FL Fire Alarm cheat sheet
FL Fire Alarm ยท Keep the key ideas within reach.
Florida Laws and Rules
Fire alarm contracting in Florida is licensed under Chapter 489, Part II, Florida Statutes; a certified contractor works statewide, a registered contractor is limited to the municipality or county that issued the registration.
Chapter 633, Florida Statutes (Florida Fire Prevention Code) governs fire protection system permitting, inspection, and the authority having jurisdiction (AHJ); the AHJ for fire alarm plan review is typically the local fire official, not the building official alone.
Certificate of Competency holders must qualify a business; a qualifying agent may qualify only one fire protection system contracting business unless the additional business is approved by the licensing board.
Financial responsibility: certificate holders must maintain a $10,000 surety bond or irrevocable letter of credit, or demonstrate net worth of at least $10,000, and must file proof with the DBPR.
Continuing education for certified fire alarm contractors is 14 hours per biennial renewal cycle, including at least 1 hour each on Florida laws and rules, workers' compensation, workplace safety, and business practices.
License renewal is biennial, expiring August 31 of odd-numbered years for certified contractors; late renewal triggers a $50 late fee and possible reversion to inactive status.
Grounds for discipline under s. 489.129 include abandoning a project, aiding unlicensed activity, signing a permit for work not performed under the qualifier's supervision, and failing to obtain required permits.
Contractors must include the license number in advertising; failure to display the certificate number on contracts, bids, and vehicles is a citable violation.
Business Practices
Written contract requirement: fire alarm contracts must be in writing for jobs over $500, must include the license number, and must state the scope, price, and payment schedule.
Notice of Commencement: on projects over $2,500, the owner must record a Notice of Commencement before the first inspection; the contractor must be given a certified copy before starting work.
Lien rights: a contractor must serve a Notice to Owner within 45 days of first furnishing labor or materials to preserve lien rights on a private project; final payment lien deadlines run 90 days from last furnishing.
Florida's Construction Lien Law (Chapter 713) requires a contractor to provide a Contractor's Final Payment Affidavit before filing a lien foreclosure action.
Truth in Contracting: s. 489.119 requires contracts to disclose the contractor's name, address, and certificate or registration number; subcontracting without written consent is a breach.
Retainage on private construction is limited to 10 percent; on public projects, Florida's prompt payment act requires payment within 30 days of a proper invoice.
Homeowner's recovery: the Florida Homeowners' Construction Recovery Fund may pay up to $50,000 per claimant (aggregate caps per licensee) for losses caused by a licensed contractor's misconduct.
Change orders must be written and signed; oral change orders are a leading source of disputes and are generally unenforceable for extra work over the contract threshold.
Workers' Compensation
Florida construction employers with one or more employees (including the owner working on the job) must carry workers' compensation; corporate officers may elect exemption but must file the election with the Division of Workers' Compensation.
Sole proprietors and partners are not automatically covered; they must elect coverage and pay premiums to be included, and the election must be documented.
Workers' comp coverage must be maintained continuously; a lapse requires the contractor to notify the licensing board and can result in license suspension until reinstated.
s. 440.10 makes the general contractor liable for subcontractor employees' injuries when the subcontractor is uninsured; the GC must verify a Certificate of Insurance before allowing any sub on site.
The Certificate of Insurance must show the policy number, carrier, effective and expiration dates, and the class codes matching the work performed; a certificate alone does not prove coverage-verify with the carrier.
First report of injury must be filed with the carrier within 7 days of knowledge; the carrier reports to the state within 14 days.
Florida workers' comp provides indemnity at 66 2/3 percent of the average weekly wage for temporary total disability, subject to the statewide maximum and minimum compensation rates in effect for the injury date.
Exemptions: an officer exemption is valid only if the officer owns at least 10 percent of the corporation and the exemption is filed and approved; LLC members with at least 10 percent may also elect exemption.
Workplace Safety
OSHA 29 CFR 1926 Subpart K governs electrical safety on construction sites; temporary wiring, GFCI protection, and lockout/tagout apply to fire alarm installation work.
Fall protection is required at 6 feet or more in construction; personal fall arrest systems, guardrails, or safety nets must be used, and the 100 percent tie-off rule applies when working from aerial lifts.
Ladder safety: 4-to-1 setback for extension ladders, 3 points of contact, and the top three rungs may not be used for standing; ladders must extend 3 feet above the landing.
