GA Fire Sprinkler study materials
GA Fire Sprinkler study resources

GA Fire Sprinkler flashcards

GA Fire Sprinkler · Build recall with a focused review session.

34 cards. Read the term and the definition here. The deck at the top of this page is optional.

Light hazard density
Design density of 0.10 gpm/ft² over 1,500 ft² for light hazard occupancies such as offices, churches, and schools, per NFPA 13 density/area curves.
Ordinary hazard Group 2
Occupancy with moderate combustibility (e.g., mercantile, parking garages); design density 0.20 gpm/ft² over 1,500 ft² per NFPA 13.
Wet-pipe system
Automatic sprinkler system with water under pressure in piping at all times; fastest acting and most common system type.
Dry-pipe system
System with air pressure in piping; water enters after sprinkler operation releases air; requires dry-pipe valve, air compressor, and accelerator for large systems.
Preaction system
Dry system with detection; single-interlock releases water on detection only; double-interlock requires both detection and sprinkler operation; non-interlock releases on either.
Deluge system
System with open sprinklers/nozzles; all discharge simultaneously upon detection activation; used for high-hazard or special protection.
Maximum sprinkler coverage
Light hazard 225 ft², ordinary hazard 130 ft², extra hazard 100 ft² per sprinkler for standard spray upright/pendent sprinklers per NFPA 13 Table 8.6.2.2.1(a).
Maximum sprinkler spacing
Light and ordinary hazard 15 ft, extra hazard 12 ft between sprinklers on branch lines for standard spray sprinklers per NFPA 13.
Minimum sprinkler spacing
6 ft between sprinklers on the same branch line to avoid cold soldering, unless baffles or calculations permit closer spacing per NFPA 13 8.6.2.2.1.
Deflector distance
Standard spray sprinklers: 1-12 in. below ceiling; residential: 1-4 in.; extended coverage per listing; ensures proper spray pattern per NFPA 13.
Obstruction rule
Sprinklers must be within 12 in. horizontally of obstructions ≤4 ft wide; greater than 4 ft wide requires sprinklers under or split per NFPA 13 Figure 8.6.5.1.1.
Hazen-Williams formula
Pressure loss: p = 4.52 Q^1.85 / (C^1.85 d^4.87) in psi/ft; C=120 for black steel, 100 for galvanized; Q in gpm, d in inches.
Hose allowance
Additional flow added to sprinkler demand for hose streams; typically 250 gpm for light hazard, 250-500 gpm for ordinary/extra hazard per NFPA 13.
NFPA 13D duration
One- and two-family dwellings and manufactured homes; design for 10-minute water supply duration; at least one sprinkler per compartment; no attic sprinklers generally.
NFPA 13R scope
Residential occupancies up to four stories above grade (apartments, condos); design for 30-minute duration; sprinklers in all habitable areas, closets, and some attics.
13R design density
0.05 gpm/ft² over entire floor area or 0.10 gpm/ft² over most remote two sprinklers, whichever is greater, per NFPA 13R.
Residential sprinkler pressure
Listed residential sprinklers (NFPA 13R/13D) have minimum design pressure of 7 psi and larger coverage up to 20 ft x 20 ft for 13D.
13R omission closets
NFPA 13R permits omitting sprinklers in small closets (<24 ft²), bathrooms (<55 ft²), and certain attics/crawlspaces if noncombustible or limited combustible.
Main drain test
Annual test recording static and residual pressure; a drop of >10% from baseline indicates a supply problem or partially closed valve per NFPA 25.
Dry-pipe valve trip test
Annual test; record time to trip and time for water to reach test valve; should be within 60 seconds for dry pipe per NFPA 25.
Sprinkler replacement interval
Quick-response sprinklers at 20 years, then 10-year intervals; standard response at 50 years, then 10-year intervals per NFPA 25 Table 5.4.1.1.1.
Fire pump annual flow test
Test at 0%, 100%, 150% of rated flow; compare to baseline; churn pressure should not exceed 140% of rated per NFPA 25.
Impairment procedures
Tag system, notify fire department and occupants, provide fire watch if system out of service >4 hours per NFPA 25 Chapter 15.
Water flow test extrapolation
Plot static, residual, and flow on semi-log paper; extrapolate to 0 psi to estimate available flow using N^1.85 graph or formula.
Fire pump churn pressure
Maximum pressure at zero flow; must not exceed 140% of rated pressure per NFPA 20 to avoid overpressurizing system components.
Standpipe Class I
2½-in. outlets for fire department use; 100 psi at top; required in buildings with high-rise or large area per NFPA 14.
Standpipe Class II
1½-in. outlets for occupant use; 100 psi at top; typically in buildings where fire department access is limited.
Standpipe Class III
Both 2½-in. and 1½-in. outlets; provides fire department and occupant use; 100 psi at top per NFPA 14.
Georgia sprinkler contractor license
Issued by Georgia Fire Marshal's Office under O.C.G.A. Title 25-12; requires company license and at least one certified technician; biennial renewal.
Georgia technician qualifications
Minimum 2 years documented experience, pass NICET Level II or state exam, background check, fingerprinting, and 8 hours annual continuing education.
Georgia plan review
Submit shop drawings, hydraulic calculations, and product data to local AHJ for approval before installation; permit required before work begins.
Hydrostatic test
Test at 200 psi for 2 hours (or 50 psi above working pressure) per NFPA 13; required before concealment and final inspection.
Fall protection threshold
Required when working at heights >6 ft per OSHA 1926.501; use ladders, scaffolds, or lifts properly; inspect before use.
Lockout/tagout
Procedures required when servicing equipment with hazardous energy; follow OSHA 1910.147 to prevent unexpected startup or release of energy.