q drive output; pumped storage has round-trip efficiency typically 70–80%.

  • Biomass and biogas: energy content depends on moisture and lower heating value (LHV). Anaerobic digestion yields methane-rich biogas (~50–70% CH4).

Quick reference

Energy Efficiency and Demand Management

  • Energy efficiency ratio: EER = cooling output (Btu/h) / power input (W); COP = cooling output (kW) / power input (kW); COP ≈ EER/3.412.

  • Demand response categories: price-based (time-of-use, real-time pricing, critical-peak pricing) and incentive-based (direct load control, demand bidding, interruptible tariffs).

  • Load factor = average load / peak load over a period. Low load factor signals peaky consumption and higher per-kWh delivery cost.

  • Energy savings from variable-speed drives on fans/pumps follow affinity laws: flow ∝ speed, head ∝ speed², power ∝ speed³.

  • Lighting efficacy: LED ~100–200 lm/W, fluorescent ~60–100 lm/W, incandescent ~10–17 lm/W. Luminous efficacy converts electrical watts to lumens.

  • Building envelope: U-value (W/m²·K) is thermal transmittance; R-value = 1/U. Lower U-value means better insulation.

  • Peak demand reduction strategies include load shifting, thermal storage, behind-the-meter batteries, and automated demand response (OpenADR signaling).

  • Measurement and verification (M&V) per IPMVP options: Option A (retrofit isolation, key parameters), B (retrofit isolation, all parameters), C (whole facility), D (calibrated simulation).

Quick reference

Environmental Impact and Sustainability

  • Life-cycle assessment (LCA) stages per ISO 14040/14044: goal and scope definition, inventory analysis (LCI), impact assessment (LCIA), and interpretation.

  • Common impact categories: global warming potential (GWP, kg CO2e), acidification, eutrophication, ozone depletion, photochemical smog, and particulate matter.

  • GWP values are relative to CO2 over a time horizon; methane has GWP100 ≈ 28–30 (AR5, fossil) and N2O ≈ 265–298.

  • Environmental impact assessment (EIA) typically includes screening, scoping, baseline study, impact prediction, mitigation, and monitoring.

  • Cumulative impacts consider combined effects of multiple projects and past, present, and reasonably foreseeable actions.

  • Carbon footprint of electricity depends on the generation mix; grid emission factor = total emissions / total generation (kg CO2e/kWh).

  • Circular economy principles: reduce, reuse, recycle, recover. Material intensity of solar PV and wind includes critical minerals (lithium, cobalt, rare earths).

  • Water use: thermoelectric cooling (once-through vs. closed-loop) and hydropower evaporation are key water-intensity concerns for energy systems.

Quick reference

Energy Policy, Regulation, and Economics

  • Levelized cost of energy (LCOE) = Σ[(I_t + O_t + F_t)/(1+r)^t] / Σ[(E_t)/(1+r)^t], where I is investment, O is O&M, F is fuel, E is energy, r is discount rate.

  • Feed-in tariffs (FiT) pay a fixed price per kWh; renewable portfolio standards (RPS) mandate a minimum renewable share; auctions/tenders set competitive prices.

  • Net metering credits exports at retail rate; net billing credits at avoided cost or wholesale rate.

  • Capacity markets pay for availability (kW) rather than energy (kWh); energy-only markets rely on scarcity pricing.

  • Merit order effect: low-marginal-cost renewables push down wholesale prices and displace higher-cost plants.

  • Discounting: present value PV = FV/(1+r)^n. Higher discount rates favor near-term cash flows and lower long-lived capital-intensive projects' apparent value.

  • Externalities (health, climate) can be internalized via carbon pricing: carbon tax (price-based) or cap-and-trade (quantity-based).

  • Regulatory frameworks: rate-of-return (cost-of-service) vs. performance-based regulation. Depreciation, rate base, and allowed return drive utility revenue.

Quick reference

GHG Accounting and Emissions Measurement

  • GHG Protocol scopes: Scope 1 (direct combustion/process), Scope 2 (purchased electricity/heat), Scope 3 (value chain, upstream and downstream).

  • Scope 2 dual reporting: location-based (grid average emission factor) and market-based (contractual instruments such as RECs/PPAs).

  • Emission calculation: emissions = activity data × emission factor (e.g., kWh × kg CO2e/kWh; liters fuel × kg CO2/L).

  • Global Warming Potential converts non-CO2 gases to CO2-equivalent: CO2e = mass × GWP.

  • ISO 14064-1 specifies organizational GHG inventory principles: relevance, completeness, consistency, accuracy, transparency.

  • The GHG Protocol requires setting a base year, recalculating for structural changes (mergers, acquisitions, methodology changes) and using a significance threshold.

  • Direct measurement methods: continuous emissions monitoring systems (CEMS), stack testing, and flow meters; indirect methods use activity data and factors.

  • Verification: third-party assurance (limited vs. reasonable) checks inventory accuracy against a standard; materiality thresholds apply.

  • Avoided emissions and renewable energy certificates (RECs) must be reported separately from the inventory; RECs represent 1 MWh of renewable generation attributes.

Quick reference

Climate Risk, Adaptation, and Resilience

  • Climate risk = hazard × exposure × vulnerability. Hazard is the physical event; exposure is assets/populations in harm's way; vulnerability is susceptibility to damage.

  • TCFD framework pillars: governance, strategy, risk management, and metrics/targets. Physical risks are acute (floods, storms) or chronic (sea-level rise, heat).

  • Transition risks: policy/legal, technology, market, and reputational risks arising from the shift to a low-carbon economy.

  • Climate scenarios: RCPs (Representative Concentration Pathways) and SSPs (Shared Socioeconomic Pathways); SSP5-8.5 is high-emissions, SSP1-2.6 is low-emissions.

  • Adaptation measures for energy systems: hardening substations, undergrounding lines, flood defenses, cooling-water resilience, and diversified generation.

  • Resilience metrics: robustness, rapidity, resourcefulness, redundancy. Grid resilience includes islanding capability and microgrids.

  • Stress testing: scenario-based analysis of assets under physical and transition risk, often using return periods (e.g., 100-year flood).

  • Stranded assets: fossil fuel reserves or infrastructure that may lose value under decarbonization policy and demand shifts.