Lockout/tagout (29 CFR 1910.147) requires a written energy control procedure, employee training, and verification of de-energization before work on alarm panels or circuits.
Personal protective equipment: hard hats, safety glasses, and hearing protection where noise exceeds 85 dBA TWA; NFPA 70E arc-rated clothing is required for energized work within the arc flash boundary.
Hazard communication (29 CFR 1910.1200) requires a written program, Safety Data Sheets for battery electrolytes and chemicals, and labeling of secondary containers.
Scaffold users must be trained; scaffolds over 10 feet require fall protection, and the platform must be fully planked with a 4-to-1 base-to-height ratio for supported scaffolds.
Confined space entry for vaults and risers requires atmospheric testing, an attendant, and a permit under 29 CFR 1926 Subpart AA.
False Alarm Prevention
A false alarm is any alarm activation not caused by a fire or other emergency condition, including activations caused by construction dust, smoke from cooking, or system malfunction.
Florida law (s. 633.4265) allows local governments to establish false alarm fees; many jurisdictions charge after the second or third false alarm in a 12-month period, with escalating fees.
Detector placement: keep smoke detectors at least 3 feet (36 inches) from HVAC supply diffusers and at least 20 feet from cooking appliances to reduce nuisance alarms.
Duct smoke detectors must be installed per NFPA 90A and tested with the manufacturer's listed test method; improper sampling tube orientation is a common false alarm cause.
During construction, smoke detectors should be disabled or covered with approved covers and the system placed on test; the AHJ must be notified before any disabling.
Verify detector spacing and the 4-inch rule: detectors must be at least 4 inches from a wall when mounted on the ceiling, and wall-mounted detectors 4 to 12 inches from the ceiling.
Alarm verification (NFPA 72) requires a 60-second confirmation period before a signal is transmitted for smoke detectors, reducing nuisance transmissions.
After any false alarm, document the cause, corrective action, and retest results; repeated false alarms can trigger AHJ-ordered system modifications or suspension of monitoring.
Florida Building Code Advanced Module
The Florida Building Code (FBC) is updated on a three-year cycle; the 8th Edition (2023) took effect December 31, 2023, and local amendments are limited to those approved through the state process.
FBC Chapter 9 (Fire Protection Systems) and the Florida Fire Prevention Code (NFPA 1 and NFPA 101 as adopted) govern when a fire alarm system is required based on occupancy and occupant load.
NFPA 72 (National Fire Alarm and Signaling Code) is adopted by reference; the edition referenced by the current FBC is the applicable standard for design, installation, and testing.
Plan review: fire alarm shop drawings must be submitted to the AHJ with the permit application and must include device locations, riser diagram, battery calculations, and voltage drop calculations.
Inspection and testing: NFPA 72 requires acceptance testing of every initiating device and notification appliance, plus a completed Record of Completion and Record of Inspection and Testing.
Battery calculations must demonstrate 24 hours of standby followed by 5 minutes (or 15 minutes for voice systems) of alarm operation at the end of the battery's useful life.
Accessibility: visible notification appliances must meet ADA and FBC accessibility requirements, including candela ratings based on room size and mounting height per NFPA 72 tables.
High-rise and special occupancy requirements: FBC requires voice evacuation and fire command centers in high-rise buildings over 75 feet, with specific survivability and pathway requirements.
Florida Laws and Rules
Licensing categories: certified fire protection system contractor (works statewide) versus registered contractor (limited to the jurisdiction that registered them).
Continuing education: 14 hours per biennium, including 1 hour each on laws and rules, workers' comp, workplace safety, and business practices.
Discipline grounds under s. 489.129 include abandonment, unlicensed activity, and signing permits for unsupervised work.
License number must appear on advertising, contracts, and bids under s. 489.119.
Biennial renewal for certified contractors expires August 31 of odd-numbered years; late fee is $50.
Financial responsibility: $10,000 bond or irrevocable letter of credit, or $10,000 net worth, filed with DBPR.
A qualifying agent may qualify only one business unless the board approves an additional qualifying business.
The AHJ for fire alarm permitting and plan review is the local fire official under Chapter 633.
Business Practices
Written contract required for jobs over $500; must include license number, scope, price, and payment schedule.
