HKIE Professional Assessment - Energy Discipline flashcards
HKIE Professional Assessment - Energy Discipline · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Exergy
- The maximum useful work obtainable from a system as it reversibly comes to equilibrium with its environment. Unlike energy, exergy is destroyed by irreversibility, so exergy analysis pinpoints where quality of energy is lost.
- Capacity factor
- Actual energy generated over a period divided by the energy the plant would produce running at rated output continuously. It measures how fully a generating asset is used.
- Load factor
- Average load divided by peak load over a period. A low value indicates peaky demand, meaning capital-intensive plant is underused and unit costs rise.
- Carnot efficiency
- The maximum thermal efficiency of any heat engine between a hot reservoir at Th and cold reservoir at Tc, both in kelvin: 1 minus Tc over Th. It is an unattainable upper bound.
- Overall heat transfer coefficient
- A combined coefficient U for a wall or exchanger, where 1/UA equals the sum of convection and conduction resistances. The largest resistance dominates the design.
- NTU effectiveness method
- A heat exchanger design method using effectiveness, the ratio of actual to maximum possible heat transfer, and NTU, the number of transfer units. It avoids iterative outlet temperature solving.
- Rankine cycle
- The steam power cycle of pump, boiler, turbine and condenser. Efficiency improves with higher steam pressure and temperature, lower condenser pressure, reheat and regenerative feedwater heating.
- Combined cycle efficiency
- A gas turbine exhausting into a heat recovery steam generator that drives a steam turbine. Overall efficiency of 55 to 62 percent exceeds either simple cycle alone.
- Turbine heat rate
- The thermal energy input in kilojoules per kilowatt-hour of output, equal to 3600 divided by cycle efficiency. A lower heat rate means better plant performance.
- Theoretical air for combustion
- The stoichiometric air required to fully oxidise a fuel; for a hydrocarbon CxHy, oxygen moles equal x plus y over four per mole of fuel. Practical plant uses excess air above this.
- Betz limit
- The maximum fraction of wind kinetic energy a turbine can extract, 16 over 27 or about 0.593. Real turbines achieve power coefficients of 0.35 to 0.45.
- Performance ratio of PV
- Actual PV energy yield divided by the yield expected at standard test conditions. Values of 0.75 to 0.85 account for temperature, soiling, inverter and wiring losses.
- PV temperature coefficient
- The fractional change in module power per kelvin above 25 degrees Celsius, typically minus 0.3 to minus 0.45 percent per kelvin. Hot modules therefore produce less than rated output.
- Feed-in tariff
- A guaranteed payment per kilowatt-hour for renewable generation exported or generated over a fixed contract term. Hong Kong operates technology and capacity banded rates under CLP and HK Electric schemes.
- IPMVP Option C
- A measurement and verification approach that uses whole-facility metered energy, with a regression baseline adjusted for weather and activity, to determine savings from a retrofit programme.
- Simple payback period
- Capital cost divided by annual energy cost saving, expressed in years. It ignores the time value of money and any savings beyond the payback period.
- Affinity laws
- For a centrifugal fan or pump, flow varies with speed, head with speed squared, and shaft power with speed cubed. Halving speed cuts power to about one eighth.
- Load duration curve
- A plot of load against the hours per year it is equalled or exceeded. It shows how much time peak plant runs and helps size generation and demand-side measures.
- Chiller kW per RT
- Cooling power input in kilowatts per refrigeration ton of cooling delivered, related to COP by 3.517 divided by COP. Water-cooled chillers typically reach 0.55 to 0.65.
- Low delta-T syndrome
- A condition where chilled water returns too warm, giving a small supply-to-return difference. Flow must rise, pumping energy increases and more chillers are forced on.
- Power factor correction
- Adding capacitors to raise power factor toward unity, reducing kVA demand, cable losses and utility penalties. Capacitor kVAr equals kW times the tangent difference of the two angles.
- Demand-controlled ventilation
- Modulating outdoor air intake using CO2 or occupancy sensors instead of a fixed design rate. It saves fan and cooling energy where occupancy varies through the day.
- Levelised cost of energy
- Total discounted lifetime cost divided by discounted lifetime energy output, giving a cost per kilowatt-hour. It excludes system integration and flexibility costs of variable generation.
- Scope 2 emissions
- Indirect greenhouse gas emissions from purchased electricity, heat, steam or cooling, calculated by multiplying consumption by a grid emission factor. Reported location-based or market-based.
- Marginal abatement cost curve
- A ranking of measures by cost per tonne of carbon dioxide equivalent abated, with negative-cost measures on the left. It guides which measures to implement first.
- Fuel clause adjustment
- A tariff component that passes through changes in fuel cost to customers, adjusted periodically. It separates fuel price risk from the basic charge for capacity and network.
- Retro-commissioning
- A systematic process of testing and tuning existing building systems to meet current operating needs. It typically delivers 5 to 15 percent energy savings at low capital cost.
- Lockout tagout
- A hazardous energy control procedure isolating and locking all energy sources before maintenance, with isolation verified by test rather than assumed from a drawing.
- Environmental permit
- An approval required under the Environmental Impact Assessment Ordinance before constructing or operating designated projects, setting binding conditions on emissions, noise and ecology.
- HKIE Code of Conduct
- The professional obligations of HKIE members: integrity, competence within one's field, priority of public safety, and written disclosure of conflicts of interest.
- Continuing professional development
- Documented ongoing learning required to maintain professional registration, covering technical and non-technical subjects and recorded against a minimum annual hours requirement.
- Signing and sealing work
- Certifying personal technical responsibility for a design or report. A member should sign only work personally supervised or reviewed and should record the basis of judgement.