Notice to Owner must be served within 45 days of first furnishing to preserve lien rights on private projects.
Notice of Commencement required on projects over $2,500 and must be recorded before the first inspection.
Retainage on private construction is capped at 10 percent under s. 713.346.
Contractor's Final Payment Affidavit is required before filing a lien foreclosure action.
Florida Homeowners' Construction Recovery Fund may pay up to $50,000 per claimant for licensed contractor misconduct.
Change orders must be written and signed; oral change orders are generally unenforceable for extra work.
Public project prompt payment requires payment within 30 days of a proper invoice.
Workers' Compensation
Construction employers with one or more employees must carry workers' comp; corporate officers may elect exemption if they own at least 10 percent.
s. 440.10 makes the general contractor liable for uninsured subcontractor employees' injuries.
First report of injury must be filed with the carrier within 7 days of knowledge.
Indemnity for temporary total disability is 66 2/3 percent of the average weekly wage, subject to statewide maximums.
A lapse in coverage must be reported to the licensing board and can result in license suspension.
Verify a Certificate of Insurance with the carrier-do not rely on the certificate alone.
Sole proprietors and partners must elect coverage to be included; election must be documented.
Class codes on the policy must match the work performed; mismatches can void coverage for a claim.
Workplace Safety
Fall protection required at 6 feet or more in construction; 100 percent tie-off when working from aerial lifts.
Extension ladders: 4-to-1 setback, extend 3 feet above the landing, and never stand on the top three rungs.
Lockout/tagout under 29 CFR 1910.147 requires a written procedure and verification of de-energization before panel work.
NFPA 70E arc-rated clothing is required for energized work within the arc flash boundary.
Hazard communication requires a written program, SDS access, and labeling of secondary containers.
Scaffolds over 10 feet require fall protection; supported scaffolds need a 4-to-1 base-to-height ratio.
Confined space entry in vaults requires atmospheric testing, an attendant, and a permit under 29 CFR 1926 Subpart AA.
Hearing protection is required where noise exceeds 85 dBA as an 8-hour time-weighted average.
False Alarm Prevention
A false alarm is any activation not caused by a fire or emergency condition, including dust, cooking smoke, or malfunction.
s. 633.4265 allows local governments to impose escalating false alarm fees, often after the second or third alarm in 12 months.
Keep smoke detectors at least 3 feet from HVAC supply diffusers and 20 feet from cooking appliances.
Duct smoke detectors must be installed per NFPA 90A and tested with the manufacturer's listed method.
During construction, cover or disable detectors and notify the AHJ before disabling any part of the system.
Detectors must be at least 4 inches from a wall when ceiling-mounted; wall-mounted detectors 4 to 12 inches from the ceiling.
Alarm verification under NFPA 72 requires a 60-second confirmation before signal transmission for smoke detectors.
Document the cause, corrective action, and retest after every false alarm to avoid AHJ-ordered modifications.
Florida Building Code Advanced Module
The FBC updates every three years; the 8th Edition (2023) took effect December 31, 2023.
FBC Chapter 9 and the Florida Fire Prevention Code (NFPA 1 and NFPA 101) determine when a fire alarm system is required.
NFPA 72 is adopted by reference; the edition cited by the current FBC governs design, installation, and testing.
Shop drawings must include device locations, riser diagram, battery calculations, and voltage drop calculations.
NFPA 72 acceptance testing requires testing every initiating device and notification appliance and completing a Record of Completion.
Battery calculations must show 24 hours standby plus 5 minutes alarm (15 minutes for voice systems) at end of battery life.
Visible notification appliances must meet ADA and FBC candela requirements based on room size and mounting height.
High-rise buildings over 75 feet require voice evacuation and a fire command center under the FBC.
Florida Laws and Rules
Certified contractors work statewide; registered contractors are limited to the jurisdiction that registered them.
Continuing education is 14 hours per biennium, including 1 hour each on laws and rules, workers' comp, workplace safety, and business practices.
s. 489.129 discipline grounds include abandonment, unlicensed activity, and signing permits for unsupervised work.
License numbers must appear on advertising, contracts, and bids under s. 489.119.
Certified licenses expire August 31 of odd-numbered years; late renewal fee is $50.
Financial responsibility requires a $10,000 bond or letter of credit, or $10,000 net worth, filed with DBPR.
A qualifying agent may qualify only one business unless the board approves an additional one.
The local fire official is the AHJ for fire alarm permitting and plan review under Chapter 633.
Business Practices
Written contracts are required for jobs over $500 and must include the license number, scope, price, and payment schedule.
Serve a Notice to Owner within 45 days of first furnishing to preserve lien rights on private projects.
Record a Notice of Commencement on projects over $2,500 before the first inspection.
Retainage on private construction is capped at 10 percent under s. 713.346.
A Contractor's Final Payment Affidavit is required before filing a lien foreclosure action.
The Homeowners' Construction Recovery Fund may pay up to $50,000 per claimant for licensed contractor misconduct.
Change orders must be written and signed; oral change orders are generally unenforceable.
Public project prompt payment requires payment within 30 days of a proper invoice.
Workers' Compensation
Construction employers with one or more employees must carry workers' comp; officers owning at least 10 percent may elect exemption.
s. 440.10 makes the general contractor liable for uninsured subcontractor employees' injuries.
First report of injury must be filed with the carrier within 7 days of knowledge.
Temporary total disability indemnity is 66 2/3 percent of the average weekly wage, subject to statewide maximums.
A coverage lapse must be reported to the licensing board and can result in license suspension.
Verify a Certificate of Insurance with the carrier; the certificate alone does not prove coverage.
Sole proprietors and partners must elect coverage and document the election.
Policy class codes must match the work performed; mismatches can void coverage for a claim.
Workplace Safety
Fall protection is required at 6 feet or more in construction; 100 percent tie-off applies when working from aerial lifts.
Extension ladders need a 4-to-1 setback, must extend 3 feet above the landing, and the top three rungs may not be used for standing.
Lockout/tagout under 29 CFR 1910.147 requires a written procedure and verification of de-energization before panel work.
NFPA 70E arc-rated clothing is required for energized work within the arc flash boundary.
Hazard communication requires a written program, SDS access, and labeling of secondary containers.
Scaffolds over 10 feet require fall protection; supported scaffolds need a 4-to-1 base-to-height ratio.
Confined space entry in vaults requires atmospheric testing, an attendant, and a permit under 29 CFR 1926 Subpart AA.
Hearing protection is required where noise exceeds 85 dBA as an 8-hour time-weighted average.
False Alarm Prevention
A false alarm is any activation not caused by a fire or emergency condition, including dust, cooking smoke, or malfunction.
s. 633.4265 allows local governments to impose escalating false alarm fees, often after the second or third alarm in 12 months.
Keep smoke detectors at least 3 feet from HVAC supply diffusers and 20 feet from cooking appliances.
Duct smoke detectors must be installed per NFPA 90A and tested with the manufacturer's listed method.
During construction, cover or disable detectors and notify the AHJ before disabling any part of the system.
Ceiling-mounted detectors must be at least 4 inches from a wall; wall-mounted detectors 4 to 12 inches from the ceiling.
Alarm verification under NFPA 72 requires a 60-second confirmation before signal transmission for smoke detectors.
Document the cause, corrective action, and retest after every false alarm to avoid AHJ-ordered modifications.
Florida Building Code Advanced Module
The FBC updates every three years; the 8th Edition (2023) took effect December 31, 2023.
FBC Chapter 9 and the Florida Fire Prevention Code (NFPA 1 and NFPA 101) determine when a fire alarm system is required.
NFPA 72 is adopted by reference; the edition cited by the current FBC governs design, installation, and testing.
Shop drawings must include device locations, riser diagram, battery calculations, and voltage drop calculations.
NFPA 72 acceptance testing requires testing every initiating device and notification appliance and completing a Record of Completion.
Battery calculations must show 24 hours standby plus 5 minutes alarm (15 minutes for voice systems) at end of battery life.
Visible notification appliances must meet ADA and FBC candela requirements based on room size and mounting height.
High-rise buildings over 75 feet require voice evacuation and a fire command center under the FBC.
Florida Laws and Rules
Certified contractors work statewide; registered contractors are limited to the jurisdiction that registered them.
Continuing education is 14 hours per biennium, including 1 hour each on laws and rules, workers' comp, workplace safety, and business practices.
s. 489.129 discipline grounds include abandonment, unlicensed activity, and signing permits for unsupervised work.
License numbers must appear on advertising, contracts, and bids under s. 489.119.
Certified licenses expire August 31 of odd-numbered years; late renewal fee is $50.
Financial responsibility requires a $10,000 bond or letter of credit, or $10,000 net worth, filed with DBPR.
A qualifying agent may qualify only one business unless the board approves an additional one.
The local fire official is the AHJ for fire alarm permitting and plan review under Chapter 633.
Business Practices
Written contracts are required for jobs over $500 and must include the license number, scope, price, and payment schedule.
Serve a Notice to Owner within 45 days of first furnishing to preserve lien rights on private projects.
Record a Notice of Commencement on projects over $2,500 before the first inspection.
Retainage on private construction is capped at 10 percent under s. 713.346.
A Contractor's Final Payment Affidavit is required before filing a lien foreclosure action.
The Homeowners' Construction Recovery Fund may pay up to $50,000 per claimant for licensed contractor misconduct.
Change orders must be written and signed; oral change orders are generally unenforceable.
Public project prompt payment requires payment within 30 days of a proper invoice.
Workers' Compensation
Construction employers with one or more employees must carry workers' comp; officers owning at least 10 percent may elect exemption.
s. 440.10 makes the general contractor liable for uninsured subcontractor employees' injuries.
First report of injury must be filed with the carrier within 7 days of knowledge.
Temporary total disability indemnity is 66 2/3 percent of the average weekly wage, subject to statewide maximums.
A coverage lapse must be reported to the licensing board and can result in license suspension.
Verify a Certificate of Insurance with the carrier; the certificate alone does not prove coverage.
Sole proprietors and partners must elect coverage and document the election.
Policy class codes must match the work performed; mismatches can void coverage for a claim.
Workplace Safety
Fall protection is required at 6 feet or more in construction; 100 percent tie-off applies when working from aerial lifts.
Extension ladders need a 4-to-1 setback, must extend 3 feet above the landing, and the top three rungs may not be used for standing.
Lockout/tagout under 29 CFR 1910.147 requires a written procedure and verification of de-energization before panel work.
NFPA 70E arc-rated clothing is required for energized work within the arc flash boundary.
Hazard communication requires a written program, SDS access, and labeling of secondary containers.
Scaffolds over 10 feet require fall protection; supported scaffolds need a 4-to-1 base-to-height ratio.
Confined space entry in vaults requires atmospheric testing, an attendant, and a permit under 29 CFR 1926 Subpart AA.
Hearing protection is required where noise exceeds 85 dBA as an 8-hour time-weighted average.
False Alarm Prevention
A false alarm is any activation not caused by a fire or emergency condition, including dust, cooking smoke, or malfunction.
s. 633.4265 allows local governments to impose escalating false alarm fees, often after the second or third alarm in 12 months.
Keep smoke detectors at least 3 feet from HVAC supply diffusers and 20 feet from cooking appliances.
Duct smoke detectors must be installed per NFPA 90A and tested with the manufacturer's listed method.
During construction, cover or disable detectors and notify the AHJ before disabling any part of the system.
Ceiling-mounted detectors must be at least 4 inches from a wall; wall-mounted detectors 4 to 12 inches from the ceiling.
Alarm verification under NFPA 72 requires a 60-second confirmation before signal transmission for smoke detectors.
Document the cause, corrective action, and retest after every false alarm to avoid AHJ-ordered modifications.
Florida Building Code Advanced Module
The FBC updates every three years; the 8th Edition (2023) took effect December 31, 2023.
FBC Chapter 9 and the Florida Fire Prevention Code (NFPA 1 and NFPA 101) determine when a fire alarm system is required.
NFPA 72 is adopted by reference; the edition cited by the current FBC governs design, installation, and testing.
Shop drawings must include device locations, riser diagram, battery calculations, and voltage drop calculations.
NFPA 72 acceptance testing requires testing every initiating device and notification appliance and completing a Record of Completion.
Battery calculations must show 24 hours standby plus 5 minutes alarm (15 minutes for voice systems) at end of battery life.
Visible notification appliances must meet ADA and FBC candela requirements based on room size and mounting height.
High-rise buildings over 75 feet require voice evacuation and a fire command center under the FBC.
Florida Laws and Rules
Certified contractors work statewide; registered contractors are limited to the jurisdiction that registered them.
Continuing education is 14 hours per biennium, including 1 hour each on laws and rules, workers' comp, workplace safety, and business practices.
s. 489.129 discipline grounds include abandonment, unlicensed activity, and signing permits for unsupervised work.
License numbers must appear on advertising, contracts, and bids under s. 489.119.
Certified licenses expire August 31 of odd-numbered years; late renewal fee is $50.
Financial responsibility requires a $10,000 bond or letter of credit, or $10,000 net worth, filed with DBPR.
A qualifying agent may qualify only one business unless the board approves an additional one.
The local fire official is the AHJ for fire alarm permitting and plan review under Chapter 633.
Business Practices
Written contracts are required for jobs over $500 and must include the license number, scope, price, and payment schedule.
Serve a Notice to Owner within 45 days of first furnishing to preserve lien rights on private projects.
Record a Notice of Commencement on projects over $2,500 before the first inspection.
Retainage on private construction is capped at 10 percent under s. 713.346.
A Contractor's Final Payment Affidavit is required before filing a lien foreclosure action.
The Homeowners' Construction Recovery Fund may pay up to $50,000 per claimant for licensed contractor misconduct.
Change orders must be written and signed; oral change orders are generally unenforceable.
Public project prompt payment requires payment within 30 days of a proper invoice.
Workers' Compensation
Construction employers with one or more employees must carry workers' comp; officers owning at least 10 percent may elect exemption.
s. 440.10 makes the general contractor liable for uninsured subcontractor employees' injuries.
First report of injury must be filed with the carrier within 7 days of knowledge.
Temporary total disability indemnity is 66 2/3 percent of the average weekly wage, subject to statewide maximums.
A coverage lapse must be reported to the licensing board and can result in license suspension.
Verify a Certificate of Insurance with the carrier; the certificate alone does not prove coverage.
Sole proprietors and partners must elect coverage and document the election.
Policy class codes must match the work performed; mismatches can void coverage for a claim.
Workplace Safety
Fall protection is required at 6 feet or more in construction; 100 percent tie-off applies when working from aerial lifts.
Extension ladders need a 4-to-1 setback, must extend 3 feet above the landing, and the top three rungs may not be used for standing.
Lockout/tagout under 29 CFR 1910.147 requires a written procedure and verification of de-energization before panel work.
NFPA 70E arc-rated clothing is required for energized work within the arc flash boundary.
Hazard communication requires a written program, SDS access, and labeling of secondary containers.
Scaffolds over 10 feet require fall protection; supported scaffolds need a 4-to-1 base-to-height ratio.
Confined space entry in vaults requires atmospheric testing, an attendant, and a permit under 29 CFR 1926 Subpart AA.
Hearing protection is required where noise exceeds 85 dBA as an 8-hour time-weighted average.
False Alarm Prevention
A false alarm is any activation not caused by a fire or emergency condition, including dust, cooking smoke, or malfunction.
s. 633.4265 allows local governments to impose escalating false alarm fees, often after the second or third alarm in 12 months.
Keep smoke detectors at least 3 feet from HVAC supply diffusers and 20 feet from cooking appliances.
Duct smoke detectors must be installed per NFPA 90A and tested with the manufacturer's listed method.
During construction, cover or disable detectors and notify the AHJ before disabling any part of the system.
Ceiling-mounted detectors must be at least 4 inches from a wall; wall-mounted detectors 4 to 12 inches from the ceiling.
Alarm verification under NFPA 72 requires a 60-second confirmation before signal transmission for smoke detectors.
Document the cause, corrective action, and retest after every false alarm to avoid AHJ-ordered modifications.
Florida Building Code Advanced Module
The FBC updates every three years; the 8th Edition (2023) took effect December 31, 2023.
FBC Chapter 9 and the Florida Fire Prevention Code (NFPA 1 and NFPA 101) determine when a fire alarm system is required.
NFPA 72 is adopted by reference; the edition cited by the current FBC governs design, installation, and testing.
Shop drawings must include device locations, riser diagram, battery calculations, and voltage drop calculations.
NFPA 72 acceptance testing requires testing every initiating device and notification appliance and completing a Record of Completion.
Battery calculations must show 24 hours standby plus 5 minutes alarm (15 minutes for voice systems) at end of battery life.
Visible notification appliances must meet ADA and FBC candela requirements based on room size and mounting height.
High-rise buildings over 75 feet require voice evacuation and a fire command center under the FBC.